VDRT-960-48 Three Phase Industrial DIN Rail Power Supply
F eatures
·High efficiency 89% and low dissipation ·Protections:Short circuit/Over load/Over voltage/Over temperature ·Cooling by free air convection ·Built-in constant current limiting circuit ·Can be installed on DIN rail TS-35/7.5 or 15 ·UL 508(industrial control equipment)approved ·EN61000-6-2(EN50082-2) industrial immunity level ·100% full load burn-in test ·3 year warranty
DC output voltage Output rated current Output current range Rated output power Ripple & noise Voltage adj. range Voltage tolerance Line regulation Load regulation S etup, rise, hold time Input voltage range F requency range Efficiency A C current Inrush current Leakage current Overload protection Over voltage protection Over temp. protection
Working temperature Working humidity Storage temp., humidity Temperature coefficient Vibration Safety standards Withstand voltage Isolation resistance EMI conduction & radiation Harmonic current EMS immunity MTBF Dimensions W eight
Notes:
48V 20A 0~20A 960W 80mVp-p 48~55V ±1.0% ±0.5% ±0.5% 200ms, 60ms, 10ms/400VAC 200ms, 60ms, 24ms/500VAC at full load Three phrase 340 ~ 550VAC 47 ~ 63Hz 92% 2.4A/400VAC 1.9A/500VAC Cold start 50A