Additional Resources:
Product Page
|
3D Model
date
04/11/2023
page
1 of 6
SERIES: PDRB-100 │ DESCRIPTION: AC-DC DIN RAIL POWER SUPPLY
FEATURES
•
•
•
•
•
•
•
•
universal input range (85 ~ 264 Vac)
IEC/EN/UL 62368 certified
designed to meet 61558 system requirements
over Voltage Category (OVC) III design
over voltage, over current, and short circuit protections
4kVac isolation input to output
withstand up to 300 Vac input surge events
Class B emissions
MODEL
output1
voltage
output
current
output
power
ripple
and noise2
efficiency3
(Vdc)
range
(Vdc)
max
(A)
max
(W)
max
(mVp-p)
typ
(%)
PDRB-100-12
12
12.0 ~ 13.8
7.5
90.0
120
88
PDRB-100-15
15
13.5 ~ 18.0
6.5
97.5
120
89
PDRB-100-24
24
21.6 ~ 29.0
4.2
100.8
150
90
PDRB-100-48
48
43.2 ~ 55.2
2.1
100.8
240
90
Notes:
1. Output adjustable via built-in trimpot. The actual adjustment range may extend beyond the values listed and care should be taken to ensure the output
voltage and output power do not exceed stated limits.
2. At full load, nominal input, 20 MHz bandwidth oscilloscope.
3. At 230 Vac input.
PART NUMBER KEY
PDRB-100 - XX
Base Number
Output Voltage
cui.com
Additional Resources:
Product Page
|
3D Model
CUI Inc │ SERIES: PDRB-100 │ DESCRIPTION: AC-DC DIN RAIL POWER SUPPLY
date 04/11/2023 │ page 2 of 6
INPUT
parameter
conditions/description
min
max
units
input voltage
ac input
dc input
85
120
264
370
Vac
Vdc
47
63
Hz
3.0
1.6
A
A
frequency
current
at 115 Vac
at 230 Vac
inrush current
at 115 Vac
at 230 Vac
leakage current
at 240 Vac
typ
35
70
A
A
0.5
mA
max
units
10,000
6,400
2,500
1,100
µF
µF
µF
µF
OUTPUT
parameter
conditions/description
capacitive load
12
15
24
48
initial set point accuracy
0% ~ 100% load
line regulation
load regulation
Vdc
Vdc
Vdc
Vdc
output
output
output
output
min
typ
models
models
models
models
±2
%
at rated load
±0.5
%
at 230 Vac
±1.5
%
at 230 Vac
30
start-up time
hold-up time
3
switching frequency
temperature coefficient
no load power consumption
s
ms
65
kHz
±0.03
%/°C
at 230 Vac
12 Vdc, 15 Vdc output models
24 Vdc output models
48 Vdc output models
0.3
0.35
0.4
W
W
max
units
20
25
35
60
Vdc
Vdc
Vdc
Vdc
200
%
PROTECTIONS
parameter
conditions/description
over voltage protection
12
15
24
48
over current protection
auto recovery
short circuit protection
continuous, auto recovery, hiccup
Vdc
Vdc
Vdc
Vdc
output
output
output
output
min
models
models
models
models
110
cui.com
typ
Additional Resources:
Product Page
|
3D Model
CUI Inc │ SERIES: PDRB-100 │ DESCRIPTION: AC-DC DIN RAIL POWER SUPPLY
date 04/11/2023 │ page 3 of 6
SAFETY & COMPLIANCE
parameter
conditions/description
isolation voltage
input to output 5 mA for 1 minute
min
safety approvals
certified to 62368: IEC, EN, UL/cUL
safety class
Class II
conducted emissions
CISPR32/EN55032 CLASS B
radiated emissions
CISPR32/EN55032 CLASS B
ESD
IEC/EN61000-4-2 Contact ±6KV/Air ±8KV perf. Criteria A
radiated immunity
IEC/EN61000-4-3 10V/m perf. Criteria A
EFT/burst
IEC/EN61000-4-4 ±4KV perf. Criteria A
surge
IEC/EN61000-4-5 line to line ±2KV perf. Criteria A
conducted immunity
IEC/EN61000-4-6 10Vr.m.s perf. Criteria A
voltage dips and interruption
IEC/EN61000-4-11 0%, 70% perf. Criteria A
MTBF
as per MIL-HDBK-217F at 25°C
RoHS
yes
typ
max
4,000
units
Vac
300,000
hours
ENVIRONMENTAL
parameter
conditions/description
min
max
units
operating temperature
see derating curve
-40
70
°C
-40
85
°C
0
95
%
2,000
m
storage temperature
storage humidity
non-condensing
altitude
cui.com
typ
Additional Resources:
Product Page
|
3D Model
CUI Inc │ SERIES: PDRB-100 │ DESCRIPTION: AC-DC DIN RAIL POWER SUPPLY
date 04/11/2023 │ page 4 of 6
MECHANICAL
parameter
conditions/description
dimensions
70.00 x 92.66 x 58.00
min
material
plastic, heat-resistant (UL94V-0)
235
cooling
natural convection
MECHANICAL DRAWING
units: mm [inch]
ADJ: built-in trimpot
wire range: 24-12 AWG
tightening torque: Max 0.4 N·m
mounting rail: TS35
general tolerances: ±1.0 [±0.039]
TERMINAL
CONNECTIONS
Function
1
AC (L)
2
AC (N)
3
+Vo
4
+Vo
5
-Vo
6
-Vo
max
units
mm
weight
TERMINAL
typ
cui.com
g
Additional Resources:
Product Page
CUI Inc │ SERIES: PDRB-100 │ DESCRIPTION: AC-DC DIN RAIL POWER SUPPLY
DERATING CURVE
EFFICIENCY CURVES
cui.com
|
3D Model
date 04/11/2023 │ page 5 of 6
Additional Resources:
Product Page
|
3D Model
CUI Inc │ SERIES: PDRB-100 │ DESCRIPTION: AC-DC DIN RAIL POWER SUPPLY
date 04/11/2023 │ page 6 of 6
REVISION HISTORY
rev.
description
date
1.0
initial release
11/25/2020
1.01
derating and efficiency curves updated
02/17/2022
1.02
UKCA mark added
04/11/2023
The revision history provided is for informational purposes only and is believed to be accurate.
Headquarters
20050 SW 112th Ave.
Tualatin, OR 97062
800.275.4899
Fax 503.612.2383
cui.com
techsupport@cui.com
CUI offers a two (2) year limited warranty. Complete warranty information is listed on our website.
CUI reserves the right to make changes to the product at any time without notice. Information provided by CUI is believed to be accurate and reliable. However, no responsibility is
assumed by CUI for its use, nor for any infringements of patents or other rights of third parties which may result from its use.
CUI products are not authorized or warranted for use as critical components in equipment that requires an extremely high level of reliability. A critical component is any component of a
life support device or system whose failure to perform can be reasonably expected to cause the failure of the life support device or system, or to affect its safety or effectiveness.
很抱歉,暂时无法提供与“PDRB-100-15”相匹配的价格&库存,您可以联系我们找货
免费人工找货