VRLA Rechargeable Battery
BC75-12
Measures
Technology
Values
Innovation
(BC75-12FR)
FEATURES
Maintenance free(no water topping-up required)
No free acid(Non-spillable battery)
Can be used in any orientation(excluding used inverted)
Carry handles for easy installation
Absorbent Glass Mat technology for efficient gas recombination
Its design life is up to 5 years in floating application
APPLICATION
UPS
Golf-Carts
TELECOM
SPECIFICATIONS
Nominal Voltage
12V
75.0 Ah
71.3 Ah
63.8 Ah
45.0 Ah
20 Hour Rate (3.75A, 10.5V)
10 Hour Rate (7.13A, 10.5V)
5 Hour Rate (12.75A, 10.5V)
1 Hour Rate (45.00A, 9.3V)
Nominal Capacity
Approx. Weight
BC75-12:
ABS: UL 94-HB (Dark gray color)
BC75-12FR:
ABS: UL 94-V0 (Light gray color)
20.2Kg(44.53lbs.)
Terminals
B5 (Fitting M6 bolt & nut) I2 is optional
Max. Discharge Current
750 A (5 sec.)
Max. Charge Current
22.5 A
0oC~40oC(32oF~104oF)
-20oC~50oC(-4oF~122oF)
-20oC~40oC(-4oF~104oF)
Charge
Operating Temperature
Range
CONTAINER MATERIAL
Discharge
Storage
o
Self Discharge
< 3% per month (25 C)
Internal Resistance
8m
OUTER DIMENSIONS mm(inch)
ISO14001
UL
CE
IEC61056
JIS C 8702
GB/T 19639
(Fully Charged )
Length (L)
350±2.0(13.78±0.08)
ISO 9001
Width (W)
166±2.0(6.54±0.08)
Container Height (H)
174±2.0(6.85±0.08)
Total Height (TH)
174±2.0(6.85±0.08)
TERMI NAL TYPE
Terminal I2
Terminal B5
M6x1.0
[M6 BOLT & NUT]
2.0(0.08)
19.0(0.75)
174 ± 20(6.86 ± 0.08)
7.0(0.28)
16 6 ± 2.0 (6. 54 ± 0.08)
35 0 ± 2.0 (13. 78 ± 0.08)
7.0(0.28)
6.3 (0.25)
21.0 (0.83)
[M6 BOLT]
Terminal Hardware Initial Torque: B5,I2(5.5Nm±5%)
o
o
BC75-12 (BC75-12FR) discharge characteristics (25 C/77 F)
Battery Charging Characteristics
(Typical examp le of t he charge characteristics for the standby us e)
13.0
0.21
15.0
0.18
14.0
140
10.0
0.6CA
9.0
8.0
2.5CA 2CA
7.0
1
2
3
5
10
1CA
20 30
0.15
0.12
0.09
0.06
120
Charge vo ltag e
l um e
C ha r ge vo
13.0
100
1 Battery : BC65 -12
2 Disc ha rge
10 0 %(0.05 CA x 20 h)
50 %(0.05 CA x 10 h)
3 Con stan t vo ltage ch arg ing
Cha rge vo ltage :2.27 5V /cell
Cha rge cu rrent:0.1C A
4 Tem pe rature:2 5℃(77 ℉)
12.0
11.0
80
60
10.0
40
0.03
60
2
3
5
10
20
Charge cu rr ent
20 30
0
Hr
Min
Charge volume(%)
0.17CA 0.095CA 0.05CA
0.25CA
Charge voltage(V)
11.0
Charge current(CA)
Terminal Voltage(V)
12.0
0
0
5
10
15
20
0
25
Charge time (hr)
Discharge time
Effect Of Temperature On Long Term Float Life
Application
Charging
method
Charging time
O
0.1CA, 25 C
(h)
Charging Temperature Max. charging
compensation
current
Voltage
coefficient of
(CA)
at 25OC
voltage
100%
50%
(V/cell) charging
(mV/ OC/cell)
discharge discharge
Constant
voltage & 2.25~2.30
Constant
current
charging
For
(with current
cycle service restriction) 2.40~2.50
For standby
power Source
-3
0.3
24
Temp
( OC)
20
Life expectancy(year)
Charging Procedure
0~40
(32~ 104 OF)
-4
0.3
16
10
8
6
5
4
3
2
1
0.5
20
68
10
30
86
50°C
122°F
40
104
Battery temperature
Constant power discharge characteristics at 25 oC/77 oF
Discharge
Time
Charging voltage :
2.275V/cell
Unit: W
5 Min
10 Min
15 Min
30 Min
1 Hr
3 Hr
5 Hr
10 Hr
20 Hr
1.80V
1885.0
1537.0
1254.8
850.0
534.9
218.7
150.75
84.23
44.33
1.75V
2118.3
1664.5
1312.2
882.8
551.0
223.0
153.00
85.50
45.00
1.70V
2317.6
1721.9
1352.1
902.8
560.9
225.0
153.83
85.95
45.23
1.65V
2422.2
1763.3
1383.8
915.6
567.7
226.6
154.35
86.18
45.38
1.60V
2502.3
1801.6
1410.8
924.8
573.3
227.9
154.80
86.18
45.38
F.V.
(V/cell)
Constant current discharge characteristics at 25 oC/77 oF
Discharge
Time
Unit: A
5 Min
10 Min
15 Min
30 Min
1 Hr
3 Hr
5 Hr
10 Hr
20 Hr
1.80V
171.6
138.6
112.2
72.8
44.9
18.2
12.60
7.05
3.68
1.75V
196.3
150.2
117.2
75.6
46.3
18.6
12.75
7.13
3.75
1.70V
214.8
155.5
120.9
77.3
47.2
18.8
12.83
7.20
3.75
1.65V
228.7
162.2
123.7
78.3
47.7
18.9
12.90
7.20
3.75
1.60V
240.8
168.6
126.1
79.2
48.1
19.0
12.90
7.20
3.75
F.V.
(V/cell)
All data shall be changed without prior notice, BB reserves the right to explain and update the information contained hereinto.
Trial A/0
USA:
B&B BATTERY(USA) INC.
6415 RANDOLPH ST.COMMERCE,CA,90040 U.S.A.
TEL:1-323-278-1900.1-800-278-8599
FAX:1-323-278-1268
E-Mail:sales@bb-battery.com
CHINA FACTORY:
B.B. BATTERY CO., LTD.
CHENG DONG TRIAL AREA,HUANG GANG,
RAOPING, GUANG DONG,CHINA,515700
TEL:86-768-7601001-2
FAX:86-768-7601469
E-Mail:maggy@bb-battery.com
Web Site: http://www.bb-battery.com
REV. May. 2011
EUROPE:
B&B BATTERY(EUROPE) B.V.
SUITE 8, HAAKSBERGWEG 33, 1101
BP AMSTERDAM,THE NETHERLANDS
TEL: 31-30-3200190
MOBILE: 886-933896989
E-Mail: gary@bb-battery.com
JAPAN:
B&B BATTERY(JAPAN) CO., LTD.
1375-11 NARAHARA-MACHI,HACHIOJI,
TOKYO 193-0803,JAPAN.
TEL:81-426-25-6375
FAX:81-426-25-6375
E-Mail:miyata@bb-battery.com
HONG KONG:
B&B BATTERY(Hong Kong) Co.
TEL:852-2311-4918
FAX:852-2739-1182
E-Mail:bbhk@hkstar.com
TAIWAN:
B.B. BATTERY(TAIWAN) CO., LTD.
TEL:886-6-502-5150
FAX:886-6-589-8087
E-Mail:kevin@bb-battery.com
Powered by
B.B. Battery Co., Ltd.
很抱歉,暂时无法提供与“BC75-12”相匹配的价格&库存,您可以联系我们找货