ARTESYN LCM1500
1500 Watts Bulk Front End
Advanced Energy’s Artesyn LCM1500 series provide for a
very wide range of AC-DC embedded power requirement.
Featuring high build quality with robust screw terminals,
long life, and typical full-load efficiency of greater than 89
percent, these units are ideal for use in industrial and medical
applications. They are backed by a comprehensive set of
industrial and medical safety approvals and certificates.
Variable-speed ‘Smart Fans’ draw on software controls
developed by Advanced Energy to match fan speed to the
unit’s cooling requirement and load current. Slowing the fan
not only saves power but also reduces wear, thus extending
its life.
SPECIAL FEATURES
COMPLIANCE
1500 W output power
EMI Class A
Low cost
EN61000 Immunity
2.5” x 5.2” x 10.0”
RoHS3
12 Watts per cubic inch
Industrial/Medical safety
-40 °C to 70 °C with derating
Optional 5 VDC @ 2 A housekeeping
High efficiency: 89% typical
Variable speed “Smart Fans”
DSP controlled
Conformal coat option
± 10% adjustment range
Margin programming
OR-ing FET
AT A GLANCE
Total Power
1500 W
# of Outputs
Single
Outputs
12 to 48 VDC
Optional 5 VDC standby
SAFETY
UL/cUL Recognized ITE
(UL/CSA62368-1)
UL/cUL Recognized Medical
(ANSI/AAMI ES60601-1)
TUV-SuD ITE + Medical
(EN62368-1 and EN60601-1)
CE LVD (EN62368-1 + RoHS)
BSMI
CB Report
CE and UKCA Mark
· through Demko for IEC60950-1
· through TUV-SuD for IEC60601-1
©2022 Advanced Energy Industries, Inc.
LCM1500
ELECTRICAL SPECIFICATIONS
Input
Input range
90 to 264 VAC (Operating)
115/230 VAC (Nominal)
Terminal Block
Frequency
47 to 440 Hz, Nominal 50/60
Input fusing
Internal 30 A fuses, both lines fused
Inrush current
≤ 25 A peak
Power factor
0.99 typical, meets EN61000-3-2
Harmonics
Meets IEC 1000-3-2 requirements
Input current
18 A RMS max input current, at 100 VAC
Hold up time
14 ms minimum for main O/P, at full rated load
Efficiency
> 89% typical at full load / 230 VAC nominal
Leakage current
< 400 μA @ 240 VAC for UL test method
Isolation voltage
PRI-Chassis 2087 VAC Basic
PRI-SEC 4000 VAC Reinforced 2xMOPP
SEC-Chassis 250 VDC
LCM1500Q Efficiency Without the 5 Vsb
92.00
90.00
88.00
Efficiency %
86.00
100 Vac
230 Vac
84.00
82.00
80.00
78.00
76.00
25
50
75
Loading %
2 advancedenergy.com
100
LCM1500
ELECTRICAL SPECIFICATIONS
Output
Output rating
See Ordering Information Table
Set point
± 0.5%
230 VAC @ half load
Total regulation
Main Output: ± 2.0%
5 Vsb: ± 5%
Combined line/load/temperature change, warm-up drift
when measured at output terminal
Rated load
1500 W maximum
Derate linear to 50% from 50 °C to 70 °C
Minimum load
Main Output @ 0A
5 Vsb @ 0A
No loss of regulation
Output ripple
Main Output: 1% max p-p
5 Vsb: 50 mV max p-p
Measured with 0.1 μF Ceramic and 10 μF Tantalum
Capacitor on any output, 20 MHz
No overshoot/undershoot outside the regulation band
during on or off cycle
Output voltage overshoot
Transient response
Peak Deviation: ± 4%
Setting time < 300 μS
Max units in parallel
50% load step @ 1 A/μs
Step load valid between 10% to 100% of output rating
Recovery time to within 1% of set point at onset of
transient
Up to 4
Remote sense
Compensation up to 500 mV
Short circuit protection (SCP)
Protected, no damage to occur
Bounce mode
Overcurrent protection (OCP)
105% to 125%
120% to 170%
Main output (Bounce mode)
5 Vsb output (Bounce mode)
Overvoltage protection (OVP)
125% to 145%
110% to 125%
Main output (Latch mode)
5 Vsb output (Latch mode)
Overtemperature protection (OTP)
55 °C to 65 °C ambient temperature
Shut down and auto-recover
ENVIRONMENTAL SPECIFICATIONS
Operating temperature range
-40 °C to +70 °C linear derating to 50% from 50 °C to 70 °C. For "L" version linear derating starts at 45 °C
Storage temperature
-40 °C to +85 °C
Humidity
10% to 95% Non-operating. 20-90% operating. Conformal coat option available
Altitude
Operating - 16,404 feet (5000 m)
Storage - 30,000 feet (9144 m)
Shock
MIL-STD-810F 516.5 Procedure I, VI Storage
Vibration
MIL-STD-810F 514.5 Cat. 4, 10 Storage
Fan noise
< 45 dBA, 80% load at 30 °C. For the "L" version, the noise is < 61dBA at 80% load at 25 °C
advancedenergy.com
3
LCM1500
ORDERING INFORMATION TABLE 1
Nominal
Output
Voltage Set
Point
Set Point
Tolerance
Adjustment
Range
12 V
12 V
±0.5%
Model
Number
Output
LCM1500L
Min
Max
Output
Ripple
P/P (0-50 ˚C)
10.8 - 13.2 V
0A
133 A
120 mV
1500 W
2%
Current
Max
Continuous
Power
Combined Line/
Load Regulation
LCM1500N
15 V
15 V
±0.5%
13.5 - 16.5 V
0A
100 A
150 mV
1500 W
2%
LCM1500Q
24 V
24 V
±0.5%
21.6 - 26.4 V
0A
67 A
240 mV
1500 W
2%
LCM1500R
28 V
28 V
±0.5%
25.2 - 30.8 V
0A
53 A
280 mV
1500 W
2%
LCM1500U
36 V
36 V
±0.5%
32.4 - 39.6 V
0A
43 A
360 mV
1500 W
2%
LCM1500W
48 V
48 V
±0.5%
43.2 - 52.8 V
0A
33 A
480 mV
1500 W
2%
Note: LCM1500Q is 80 PLUS® certified
ORDERING INFORMATION TABLE 2
LCMXXXXY
-
Case Size
A
Input Termination
-
B
-
C
-
###
Acoustic Noise
Option Codes*
Hardware Code
Blank = Standard
Blank = No Options
Factory Assigned for
Modiefied Standards
1-Phase input where XXXX =
1500 = 2.5” x 5.2” x 10.0”, 1500W
T = Terminal Block
Voltage Code Y =
1 = Conformal Coat
2 = Reverse Air
Code
3 = Opt 1 + 2
L
12
4 = 5V Standby
N
15
5 = Opt 1 + 4
Q
24
6 = Opt 2 + 4
R
28
7 = Opt 1 + 2 + 4
U
36
8 = Constant Current
W
48
9 = Opt 1 + 8
B = Opt 2 + 8
C = Opt 1 + 2 + 8
D = Opt 4 + 8
E = Opt 1 + 4 + 8
F = Opt 2 + 4 + 8
G = Opt 1 + 2 + 4 + 8
*Note: Some option code combinations may not be configured yet and will require extra leadtime the first time they are requested.
4 advancedenergy.com
LCM1500
MECHANICAL DRAWINGS (LCM1500Q-T, LCM1500R-T,LCM1500U-T and LCM1500W-T)
Notes:
MOUNTING LOCATIONS SCREW
PENETRATION DEPTH IS 4.6 mm MAX.
RECOMMENDED SCREW TORQUE:
M3.5 x 0.6P = 6 - 8kgf-cm
M4.0 x 0.7P = 8 - 10kgf-cm
Bus bar adapter (option)
P/N 500-006848-0000
advancedenergy.com
5
LCM1500
MECHANICAL DRAWINGS (LCM1500L-T and LCM1500N-T)
Notes:
1. Parts must be completely assembled.
2. Quality controlled dimensions. These dimensions to be included in the mechanical CPK of 1.33
3. C asing parts used must have matching color. In order to ensure color matching of parts, it is required that the raw material that will be processed by the fabricator will come from the
same supplier and the sheetmetal fabricator for all matching parts must be the same. To avoid color variations on the same lot delivered, all parts with matching color requirement
should be delivered as a set by the fabricator.
5. S
heared edges visible to the customer should have no rust formation. If rust formation is present then a concealing layer of silver ink or some other substitute should be applied on
the rusted area.
6. Mounting locations screw penetration depth is 4.6mm max.
7. Recommended screw torque:
M3.5X0.6P = 6-8kgf-cm
M4.0X0.7P = 8-10kgf-cm
8. Input: terminal block type. M4 screw torque value of 16kgf-cm using wire gauge 18-10 (13mm centers)
6 advancedenergy.com
LCM1500
PIN ASSIGNMENT
SIGNALS
DESCRIPTION
PIN #
+Vout
Power Rail
SK3
GND
Power Ground
SK4
SIGNALS
DESCRIPTION
SK2 PIN NUMBER
A2
EEPROM Address
1
-VPROG
Return Connection of External Supply for Margin Programming
2
A1
EEPROM Address
3
-Vsense
Remote Sense Return
4
ISHARE
Load Share Voltage
5
A0
EEPROM Address
6
SDA1
Serial Data Signal (I2C)
7
+VPROG
Positive Connection of External Supply for Margin Programming
8
SCL1
Serial Clock Signal (I2C)
9
+Vsense
Remote Sense Positive
10
5VSB
5 V Standby
11
GND
5 V Standby Return
12
5VSB
5 V Standby
13
G_DCOK_C
Global DCOK Collector
14
GPIOA6
EEPROM Write Protect
15
G_DCOK_E
Global DC_OK Emitter (GND)
16
GND
Return GND for O/P Signal and I2C communication
17
G_ACOK_C
Global AC_OK Collector
18
INH_EN
Turn Off Main Output
19
G_ACOK_E
Global AC_OK Emitter (GND)
20
Note: Mating connector for SK2 is:
LANDWIN
(LWE PN: 2050S) Housing
(LWE PN: 2053T) Contact
CVILUX
(CX PN: CI0120SD000) Housing
(CX PN: CI01TD21PE0) Contact
Signal Output Signal Connectors (SK2)
PSU Front View (24V & 48V UNITS)
CI0120P1HD0-LF
advancedenergy.com
7
LCM1500
PIN ASSIGNMENT (CONTINUED)
LED INDICATORS
2 provided are clearly visible up to a 45 degree offset from vertical with office environment ambient lighting. The status is reflected in the indicator
color.
The DC_OK LED shall light green if the DC output is within specification, and shall be off if the output falls out of specification.
The AC_OK LED is green if the AC within specification and off when AC out of specification.
CONTROL SIGNALS
AC_OK open collector 0.5 V maximum at 10 mA. Both emitter and collector access provided.
DC_OK open collector 0.5 V maximum at 10 mA. Both emitter and collector access provided.
PS_INHIBIT/ENABLE Signal 0.0 to 0.5 V contact closure, output OFF
OPTIONAL ACCESSORIES
PIN 20
PIN 19
PIN 2
PIN 3
PIN 1
300 ± 5 mm
Orderable kit part number: 73-788-001
PIN 20
PIN 19
PIN 2
PIN 3
PIN 1
Orderable kit part number: 73-788-002
8 advancedenergy.com
LCM1500
MISCELLANEOUS SPECIFICATIONS
BURN-IN
100% Burn-in at 45 °C, at 80% to 90% load. Duration of burn-in determined by Quality Assurance Procedures.
MTBF
The power supply has a minimum MTBF of 300K hours using the Bell core 332, issue 6 specification @ 25 °C and 40 °C, ambient, at full
load. With the power supply installed in a system in a 25 °C ambient environment and operating at full load, capacitor life shall be 10 years,
minimum for all electrolytic capacitors contained within this power supply. The power supply shall demonstrate a MTBF level of
> 500,000 hours.
QAV
Full QAV testing shall be conducted in accordance with Advanced Energy standards.
WARRANTY
Artesyn Embedded Power shall warrant the power supply to be free of defects in materials and workmanship for a minimum period of
three years from the date of shipment, when operated within specifications. The warranty shall be fully transferable to the end owner of the
equipment powered by the supply.
advancedenergy.com
9
ABOUT ADVANCED ENERGY
Advanced Energy (AE) has devoted more than three
decades to perfecting power for its global customers. AE
designs and manufactures highly engineered, precision
power conversion, measurement and control solutions for
mission-critical applications and processes.
Our products enable customer innovation in complex
applications for a wide range of industries including
semiconductor equipment, industrial, manufacturing,
telecommunications, data center computing, and medical.
With deep applications know-how and responsive service
and support across the globe, we build collaborative
partnerships to meet rapid technological developments,
propel growth for our customers, and innovate the future
of power.
For international contact information,
visit advancedenergy.com.
powersales@aei.com (Sales Support)
productsupport.ep@aei.com (Technical Support)
+1 888 412 7832
Specifications are subject to change without notice. Not responsible
for errors or omissions. ©2022 Advanced Energy Industries, Inc. All rights
reserved. Advanced Energy®, AE® and Artesyn™ are U.S. trademarks
of Advanced Energy Industries, Inc.
ENG-LCM1500-235-01.03.04.22