celduc®
r e l a i s
S/CON/SOM020200/A/08/12/05
PRELIMINARY DATA
Page 1/5 UK
MOSFET BASED DC SOLID-STATE RELAY
Latest MOSFET technology generation. Ultra low on-state resistance. Low output leakage current. Low control current consumption. Built-in overvoltage protection
SOM020200
Reverse protected triggered control input to avoid linear control Control voltage risks No radiated or conducted disturbances Touch protected housing IP20
Load voltage range Load current range
(with heatsink)
range Max. permanent output voltage Max. load current with heatsink
Dimensions (WxHxD) 45 x 58.5 x 30
3.5-32VDC 110VDC 20ADC
Weight
Control input voltage range
In & case / Out Insulation
Connections
5-110VDC Fig. 1
Up to 20A
3.5-32VDC
2.5kV Fig. 2
Screw terminals
80g
HIGH SIDE WIRING DIAGRAM (Load connected to “-“)
LOW SIDE WIRING DIAGRAM (Load connected to “+”)
See Instruction sheet to select the right protective components The red paths (C1/D2) must be as short as possible !
See Instruction sheet to select the right protective components The red paths (C1/D2) must be as short as possible !
Fig. 3
INTERNAL DIAGRAM
Proud Proud to serve you
Data given at Tambient=25°C and subject to modification without previous notice
r
celduc
e l a i
®
s
celduc®
r e l a i s
S/CON/SOM020200/A/08/12/05
PRELIMINARY DATA
Page 2/5 UK
CONTROL INPUT CHARACTERISTICS
INPUT CIRCUIT
CHARACTERISTIC Nom. Control voltage Min. Control current Control voltage range Control current consumption Releasing control voltage Max. reverse control voltage Input impedance LABEL Ucnom Icmin Uc Ic Ucoffmax -Ucmax Rin VALUE 12-24VDC 35mADC 3.5 – 32VDC 32 – 35mADC (for control voltage range) 1VDC 32VDC Current limitation INFO. -100µA/°C
typical ON=3.3V
See fig. 5
typical OFF= 2.6V
-Icmax+90°C 100°C @∆Tra=75°C @∆Tra=50°C
@Utmax @Tjmax @Iemax @Tjmax
VALUE 90VDC 5-110VDC 200V Varistor 75V size 20 1.5V Motor Please contact us
INFO.
Ue
@Ie=-20A @Uc=0
See fig. 7 (limits) See fig. 8
POWER CIRCUIT
See fig. 7
PROTECTION CHARACTERISTICS
Leakage current (Ielk) vs DC voltage (Ut)
Ielk / Ie
Absolute limits
1
Uto < Utp
t max = 0.75 (Uto − Ut max) × Ie
PROTECTION
0,8 0,6 0,4 0,2 0 0 20 40 60 80 100 120 140 160 180 200 Ut (V)
U t max ( =U emax) Utp
P ( protection ) = 1W max (Uto − Ut max) × Ie × t ⇒ ≤1 T
Ielk : Leakage current of the relay Ie : User load nominal current Utp : Relay max. non repetitive peak voltage
Utmax : Max. nominal voltage of the relay Uto : Possible overvoltage above Utmax Utn = Ue : User DC power supply voltage
t : Overvoltage duration T: Time between 2 overvoltage
celduc®
r e l a i s
S/CON/SOM020200/A/08/12/05
PRELIMINARY DATA
Page 3/5 UK
TIME CHARACTERISTICS
Fig. 4 TIME DIAGRAMS
TIME CHARACT.
CHARACTERISTIC Turn on time Turn on delay Turn off time Turn off delay Max. On-Off frequency
LABEL ton tdon toff tdoff F(on-off)
VALUE 20µs 20µs 20µs 20µs >1000Hz (for high frequency, take 2 x Ie to calculate the heatsink; the protections must be chosen carefully)
INFO.
Refer to the instruction sheet
GENERAL INFORMATION
CONNECTIONS
Connections Screwdriver advised Min and max tightening torque Insulated crimp terminals (round tabs, eyelet type) Display 2 N.m M5 Power POZIDRIV2 1.2 N.m M4 Control
Green LED (indicates relay has switched ON) UL94V0 2 screws (M4x12mm ; tightening = 1.2N.m) None 80g
See mounting sheet
MISC.
Housing Mounting Noise level Weight
STANDARDS
GENERAL
Standards Protection level Protection against direct touch CE marking UL, cULUS and VDE approvals TYPE OF TEST
STANDARD EN61000-4-2 EN61000-4-3 EN61000-4-4 EN61000-4-5 EN61000-4-11
IEC60947-1 IP20 Yes Yes Pending LEVEL Pending Pending Pending Pending EFFECT ? ? ? ?
E.M.C. IMMUNITY E.M.C. EMISSION
E.S.D. (Electrostatic discharges) Radiated electromagnetic fields Fast transients bursts Electric chocks Voltage drop
Radiated and conducted disturbances
NFEN55011
Pending
celduc®
r e l a i s
S/CON/SOM020200/A/08/12/05
PRELIMINARY DATA
Page 4/5 UK
CHARACTERISTIC CURVES
Fig. 5
Ic (mADC) 50 45 40 35 30 25 20 15 10 5 0 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 Uc (VDC)
0 -50 0 50 100 150
INPUT CHARACTERISTIC
Fig. 6
ON RESISTANCE VS JUNCTION TEMPERATURE
-35°C -35°C 25°C 100°C
RDSon 120 (mOhms)
100 80 60 40 20
Junction Temperature (°C)
Fig. 7
Permanent current Ie (ARMS)
POWER DISSIPATED AND LOAD CURRENT LIMIT VS TEMPERATURE
Please refer to the installation notice for precautions about mounting the device on a heatsink.
10K/W 4K/W 2.2K/W 2.1K/W 1.2K/W 1.1K/W 0,9K/W
Power dissipated ( W)
25
56.25
20
36
15
0.75K/W 0.55K/W 0.3K/W
20.25
10
9
5
2.25
0 0 10 20 30 40 50 60 70 80 90 100
0 110
Ambient temperature (°C) 10K/W = No Heatsink 2.1K/W = WF210000 0.75K/W = WF070000 4K/W = 150x150x3mm aluminium sheet 1.2K/W = WF121000 0.55K/W = WF050000 2.2K/W = WF262100 1.1K/W = WF131100 0.3K/W = WF031100 2.2K/W = WF151200 0.9K/W = WF115100
Fig. 8
PEAK OVERLOAD CURRENT vs. PULSE DURATION CHARACTERISTIC
Ie 180 (Apk) 160 140 120 100 80 60 Repetitive D=20% (Tc=100°C, Tjmax=175°C) Non-repetitive D=1% (Tc=100°C, Tjmax=175°C) Repetitive D=5% (Tc=100°C, Tjmax=175°C) Repetitive D=10% (Tc=100°C, Tjmax=175°C)
t1 D(% ) = × 100 t2
40 20 0 0,1
Repetitive D=50% (Tc=100°C, Tjmax=125°C)
1
10
100
1000 Pulse duration (ms)
celduc®
r e l a i s
S/CON/SOM020200/A/08/12/05
PRELIMINARY DATA
Page 5/5 UK
DIMENSIONS AND ACCESSORIES
Fig. 9 DIMENSIONS (mm)
2
-
1
+
Fig. 10
ACCESSORIES
FASTON : Please contact us
r
celduc®
e l a i s
www.celduc.com
Rue Ampère B.P. 4 42290 SORBIERS - France Phone : 33 (0) 4 77 53 90 20 Fax : 33 (0) 4 77 53 85 51 Email : celduc-relais@celduc.com