CUBEFuse® Compact Circuit Protector Base (CCPB)
For Quik–Spec™ Coordination Panelboards
Specifications:
• CCPB Ampacity rejection breaks: 15A, 20A, 30A, 40A, 50A and 60A • 1-, 2- and 3-Pole versions • For systems 600Vac (or less) • Box lug loadside terminal: • 18-6AWG single & dual rated, solid or stranded – 75°C, Cu only • 4AWG single – 75°C, Cu only • Box lug loadside terminal torque: 18-10AWG 20 Lb-In (2.2 N•m), 8-4AWG 35 Lb-In (3.9 N•m) The revolutionary Cooper Bussmann® CCPB with CUBEFuse® is designed as a fused branch circuit disconnect with fuse holder for the Cooper Bussmann® Quik-Spec™ Coordination Panelboard. The CCPB with CUBEFuse simplifies selective coordination and allows for isolation of individual branch circuit loads for safe work practices. • Spade terminal load connection: Max. 30A suitable for use with #8-32UNC screw • Bolt-on style bus connector, #10-32-UNC Hex flange Phillips screw, torque to 25 Lb-In (2.8N•m) • Lockout/tagout: 4mm shank lock or standard pin-out devices (Brady pin-out wide device P/N 90850 or Ideal P/N 44-784 • Bolt-mounted design into Quik-Spec Coordination Panelboard bus • Local indication: illumination requires closed circuit and minimum 90Vac operating voltage • RoHS compliant Agency Information: UL 98 Listed, File E302370, Guide WHTY cULus to CSA Standard 22.2 No. 4, File E302370, Guide WHTY7 CE Compliant Shipping Weight: 2.03 lbs per carton Carton quantity: 6 poles Environmental Data Storage and operating temperature: -20ºC to 75ºC*
*For fuse performance under or above 25ºC, consult fuse performance derating charts.
Product Features and Benefits
• Uses IP20 finger-safe with current-limiting, time-delay Class J performance • High Short-Circuit Current Ratings at 200kA • Disconnect rated to provide means for load isolation • Full voltage rated at 600Vac • UL 98 Listed and suitable for branch circuit disconnect and branch circuit protection • 1-, 2- and 3-pole versions are horsepower rated • Patented rejection feature helps prevent overfusing • Complies with UL and cULus • Open fuse indication light per pole • Additional open fuse indication can be provided by using the indicating CUBEFuse version • Built-in switch/fuse interlock prohibits removing the fuse while energized • Permanent lockout/tagout provisions • Lock-On provision Low-Peak® CUBEFuse®
1008
BU-SB08561
Form No.CCPB
Page 1 of 3
Data Sheet 1161
Bolt-on style bus connector
Symbols for ON and OFF Lockout/tagout provision Local, neon open fuse indication light Disconnect handle CUBEFuse base
Box lug loadside terminal Spade terminal connection
Technical Ratings
CUBEFuse Type (Class J performance) CCPB Part Numbers CCPB-1-15CF CCPB-2-15CF CCPB-3-15CF CCPB-1-20CF CCPB-2-20CF CCPB-3-20CF CCPB-1-30CF CCPB-2-30CF CCPB-3-30CF CCPB-1-40CF CCPB-2-40CF CCPB-3-40CF CCPB-1-50CF CCPB-2-50CF CCPB-3-50CF CCPB-1-60CF CCPB-2-60CF CCPB-3-60CF Poles 1 2 1-15 3 1 2 171⁄2-20 3 1 2 25-30 3 1 2 35-40 3 1 2 45-50 3 1 2 60 3 600Vac TCF60RN TCF60 60A 200kA 600Vac TCF45RN, TCF50RN TCF45, TCF50 50A 200kA 600Vac TCF35RN, TCF40RN TCF35, TCF40 40A 200kA 600Vac TCF25RN, TCF30RN TCF25, TCF30 30A 200kA 600Vac TCF17-1/2RN, TCF20RN TCF17-1/2, TCF20 20A 200kA 600Vac Fuse Amp Range Voltage Rating Non-Indicating Indicating* Max. Fuse Ampacity SCCR Hp Ratings 0.5Hp@120V 1.5Hp@240V 3Hp@240V 5Hp@480V 7.5Hp@600V 0.75Hp@120V 2Hp@240V 3Hp@240V 7.5Hp@480V 10Hp@600V 1.5Hp@120V 3Hp@240V 5Hp@240V 15Hp@480V 10Hp@600V 2.0Hp@120V 3Hp@240V 7.5Hp@240V 20Hp@480V 10Hp@600V 3.0Hp@120V 5Hp@240V 7.5Hp@240V 20Hp@480V 10Hp@600V 3.0Hp@120V 7.5Hp@240V 7.5Hp@240V 20Hp@480V 10Hp@600V
TCF1RN, TCF3RN, TCF6RN, TCF10RN, TCF15RN
TCF3, TCF6, TCF10, TCF15
15A
200kA
*1A indicating CUBEFuse not available. Correct fit with CCPB disconnect requires indicating CUBEFuse with date code R38 or later.
1008
BU-SB08561
Form No.CCPB
Page 2 of 3
Data Sheet 1161
CUBEFuse® Motor Sizing Table
Motor Size (Hp) 0.167 0.25 0.333 0.5 0.75 1 1.5 2 3 ** 0.167 0.25 0.333 0.5 0.75 1 1.5 2 3 5 7.5** 0.5 0.75 1 1.5 2 3 5 7.5** 0.5 0.75 1 1.5 2 3 5 7.5 ** Motor* FLA (Amps) 4.4 5.8 7.2 9.8 13.8 16 20 24 34 2.2 2.9 3.6 4.9 6.9 8 10 12 17 28 40 2.5 3.7 4.8 6.9 7.8 11 17.5 25.3 2.4 3.5 4.6 6.6 7.5 10.6 16.7 24.2 Low-Peak® CUBEFuse® (Amp Rating) Optimal Code Heavy Protection Max Start 10 10 10 10 15 15 15 15 15 15 20 20 25 25 30 25 30 35 30 35 45 40 45 50 50 60 N/A 6 6 6 6 6 6 6 10 10 10 10 10 15 15 15 15 15 17.5 15 20 20 20 25 25 25 30 35 45 50 60 60 N/A N/A 6 6 6 6 10 10 10 10 10 15 15 15 15 15 17.5 17.5 20 20 30 35 35 40 45 50 6 6 6 6 10 10 10 10 10 10 15 15 15 15 15 17.5 20 20 25 30 35 40 45 50 Motor Size (Hp) 0.5 0.75 1 1.5 2 3 5 7.5** 0.5 0.75 1 1.5 2 3 5 7.5 10 15 20** 0.5 0.75 1 1.5 2 3 5 7.5 10 ** Motor1 FLA (Amps) 2.2 3.2 4.2 6 6.8 9.6 15.2 22 1.1 1.6 2.1 3 3.4 4.8 7.6 11 14 21 27 0.9 1.3 1.7 2.4 2.7 3.9 6.1 9 11 Low-Peak® CUBEFuse® (Amp Rating) Optimal Code Heavy Protection Max Start 6 6 6 6 6 6 10 10 10 10 15 15 15 15 15 15 20 20 25 30 30 35 40 45 3 3 3 3 3 3 6 6 6 6 6 6 6 6 6 10 10 10 15 15 15 17.5 20 20 25 25 30 35 40 45 40 50 60 3 3 3 3 3 3 3 3 3 6 6 6 6 6 6 6 10 10 10 15 15 15 20 20 17.5 20 20
Voltage
Voltage
115Vac, 1-Phase
230Vac, 3-Phase
230Vac, 1-Phase
460Vac, 3-Phase
200Vac, 3-Phase
575Vac, 3-Phase
208Vac, 3-Phase
Note: Use Code Max column for low to moderate reverse/jog/plug applications. Heavy Start permitted only if Code Max does not allow motor start-up. *Based on motor FLA from NEC® tables 430.248 and 430.250. **Max. Hp rating for the CCPB 60 Amp device at specified voltage.
Dimensional Data — in (mm)
1.0 (25.4)
3.9 (99.4)
2.0 (50.7) 3.0 (75.8)
2.7 (69.1)
2.9 (73.5)
Ø.2 (5.8)
Ø.5 (12.9) 39
For details on the CCPB and its use in the Quik-Spec™ Coordination Panelboard, see data sheet 1160.
The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.