Contact Factory for Replacement Model
Input Specifications
Parameter
Operating Range Current Efficiency Power Factor Correction (PFC)
Conditions
45 - 65 Hz, single phase, no taps required Adjustable
Min
183
Typ
Max
264 27 >85 >.99
Units
VAC A %
MEASUREMENTS OF RM24150
Module Weight Height Depth Width Shelf* Weight Height Depth Width 25 lbs. 7U (12.25”) 15.25” 5.1” 18 lbs. 7U (12.25”) 15..25” maximum 23” rack mount
*These measurements are specifically for the 600A Power Shelf for up to 4 quantity RM24150. Please consult factory for other shelf and power plant options.
GENERAL FEATURES
Hot Swappable Modules These shelf-mounted modules are easy and safe to install or remove while system is operational without affecting the overall system’s performance. Parallel Operation and Automatic Load Sharing Forced or passive load sharing is available between modules of the same operating voltages in parallel applications. Current Limit The Current Limit is adjustable between 0A to 150A. Upon exceeding this limit, the rectifier automatically reduces output voltage. Safety UL/CUL Recognized: UL 1950/CSA 950 File Number: E181908.
Alarm Outputs Rectifier Fail Alarm Thermal Shutdown Occurring Open Sense Lead Has Occurred AC Power Has Failed Alarm DC Breaker Is Open Alarm AC Breaker Is Open Alarm (RFA) (THSD) (OS) (ACF) (DCBKR) (ACBKR)
Control Inputs High Voltage Shutdown Restart Equalize Temporary Restraint Emergency Shutdown (HVSD) (RS) (EQ) (TR) (EMSD)
}
}
All control inputs are initiated with a ground closure 24VAC voltage reference to ground
Note: All alarms are “Form A” relay type contacts
Page 2
A4RM24150 5/98 REV A
Output Specifications
Parameter
Voltage Adjustment Range float voltage equalize voltage Regulation Load Current Hold-Up Time Filtering Voice band Wide band noise ENVIRONMENTAL Temperature Operating Storage Humidity Altitude Heat Dissipation Audible Noise non-condensing -0 +32 -50 -58 0 0 0 2440 16 < 32