SERIES: VGS-50B │ DESCRIPTION: AC-DC POWER SUPPLY
FEATURES
•
•
•
•
•
•
+70°C operation
output trim
current/voltage/temperature protections
screw terminal interface
low standby power consumption
30 mm height
MODEL
output
voltage
output
current
output
power
ripple
and noise1
efficiency2
(Vdc)
max
(A)
max
(W)
max
(mVp-p)
typ
(%)
VGS-50B-12
12
4.2
50.4
100
85
VGS-50B-24
24
2.2
52.8
150
88
VGS-50B-48
48
1.1
52.8
200
88
Notes:
1. 20 MHz bandwidth oscilloscope, 12” of twisted load cables paralleled with 0.1 µF ceramic and 47 µF electrolytic capacitors placed across the terminals at the load.
2. At 230 Vac, 50 Hz, full load.
3. All specifications are measured at Ta=25°C, nominal input voltage, and rated output load unless otherwise specified.
PART NUMBER KEY
VGS-50B - XX
Base Number
Output Voltage
cui.com
Additional Resources:
Product Page
|
3D Model
CUI Inc │ SERIES: VGS-50B │ DESCRIPTION: AC-DC POWER SUPPLY
date 01/28/2021 │ page 2 of 5
INPUT
parameter
conditions/description
min
voltage
typ
90
frequency
47
max
units
264
Vac
63
Hz
current
at 115 Vac, full load
at 230 Vac, full load
1.3
0.8
A
A
inrush current
at 230 Vac, cold start, full load
35
A
3.5
mA
0.3
W
max
units
leakage current
no load power consumption
at 230 Vac
OUTPUT
parameter
conditions/description
min
typ
line regulation
12 Vdc output model
all other models
±1
±0.5
%
%
load regulation
12 Vdc output model
all other models
±1
±0.5
%
%
adjustability
built in trim pot
start-up time
at 115/230 Vac input, full load
rise time
at 115/230 Vac input, full load
hold-up time
at 115 Vac input, full load
at 230 Vac input, full load
±10
%
2
s
30
ms
12
30
switching frequency
ms
ms
65
kHz
PROTECTIONS
parameter
conditions/description
min
max
units
over voltage protection
output shutdown, must recycle power to recover
120
typ
145
%
over current protection
output shutdown, auto recovery
110
180
%
short circuit protection
output shutdown, auto recovery
max
units
SAFETY & COMPLIANCE
parameter
conditions/description
isolation voltage
input to output for 1 minute, 10 mA
input to ground for 1 minute, 10 mA
output to ground for 1 minute, 10 mA
isolation resistance
input to output at 500 Vdc
input to ground at 500 Vdc
output to ground 500 Vdc
safety approvals
certified to 62368: EN
certified to 60950: IEC/UL
safety class
class I
conducted emissions
EN 55032:2015, Class B
radiated emissions
EN 55032:2015, Class B
input current harmonics
EN 61000-3-2:2014, Class A
voltage fluctuation and flicker
EN 61000-3-3:2013, Class A
ESD immunity
IEC 61000-4-2, air: ±8 kV; contact: ±4 kV, Class A
radiated field immunity
IEC 61000-4-3, 3 V/m, Class A
electrical fast transient
immunity
IEC 61000-4-4, Ac power port: 1 kV;
signal & telecommunication ports: 0.5 kV, Class B
Notes:
min
typ
1,500
1,500
500
100
100
100
Vac
Vac
Vac
MΩ
MΩ
MΩ
1. The power supply is considered a component which will be installed into final equipment. The final equipment still must be tested to meet the necessary EMC directives.
cui.com
Additional Resources:
Product Page
|
3D Model
CUI Inc │ SERIES: VGS-50B │ DESCRIPTION: AC-DC POWER SUPPLY
date 01/28/2021 │ page 3 of 5
SAFETY & COMPLIANCE (CONTINUED)
parameter
conditions/description
surge immunity
IEC 61000-4-5, input L to input N: 1 kV;
input L to FG: 2 kV; input N to FG: 2 kV, Class C
conducted immunity
IEC 61000-4-6, frequency range: 0.15~80 MHz;
field strength: 3 Vms, Class A
magnetic field immunity
IEC 61000-4-8, 1 A/m, Class A
voltage dips, interruptions
IEC 61000-4-11:
voltage dips >95% reduction, 0.5 period, Class A
voltage dips 30% reduction, 25 period, Class B
voltage dips >95% reduction, 250 period, Class C
MTBF
as per MIL-HDBK-217F, 25°C
RoHS
min
typ
max
units
200,000
hours
yes
Notes:
1. The power supply is considered a component which will be installed into final equipment. The final equipment still must be tested to meet the necessary EMC directives.
ENVIRONMENTAL
parameter
conditions/description
min
operating temperature
see derating curves
storage temperature
typ
max
units
-20
70
°C
-40
85
°C
operating humidity
non-condensing
20
90
%
storage humidity
non-condensing
10
95
%
DERATING CURVES
Output Load vs. Input Voltage
(at 25°C, Natural Convection)
Output Load vs. Ambient Temperature
(Natural Convection)
100
Output Load (%)
Output Load (%)
100
80
60
40
80
60
40
20
20
0
90
0
-20
115
132
176
200
220
240
264
Input (Vac)
cui.com
0
10
20
30
40
50
Ambient Temperature (°C)
60
70
Additional Resources:
Product Page
|
3D Model
CUI Inc │ SERIES: VGS-50B │ DESCRIPTION: AC-DC POWER SUPPLY
date 01/28/2021 │ page 4 of 5
MECHANICAL
parameter
conditions/description
dimensions
99 x 82 x 30
min
typ
max
mm
weight
200
cooling
natural convection
input/output connector
screw terminals accept 22~12 AWG wire, 1.2 N-m torque
g
MECHANICAL DRAWING
units: mm
tolerance: ±0.3 mm
I/P & O/P Connector
Input/Output Connector
f
Function
AC(L)
2
AC(N)
AC (L )
3
FG
AC ( N )
4
-V
(F G )
5
+V
-V
f
1
PIN
+V
M3X0.5
4 mm