VRLA Rechargeable Battery
BP13-6 H (BP13-6FR H)
FEATURES
Maintenance free(no water topping-up required). No free acid(Non-spillable battery). Low self-discharge rate, lower than 3% capacity loss per month. Can be used in any orientation(excluding used inverted).
Measures
T echnology
Values
Innovation
APPLICATION
UPS Electronic Toy-Cars Emergency Lights Rechargeable Flash Lights Fans
SPECIFICATIONS
Nominal Voltage Nominal Capacity Approx. Weight Terminals Internal Resistance Max. Discharge Current Max. Charge Current Operating Temperature Range
6V 13.0Ah @ 20 hour rate F.V.(1.75V/cell) 2500g(5.51lbs.) Type H 9m (Fully Charged ) UL CE IEC61056 JIS C 8702 GB/T 19639 30 A (5 sec.) 3.9 A Charge 0oC~40oC(32oF~104oF) Discharge -20oC~50oC(-4oF~122oF) Storage. -20oC~40oC(-4oF~104oF) ABS(UL94-HB, UL94-V0 is optional) ISO14001 ISO 9001
Container Material DIMENSION(mm/inch) Length 108±1.5 (4.25±0.06) Width
OUTER DIMENSIONS
TERMINAL TYPE
Terminal H
9.5(0.37)
31.4(0.84)
o o
Container Height 140±1.5 (5.51±0.06) Total Height 140±1.5 (5.51±0.06)
Constant power discharge characteristics at 25 C/77 F
F.V. (V/cell) Discharge Time
Unit: W
5 Hr
13.06 13.26 13.33 13.38 13.42
15 Min
138.6 145.0 149.5 152.9 156.0
30 Min
82.5 85.6 87.6 88.8 89.7
1 Hr
47.3 48.7 49.6 50.2 50.7
o
3 Hr
18.9 19.3 19.5 19.6 19.8
o
15.6(0.61)
71±1.5 (2.80±0.06)
10 Hr
7.30 7.41 7.45 7.47 7.47
20 Hr
3.84 3.90 3.92 3.93 3.93
1.80V 1.75V 1.70V 1.65V 1.60V
Constant current discharge characteristics at 25 C/77 F
F.V. (V/cell) Discharge Time
Unit: A
5 Hr
2.177 2.210 2.222 2.230 2.237
15 Min
24.1 25.2 26.0 26.6 27.1
30 Min
14.0 14.5 14.8 15.1 15.2
1 Hr
7.95 8.19 8.34 8.44 8.52
3 Hr
3.16 3.22 3.25 3.27 3.29
10 Hr
1.217 1.235 1.241 1.245 1.245
20 Hr
0.640 0.650 0.653 0.655 0.655
1.80V 1.75V 1.70V 1.65V 1.60V
A/0 REV. Jul. 2009
All data shall be changed without prior notice, BB reserves the right to explain and update the information contained hereinto.
Powered by
B.B. Battery Co., Ltd.
很抱歉,暂时无法提供与“BP13-6FRH”相匹配的价格&库存,您可以联系我们找货