GPL 121000 is a general purpose battery up to 10 years in standby service or more than 260 cycles at 100% discharge in cycle service . As with all CSB batteries, all are rechargeable , highly efficient , leak proof and maintenance free.
GPL 121000
12V 100Ah
Specification
Cells Per Unit Voltage Per Unit Capacity Weight Maximum Discharge Current Internal Resistance Operating Temperature Range 6 12 100Ah @ 20hr-rate to 1.75V per cell @25 Approx. 33.5 kg(73.86 lbs) 800A(5sec) Approx. 3.5 m
Discharge: -15 ~50 ( 5 ~122 ) Charge: -15 ~40 ( 5 ~104 ) Storage: -15 ~40 ( 5 ~104 ) 3 (77 5) 25 13.5 to 13.8 VDC/unit Average at 25 (77 30 A
(77
)
Nominal Operating Temperature Range Float Charging Voltage Recommended Maximum Charging Current Limit Equalization and Cycle Service Self Discharge
)
14.4 to 15.0 VDC/unit Average at 25 (77 ) CSB Batteries can be stored for more than 6 months at 25 (77 ) . Please charge batteries before using . For higher temperatures the time interval will be shorter.
I2-Thread lead alloy recessed terminal to accept M6 bolt Polypropylene(UL 94-V0/File E50955)*Flammability resistance of (UL 94-HB/File E216959) can be available upon request.
CSB-manufactured VRLA batteries are ULrecognized components under UL924 and UL1989. CSB is also certified by ISO 9001 and ISO 14001.
Terminal Container Material
Dimensions :
Unit: mm (inch)
Overall Height (H) 217.6±2.5 (8.57±0.1)
Container height (h) 214.6±2.5 (8.45±0.1)
Length (L) 343±2.5 (13.5±0.1)
Width (W) 170±2 (6.69±0.08)
Constant Current Discharge Characteristics
Unit:A (25
,77
)
F.V/Time 1.60V 1.67V 1.70V 1.75V 1.80V 1.85V
5MIN 423 375 355 317 283 245
10MIN 277 266 258 240 219 196
15MIN 212 207 203 194 183 164
30MIN 127 125 124 120 115 106
1HR 73.0 72.4 71.8 71.1 68.9 65.2
2HR 41.1 40.7 40.6 40.2 39.3 37.6
3HR 29.1 29.0 28.7 28.6 27.9 26.8
4HR 22.8 22.7 22.6 22.4 22.0 21.2
5HR 18.9 18.8 18.6 18.5 18.2 17.4
8HR 12.2 12.1 12.0 11.9 11.8 11.4
,77
10HR 10.0 9.93 9.89 9.82 9.66 9.45
)
20HR 5.28 5.23 5.21 5.19 5.10 4.92
Constant Power Discharge Characteristics
Unit:W (25
F.V/Time 1.60V 1.67V 1.70V 1.75V 1.80V 1.85V
5MIN 4,159 4,008 3,863 3,572 3,184 2,769
10MIN 2,950 2,837 2,772 2,623 2,442 2,227
15MIN 2,331 2,273 2,252 2,181 2,049 1,856
30MIN 1,436 1,417 1,404 1,372 1,316 1,234
1HR 849 843 840 830 809 767
2HR 482 480 478 475 465 444
3HR 342 340 339 337 331 320
4HR 269 268 266 265 261 252
5HR 223 222 221 220 217 210
8HR 153 152 151 150 148 142
10HR 125 124 123 122 121 117
20HR 63.5 63.3 63.2 62.4 61.4 60.0
RA: 0812
GPL121000
12V 100Ah
140 120 100 80 60 40 20
0.20 0.17 0.14 0.11 0.08 0.05 0.02
2.60 2.40 2.20 2.00 1.80 1.60 13.65V 1.40 (2.275V/Cell)
)Ratio
0
4
8
12
16
20
24
140 120 100 80 60 40 20
0.20 0.17 0.14 0.11 0.08 0.05 0.02
2.60 2.40 2.20 2.00 1.80 1.60 1.40
)Ratio
68
0
4
8
12
16
20
24
Application Cycle Use Standby
Charge Voltage(V/Cell) Temperature 25 (77 ) 25 (77 ) Set Point 2.45 2.275 Allowable Range 2.40~2.50 2.25~2.30
Max.Charge Current 0.3C
Final Discharge Voltage V/Cell Discharge Current(A)
1.75 0.2C>(A)
1.70 0.2C
很抱歉,暂时无法提供与“GPL121000”相匹配的价格&库存,您可以联系我们找货