Powered by
GPL 1272 is a general purpose battery up to 8 years in standby service or more than 260 cycles at 100% discharge in cycle service . As with all CSB batteries, all are rechargeable , highly efficient , leak proof and maintenance free.
GPL 1272
12V 7.2Ah
Specification
Cells Per Unit Voltage Per Unit Capacity Weight Maximum Discharge Current Internal Resistance Operating Temperature Range 6 12 7.2Ah @ 20hr-rate to 1.75V per cell @25 Approx. 2.6 kg(5.73 lbs) 100A/130A(5sec) Approx. 21 m
Discharge: -15 ~50 ( 5 ~122 ) Charge: -15 ~40 ( 5 ~104 ) Storage: -15 ~40 ( 5 ~104 ) 3 (77 5) 25 13.5 to 13.8 VDC/unit Average at 25 (77 2.16A
(77
)
Nominal Operating Temperature Range Float Charging Voltage Recommended Maximum Charging Current Limit Equalization and Cycle Service Self Discharge
)
14.4 to 15.0 VDC/unit Average at 25 (77 ) CSB Batteries can be stored for more than 6 months at 25 (77 ) . Please charge batteries before using . For higher temperatures the time interval will be shorter. F1/F2-Faston Tab187/250 ABS(UL 94-HB/File E50263)*Flammability resistance of (UL 94-V0/File E88637) can be available upon request.
CSB-manufactured VRLA batteries are ULrecognized components under UL924 and UL1989. CSB is also certified by ISO 9001 and ISO 14001.
Terminal Container Material
Dimensions :
Unit: mm (inch)
Overall Height (H) 100±1 (3.94±0.04)
Container height (h) 94±1 (3.7±0.04)
Length (L) 151±2 (5.94±0.08)
Width (W) 65±1 (2.56±0.04)
Constant Current Discharge Characteristics
Unit:A (25
,77
)
F.V/Time 1.60V 1.67V 1.70V 1.75V 1.80V 1.85V F.V/Time 1.60V 1.67V 1.70V 1.75V 1.80V 1.85V
5MIN 24.1 23.1 22.6 21.8 20.8 19.6 5MIN 258 251 247 240 231 222
10MIN 19.2 18.3 17.8 17.0 16.2 15.3 10MIN 210 202 199 192 185 177
15MIN 15.6 14.9 14.5 13.9 13.2 12.5 15MIN 173 166 162 156 151 146
30MIN 9.05 8.81 8.68 8.46 8.19 7.87 30MIN 103 101 99.3 97.4 95.0 92.2
1HR 4.88 4.73 4.65 4.53 4.39 4.28 1HR 54.0 53.3 52.9 52.3 51.5 50.6
2HR 2.67 2.60 2.57 2.51 2.46 2.40 2HR 29.8 29.1 28.8 28.2 27.7 27.2
3HR 1.93 1.90 1.87 1.83 1.78 1.75 3HR 22.0 21.8 21.6 21.2 20.8 20.4
4HR 1.53 1.51 1.50 1.46 1.42 1.38 4HR 18.0 17.8 17.6 17.3 16.8 16.4
5HR 1.29 1.28 1.27 1.24 1.21 1.17 5HR 15.3 15.0 14.9 14.5 14.1 13.8
8HR 0.901 0.886 0.879 0.864 0.849 0.826
,77
10HR 0.739 0.729 0.725 0.709 0.693 0.677
)
20HR 0.375 0.369 0.367 0.360 0.352 0.345 20HR 4.46 4.40 4.36 4.28 4.20 4.12
Constant Power Discharge Characteristics
Unit:W (25
8HR 10.5 10.4 10.2 10.1 10.0 9.73
10HR 8.78 8.64 8.57 8.45 8.29 8.14
RA: 0812
GPL1272
12V 7.2Ah
140 120 100 80 60 40 20
0.20 0.17 0.14 0.11 0.08 0.05 0.02
2.60 2.40 2.20 2.00 1.80 1.60 13.65V 1.40 (2.275V/Cell)
)Ratio
0
4
8
12
16
20
24
140 120 100 80 60 40 20
0.20 0.17 0.14 0.11 0.08 0.05 0.02
2.60 2.40 2.20 2.00 1.80 1.60 1.40
)Ratio
68
0
4
8
12
16
20
24
Application Cycle Use Standby
Charge Voltage(V/Cell) Temperature 25 (77 ) 25 (77 ) Set Point 2.45 2.275 Allowable Range 2.40~2.50 2.25~2.30
Max.Charge Current 0.3C
Final Discharge Voltage V/Cell Discharge Current(A)
1.75 0.2C>(A)
1.70 0.2C
很抱歉,暂时无法提供与“GPL1272”相匹配的价格&库存,您可以联系我们找货
免费人工找货