3RHP6050D24 数据手册
3 Phase RHP - Hybrid Solid State Contactors 3 Phase Contactor AC Input 40-50 Amp 280/600 VAC ENT PATDING PEN 3 Phase Contactor DC Input 40-50 Amp 120/240 VAC ENT PATDING PEN Combined SSR and EMR advantages Lifetime >2 million operations @ full load No heat sink required Input status LED indicator Wire, lug or quick connect termination DP contactor footprint CE compliant & UL/cUL recognized CONTROL SPECIFICATIONS Control Voltage Suffix Coil Voltage Range Min. Turn-On Voltage Min. Turn-Off Voltage Coil Power Consumption, Inrush Coil Power Consumption, Sealed Coil Terminals 1 Combined SSR and EMR advantages Lifetime >2 million operations @ full load No heat sink required DC logic compatible input Input status LED indicator Wire, lug or quick connect termination DP contactor footprint CE compliant & UL/cUL recognized CONTROL SPECIFICATIONS Control Voltage Suffix Control Voltage Range Max. Reverse Voltage Min. Turn-On Voltage Min. Turn-Off Voltage Input Current Input Connector 1 E 20 - 26 VAC, 50/60 Hz 20 VAC 12 VAC 56 VA @ 24 VAC 6.6 VA @ 24 VAC 10 in lb (1.13 Nm) 1 F G 100 - 130 VAC, 50/60 Hz 208 - 240 VAC, 50/60 Hz 100 VAC 208 VAC 24 VAC 48 VAC 56 VA @ 120 VAC 56 VA @ 220 VAC 6.6 VA @ 120 VAC 6.6 VA @ 220 VAC 10 in lb (1.13 Nm) 10 in lb (1.13 Nm) D5 4.5 - 5.5 VDC -5.5 VDC 4.5 VDC 1 VDC 12mA @ 5 VDC 5.31 in lb (0.6 Nm) 1 D12 10 - 15 VDC -15.5 VDC 9.5 VDC 2 VDC 12mA @ 12 VDC 5.31 in lb (0.6 Nm) D24 22 - 27 VDC -27.5 VDC 9.5 VDC 2 VDC 12mA @ 24 VDC 5.31 in lb (0.6 Nm) OUTPUT SPECIFICATIONS OUTPUT SPECIFICATIONS 28 3 Voltage suffix Operating Voltage (50/60Hz) Maximum Off-State Leakage Current per channel Load Current suffix Maximum Load Current per Phase @ 40°C Power terminals / wire range Screw torque requirements 2 60 48 - 600 VAC 0.06 mA @ 480 VAC 24 - 280 VAC 0.05 mA @ 240 VAC Voltage suffix Operating Voltage (50/60Hz) Maximum Off-State Leakage Current per channel Load Current suffix Maximum Load Current per Phase @ 40°C Power terminals / wire range Screw torque requirements 12 3 24 208 - 240 VAC 0.06 mA @ 240 VAC 100 - 120 VAC 0.05 mA @ 120 VAC 40 40 A Resistive Dual quick connect and Binder head screws / AWG#14 - AWG#8 18 in lbs (2.1 Nm) 50 50 A Resistive Dual quick connect and Box lugs / AWG#14 - AWG#6 25 in lbs (2.9 Nm) 40 2 50 40 A Resistive 50 A Resistive Dual quick connect and Binder Dual quick connect and Box head screws / AWG#14 - AWG#8 lugs / AWG#14 - AWG#6 18 in lbs (2.1 Nm) 25 in lbs (2.9 Nm) GENERAL SPECIFICATIONS 1 GENERAL SPECIFICATIONS 4000 VAC 2500 VAC Three Normally Open 4 1 Input to Output Dielectric Isolation. Input/Output to Ground Dielectric Isolation. Contacts (Double Break ) 3 Input to Output Dielectric Isolation Input/Output to Ground Dielectric Isolation Contacts (Double Break) 3 Ambient Operating Temperature Range 4 4000 VAC 2500 VAC Three Normally Open -20°C to 75°C -40°C to 100°C 16.6 mS @ 60 Hz / 20 mS @ 50 Hz 32 mS @ 60 Hz / 40 mS @ 50 Hz 30 operations per min > 2 Million operations 540 grs (1.19 lb) Ambient Operating Temperature Range Ambient Storage Temperature Range -20°C to 75°C -40°C to 100°C 16.6 mS @ 60 Hz / 20 mS @ 50 Hz 32 mS @ 60 Hz / 40 mS @ 50 Hz 30 operations per min > 2 Million operations 540 grs (1.19 lb) Max. Turn-On Time Max. Turn-Off Time Maximum Number of Operations per Minute Lifetime @ Rated Load Current, 40°C ambient temp, 30 operations/min, Rated Vcontrol Weight (typical) 1 2 3 4 Ambient Storage Temperature Range Max. Turn-On Time Max. Turn-Off Time Maximum Number of Operations per Minute Lifetime @ Rated Load Current, 40°C ambient temp, 30 operations/min, Rated Vcontrol Weight (typical) 1 2 3 4 Specificationts @ 25°C unless otherwise noted. See Derating Curves for additional operational conditions. The RHP includes a Solid-State Relay. Therefore, the output is never completely open. The RHP includes an overtemperature protection for the Solid-State Module. Specificationts @ 25°C unless otherwise noted. See Derating Curves for additional operational conditions. The RHP includes a Solid-State Relay. Therefore, the output is never completely open. The RHP includes an overtemperature protection for the Solid-State Module. Part Number Nomenclature SERIES Load Current 40: 40 Amps 50: 50 Amps Derating Curves 3RHPXX40XX 55 3RHPXX50XX Load Current, Amps rms 50 45 40 35 30 3 RHP Three Phase Device 12 40 D5 Nominal Coil /Control Voltage D5: 5 VDC D12: 12 VDC D24: 24 VDC E: 24 VAC F: 120 VAC G: 220 VAC Load Current, Amps rms 45 40 Operating Voltage VAC 50/60 Hz 12: 120 V 1-phase 24: 240 V 3-phase or 1-phase 28: 280 V 3-phase 60: 600 V 3-phase 35 Power lead size AWG # 6 AWG # 8 Power lead size AWG # 6 AWG # 8 30 Safe Operating Area 25 Safe Operating Area 25 20 25 35 45 55 65 75 25 35 45 55 65 75 20 Ambient Temperature, °C Ambient Temperature, °C Typical Electrical Connection for 3 Phase Applications (For output voltage options 24, 28, 60) 5 3 Phase RHP - Hybrid Solid State Contactors AC Input/Control Voltage (E, F, G input versions) I L3 HYBRID SOLID STATE CONTACTOR 5L3 3L2 VLL 6T3 4T2 2T1 I L1 120/240 VAC Single Phase Operating Voltage HYBRID SOLID STATE CONTACTOR 3 Phase AC Operating Voltage ~ ~ ~ AC Input/Control Voltage (E, F, G input versions) 3Ø Load ~ Line Line 5L3 3L2 1L1 I L3 -+ I L2 R1 I L1 R2 -+ Neutral DC Input/Control Voltage (D5, D12, D24 input versions) 1L1 I L1 DC Input/Control Voltage (D5, D12, D24 input versions) IL1 = (IL2 + IL3) ≤ Rated current AC Input/Control Voltage (E, F, G input versions) DO NOT apply any AC voltage to contactor coil connections, for DC versions only. Optional Electrical Connections for Single Phase Applications 6 (For output voltage options 12, 24, 28, 60) AC Input/Control Voltage (E, F, G input versions) 120/240 VAC Single Phase Operating Voltage 6T3=NC -+ Line 120/240 VAC Single Phase Operating Voltage Neutral ~ 3L2 1L1 HYBRID SOLID STATE CONTACTOR 5L3=NC ~ Neutral HYBRID SOLID STATE CONTACTOR 5L3 3L2 1L1 7 I L3 -+ I L2 R2 NC R1 I L1 R1 DC Input/Control Voltage (D5, D12, D24 input versions) IL2 ≤ Rated current IL3 ≤ Rated current IL2 + IL3 > Rated current DC Input/Control Voltage (D5, D12, D24 input versions) 5 6 7 IL1 ≤ Rated current Match VLL to voltage suffixes 28 & 60 for options E, F & G and 12 & 24 for options DX. The single phase supply voltage must be wired to terminal 1L1 and 3L2 for proper single phase operation. In applications switching two single phase loads (R1 and R2) where the combined load current exceeds the contactor’s rating (40 or 50 Amps) the return/neutral lead must not be wired through the contactor (see above drawing).
3RHP6050D24
1. 物料型号 - 3RHPXX40XX:表示三相混合固态接触器,负载电流40安培。 - 3RHPXX50XX:表示三相混合固态接触器,负载电流50安培。 - D5、D12、D24:分别表示控制电压为5VDC、12VDC、24VDC。 - E、F、G:分别表示操作电压为24VAC、120VAC、220VAC。

2. 器件简介 - 该器件是三相混合固态接触器,结合了固态继电器(SSR)和电磁继电器(EMR)的优点,具有超过200万次操作的寿命,无需散热片,具有输入状态LED指示,支持DP接触器尺寸。

3. 引脚分配 - 控制端子:10-32英寸螺栓(1.13Nm)。 - 电源端子/电线范围:双快速连接和箱式端子/AWG#14-AWG#6。 - 螺丝扭矩要求:18英寸磅(2.1Nm)和25英寸磅(2.9Nm)。

4. 参数特性 - 线圈电压范围:20-26VAC, 50/60Hz;100-130VAC, 50/60Hz;208-240VAC, 50/60Hz。 - 最小开启电压和关闭电压:12VAC/24VAC/48VAC开启;20VAC/100VAC/208VAC关闭。 - 线圈功耗:56VA@24VAC、56VA@120VAC、56VA@220VAC。

5. 功能详解 - 输入到输出和输入输出到地之间的介电强度分别为4000VAC和2500VAC。 - 接触点为三常开双断点。 - 工作环境温度范围为-20°C至75°C,存储温度范围为-40°C至100°C。

6. 应用信息 - 适用于三相和单相应用,具有不同的电压选项和负载电流选项。 - 包括固态继电器,因此输出永远不会完全打开。 - 包括固态模块的过温保护。

7. 封装信息 - 封装符合CE标准,并得到UL/cUL认证。 - 重量约为540克(1.19磅)。