SGX-1505FB220A380A25ZL 数据手册
SGX-1505FB
“HOCKEY PUCK” SOLID STATE RELAY 10 THRU 40 AMPS 48 TO 380 VRMS
FEATURES • Photo isolation • Up to 800V blocking voltage • Both “Zero Voltage” and phase controllable “Random” Switching versions • High surge capability • Built-in snubber • UL, CUR file E43203 • Triac Output Circuitry INPUT Type
Control Voltage Range Turn On Voltage Turn Off Voltage Max. Input Current Max. Reverse Voltage DC Input 3 to 32 VDC 3 VDC Max 1 VDC Min. 25 mA -32 VDC 24 VAC 19.2 to 28.8 VAC 19.2 VAC Max. 2 VAC Min. 15 mA 110 VAC 85 to 132 VAC 85 VAC Max. 10 VAC Min. 15 mA 220 VAC 175 to 264 VAC 175 VAC Max. 10 VAC Min. 15 mA -
OUTPUT
Type Output Voltage Range Blocking Voltage Max. Leakage Current (off) Max. Voltage Drop (at rated current) Max. Turn-On Time 240 48 to 264 VAC 600 Vpk 5 mA 380 48 to 380 VAC 800 Vpk 5 mA 1.5 VRMS Random Turn On (DC input): 1 ms Zero Cross Turn On (DC input): 1/2 cycles + 1 ms AC Input: 20 ms DC Input: 1/2 cycle + 1 ms AC Input: 40 ms 200 V/us 0.5 480 48 to 530 VAC 1200 Vpk 5 mA
Max. Turn-Off Time
Min. Off-State (dv/dt) Min. Power Factor
GENERAL
Dielectric Strength Insulation Resistance Max. Capacitance (in/out) Ambient Temperature 4000 Vrms min. (at 50/60 Hz, 1 min.) 1000 Min. (at 500 VDC) 8 pf Operating: -30°C (-22°F) to 80°C (176°F) Storage: -30°C (122°F) to 100°C (212°F) Panel Mount Termination Weight Screw 88g
1/13/06W
SGX-1505FB
RELAY ORDERING DATA SGX-1505FB
MODEL
D
INPUT VOLTAGE D: 3 TO 32 Vdc 24A: 24 Vac* 110A: 110 Vac* 220A: 220 Vac*
240
OPERATING VOLTAGE RANGE 240:48 TO 264 Vac 380: 48 to 380 Vac
A
LOAD TYPE A: AC LOAD
40
LOAD CURRENT 10: 15: 20: 25: 40: 10A 15A 20A 25A 40A
Z
ZERO CROSS OR RANDOM Z: Zero cross turn on P: Random turn on
L
LED INDICATOR NIL: no LED L: with LED (not for AC input type)
*UL pending
MECHANICAL DATA
Outline Dimensions
2-M.118 [M3.0]
2-M.157 [M4.0]
1.870 [47.5] 2-M.157 [M4.0]
.795Max [20.2]
.902Max [22.9]
Wiring Diagram Load power supply
Load
1.870 [47.5]
4
1.00 [25.4] .449 [11.4]
1
1.098 [27.9] 1.799 Max [45.7]
1
LOAD
2
3
2-Ø.177 [Ø4.5] 1.743 [44.26] 2.299 Max [58.4]
2 -4
.323 [8.2]
INPUT
3+
input control signal
Dimensions in inches with metric equivalents in parentheses. Tolerance: ± .010"
INSTALLATION
1. When mounting the relays side by side, provide a space equivalent to the width of a single SSR between two adjacent SSRs. Otherwise, reduce the load current flow to 1/2 to 1/3 of the rated current. When mounting relays on heat sink surface, first apply a heat conductive grease to the metal back surface of the SSR. Press the SSR firmly onto the heat sink to ensure a good seal. Screw the SSR down to the heat sink. Next, wire the screw terminals and securely tighten the screws.
PRECAUTIONS
1. Before connecting a load that generates a high surge current, such as a lamp load to the SSR, make sure that the SSR can withstand the surge current of the load. The product data sheet shows the non-repetitive peak value of the surge current that flows through the SSR. Normally, use 1/2 of the non-repetitive peak surge current as the standard value. If a surge current exceeding that value is expected, connect a quick-blowing fuse to protect the SSR.
2.
2.
3.
1/13/06W
SGX-1505FB
CHARACTERISTIC CURVES 10 Amp Model 15 Amp Model
20 Amp Model
25 Amp Model
40 Amp Model
F=50Hz
1/13/06W
SGX-1505FB220A380A25ZL 价格&库存