VRLA Rechargeable Battery
BP12-12 (BP12-12FR)
FEATURES
Maintenance free(no water topping-up required). No free acid(Non-spillable battery). Low self-discharge rate, lower than 3% capacity loss per month. Can be used in any orientation(excluding used inverted).
Measures
T echnology
Values
Innovation
APPLICATION
UPS Laboratory Equipment Toy-Cars Power Packs Fishing Lights
SPECIFICATIONS
Nominal Voltage Nominal Capacity Approx. Weight Terminals Internal Resistance Max. Discharge Current Max. Charge Current Operating Temperature Range
12 V 12.0Ah @ 20 hour rate F.V.(1.75V/cell) 3940g(8.69lbs.) T2 (Faston Tab 250) T1 is optional 18m (Fully Charged ) UL CE IEC61056 JIS C 8702 GB/T 19639 VdS G102106 180 A (5 sec.) 3.6 A Charge 0oC~40oC(32oF~104oF) Discharge -20oC~50oC(-4oF~122oF) Storage. -20oC~40oC(-4oF~104oF) ABS(UL94-HB, UL94-V0 is optional) ISO14001 ISO 9001
Container Material DIMENSION(mm/inch) Length 151±1.5 (5.94±0.06) Width 98±1.5 (3.86±0.06)
151 98 2(3.86 0.08) 94 1.5(3.7 0 0.6) 1.5(5.94
OUTER DIMENSIONS
TERMINAL TYPE
Terminal T1
3.2(0.13) 4.75(0.19)
Terminal T2
3.4(0.13)
0.06)
98
1.5(3.86
0.06)
Total Height 98±2.0 (3.86±0.08)
Constant power discharge characteristics at 25 oC/77 oF
F.V. (V/cell) Discharge Time
Unit: W
3 Hr
35.0 35.7 36.0 36.3 36.5
5 Min
433.9 502.2 533.6 557.5 576.0
10 Min
319.4 346.0 358.5 367.1 374.4
15 Min
256.0 267.7 276.0 282.4 288.0
30 Min
152.3 158.1 161.7 164.0 165.6
o
1 Hr
87.3 90.0 91.6 92.7 93.6
o
5 Hr
24.1 24.5 24.6 24.7 24.8
0.8(0.03)
Container Height 94±1.5 (3.70±0.06)
6.35(0.25)
7.85(0.31)
10 Hr
13.48 13.68 13.75 13.79 13.79
20 Hr
7.09 7.20 7.24 7.26 7.26
1.80V 1.75V 1.70V 1.65V 1.60V
Discharge Time
Constant current discharge characteristics at 25 C/77 F
F.V. (V/cell)
Unit: A
3 Hr
2.91 2.97 3.00 3.02 3.04
5 Min
39.09 46.07 48.95 51.15 52.84
10 Min
28.12 30.46 31.55 32.31 32.96
15 Min
22.26 23.28 24.00 24.55 25.04
30 Min
12.91 13.40 13.70 13.89 14.03
1 Hr
7.34 7.56 7.70 7.79 7.87
5 Hr
2.01 2.04 2.05 2.06 2.06
10 Hr
1.123 1.140 1.146 1.149 1.149
20 Hr
0.591 0.600 0.603 0.605 0.605
1.80V 1.75V 1.70V 1.65V 1.60V
A/0 REV. Jul. 2009
All data shall be changed without prior notice, BB reserves the right to explain and update the information contained hereinto.
Powered by
B.B. Battery Co., Ltd.
很抱歉,暂时无法提供与“BP12-12FR”相匹配的价格&库存,您可以联系我们找货