Product Data Sheet
50 AMP MODULAR SWITCHED MODE RECTIFIER
RM4850
FEATURES
• • • • • • • SWITCHED MODE >.99 PFC >90% EFFICIENCY AUTOMATIC LOAD SHARING HOT-SWAP CAPABLE COMPACT SIZE SHELF MOUNTED
• SOFT START TURN-ON • ESD TO 20,000 VOLTS • -40°C TO 65°C FULL OPERATION WITHOUT DERATING • • • • REMOTE EMERGENCY POWER DISCONNECT ! TELECOM BULK POWER RATED! BELLCORE COMPLIANT INFINITE, FULL CURRENT SHORT CIRCUIT CAPABLE! BUILT-IN AC & DC DISCONNECTS FRONT PANEL METER BATTERY OR BATTERYLESS OPERATION INTELLIGENT HIGH VOLTAGE SHUTDOWN GUARANTEED NO SINGLE COMPONENT FAILURE CAN LEAD TO OUTPUT HIGH VOLTAGE! GUARANTEED SAFE OPERATION TO 300 VAC ENVIRONMENTALLY HARDENED! THD 90 >.99
Units
VAC A %
MEASUREMENTS OF RM4850
Module Weight Height Depth Width Shelf* Weight Height Depth Width 25 lbs. 7U (12.25”) 15.25” 5” 18 lbs. 7U (12.25”) 15.25” maximum 23” rack mount
* These measurements are specifically for the 200A Power Shelf for up to 4 quantity RM4850 Please contact the factory for other shelf and power plant options.
GENERAL FEATURES
Hot Swappable Modules These shelf-mounted modules are easy and safe to install or remove while system is operational without affecting the overall system’s performance. Parallel Operation and Automatic Load Sharing Forced or passive load sharing is available between modules of the same operating voltages in parallel applications. Current Limit The Current Limit is adjustable between 0A to 50A. Upon exceeding this limit, the rectifier automatically reduces output voltage. Safety UL/CUL Recognized: UL 1950/CSA 950. File Number: E181908
Alarm Outputs Rectifier Fail Alarm Equalize Occurring High Voltage Occurring Temporary Restraint Occurring Thermal Shutdown Occurring Open Sense Lead Has Occurred Low Current Alarm AC Power Has Failed Alarm Rectifier Fan Has Failed Alarm DC Breaker Is Open Alarm AC Breaker Is Open Alarm (RFA) (EQO) (HVO) (TRO) (THSD) (OS) (LCA) (ACF) (FF) (DCBKR) (ACBKR)
Control Inputs High Voltage Shutdown Restart Equalize Temporary Release Emergency Shutdown (HVSD) (RS) (EQ) (TR)
}
}
All control inputs are initiated with a ground closure
(EMSD)
24VAC voltage reference to ground
Note: All alarms are “Form A” relay type contacts
Page 2
RM4850 4/98 REV A
Output Specifications
Parameter
Voltage Adjustment Range float voltage equalize voltage 0-100% load within specified input voltage and frequency range within a 10 - 100% rating nominal AC line 48 48 ± 0.5 ±10 >16