Additional Resources:
Product Page
|
3D Model
date
05/06/2021
page
1 of 10
SERIES: VMS-200 │ DESCRIPTION: AC-DC POWER SUPPLY
FEATURES
•
•
•
•
•
•
•
compact 2 x 4” high power-density design (CNF version is 2.4 x 4.6”)
universal input range
efficiencies up to 93.5%
4th edition medical safeties
fan output (+12 Vdc)
over voltage, over current, over temperature and short circuit protections
covered and open-frame configurations
TUVRheinland
MODEL
EN
60601-1
IEC
60601-1
www.tuv.com
ID xxxxxxxxxx
output
voltage
output
current
output
power1
ripple
and noise2
efficiency3
(Vdc)
max
(A)
max
(W)
max
(mVp-p)
typ
(%)
VMS-200-12
12
16.67
200
150
92
VMS-200-24
24
8.33
200
240
93.5
VMS-200-48
48
4.17
200
480
93
Notes:
1.
2.
3.
4.
Maximum output power of 200 W with 10 CFM forced air or baseplate cooling, 180 W at 220 Vac with convection cooling.
At full load, nominal input, 20 MHz bandwidth oscilloscope, output terminated with 47 μF aluminum electrolytic and 0.1 μF ceramic capacitors.
At full load, 25°C, 230 Vac input.
All specifications are measured at Ta=25°C, nominal input voltage, and 75% rated output load unless otherwise specified.
PART NUMBER KEY
VMS-200 - XX - XXX
Base Number
Output Voltage
cui.com
Chassis:
“blank” = open-frame
CNF = covered
Additional Resources:
Product Page
|
3D Model
CUI Inc │ SERIES: VMS-200 │ DESCRIPTION: AC-DC POWER SUPPLY
date 05/06/2021 │ page 2 of 10
INPUT
parameter
max
units
voltage
conditions/description
min
90
typ
264
Vac
frequency
47
60
Hz
under voltage shutdown
69
83
Vac
current
at 100 Vac, full load
2.5
A
inrush current
at 240 Vac, 25°C, cold start
100
A
leakage current
at 264 Vac
0.3
mA
0.1
mA
0.3
W
max
units
16,400
8,570
1,270
μF
μF
μF
leakage current (enclosure/
patient)
power factor correction
meets EN 61000-3-2
no load power consumption
OUTPUT
parameter
conditions/description
min
output capacitance
at 115/230 Vac, full load
12 Vdc output models
24 Vdc output models
48 Vdc output models
initial set point accuracy
at 60% load, 25°C
line regulation
high line to low line at full load
load regulation
at 60%±40% load
hold-up time
at 115 Vac
10
ms
85
kHz
±0.05
%/°C
switching frequency
temperature coefficient
fan output
open-frame: 12 Vdc / 300 mA
covered: 12 Vdc / 500 mA
LED
indicates when power is on
typ
±2
%
±0.5
%
±1
%
PROTECTIONS
parameter
conditions/description
over voltage protection
recycle ac input to restart
12 Vdc output models
24 Vdc ouput models
48 Vdc output models
over current protection
hiccup, auto recovery
short circuit protection
hiccup, auto recovery
min
typ
max
16
31
56
130
150
min
typ
units
Vdc
Vdc
Vdc
180
%
max
units
4,000
1,500
1,500
Vac
Vac
Vac
SAFETY & COMPLIANCE
parameter
conditions/description
isolation voltage
input to output for 1 minute
input to earth ground for 1 minute
output to earth ground for 1 minute
isolation resistance
100
safety approvals
UL/cUL 60601-1 (3.1 edition), IEC 60601-1 (3.1 edition), EN 60601-1 (3.1 edition)
safety class
Class I & II
EMI/EMC
EN 60601-1-2 (4th edition)
conducted disturbance
EN 55011, FCC CFR 47 Part 18, Class B
radiated disturbance1
EN 55011, FCC CFR 47 Part 18, Class B
harmonic current emissions
IEC 61000-3-2:2014, Class A, Class D
Notes:
1. Need an external 1 mH choke at input for Class II type to pass EN 55011 Class B.
cui.com
MΩ
Additional Resources:
Product Page
|
3D Model
CUI Inc │ SERIES: VMS-200 │ DESCRIPTION: AC-DC POWER SUPPLY
date 05/06/2021 │ page 3 of 10
SAFETY & COMPLIANCE (CONTINUED)
parameter
conditions/description
voltage fluctuations & flicker
IEC 61000-3-3:2013, Criteria A
min
typ
max
radio-frequency, continuous
radiated disturbance
IEC 61000-4-3:2010, Criteria A
electrical fast transient (EFT)
IEC 61000-4-4:2012, ±0.5 kV, ±1 kV, ±2 kV, Criteria A
surge
IEC 61000-4-5:2014, L-N: ±0.5 kV, ±1 kV, L-PE, N-PE: ±0.5 kV, ±1 kV, ±2 kV, Criteria A
conducted disturbances,
induced by RF fields
IEC 61000-4-6:2013, Criteria A
power frequency magnetic field
IEC 61000-4-8:2009, Criteria A
voltage dips
IEC 61000-4-11:2004, dip: 30% 500 ms, dip: 60% 100 ms, dip >95% 10 ms, Criteria A
voltage interruptions
IEC 61000-4-11:2004, >95% 5,000 ms, Criteria B
MTBF
as per MIL-HDBK-217F, at full load, 25°C
RoHS
2011/65/EU
279,000
units
hours
ENVIRONMENTAL
parameter
conditions/description
min
max
units
operating temperature
see derating curves
-20
80
°C
-40
85
°C
storage temperature
typ
operating humidity
non-condensing
93
%
storage humidity
non-condensing
93
%
DERATING CURVES
cui.com
Additional Resources:
Product Page
CUI Inc │ SERIES: VMS-200 │ DESCRIPTION: AC-DC POWER SUPPLY
|
3D Model
date 05/06/2021 │ page 4 of 10
DERATING CURVES (CONTINUED)
EFFICIENCY CURVES
cui.com
Additional Resources:
Product Page
|
3D Model
CUI Inc │ SERIES: VMS-200 │ DESCRIPTION: AC-DC POWER SUPPLY
date 05/06/2021 │ page 5 of 10
MECHANICAL
parameter
conditions/description
dimensions
VMS-200 models: 4.000 x 2.000 x 1.480 (101.60 x 50.80 x 37.60 mm)
VMS-200-CNF models: 4.606 x 2.441 x 1.575 (117.00 x 62.00 x 40.00 mm)
min
typ
max
weight
VMS-200 models
VMS-200-CNF models
cooling
external fan or baseplate cooling
CN1 input connector
CN1 mates with JST housing VHR series, JST SVH-21/41T-P1.1
series crimp terminal or equivalent
output terminals
+Vo & -Vo terminals are M3 screws
fan connector
fan mates with JST housing PHR-R5500 series, JST R5503-PT
series crimp terminal or equivalent
253
314
MECHANICAL DRAWING
Open-frame
units: inch [mm]
tolerance: ±0.020 [±0.50]
4.000 101.60
CN1
3
ACN
0.150 3.80
PE
PE
FAN
1
FAN V+
2
FAN V-
+Vo
ACN
-Vo
ACL
4-
1
0.
3
2
3.
0
PE Air flow
direction
10CFM
GBO
FAN V+
FAN VLED
0.197 5.00 max
Function
10mm
PIN
2.000 50.80
-
1.701 43.20
ACL
2
0.150 3.80
1
3.701 94.00
cui.com
1.480 37.60
Function
1.220 31.00 max
PIN
units
inch
inch
g
g
Additional Resources:
Product Page
|
3D Model
CUI Inc │ SERIES: VMS-200 │ DESCRIPTION: AC-DC POWER SUPPLY
date 05/06/2021 │ page 6 of 10
MECHANICAL DRAWING (CONTINUED)
Covered
units: inch [mm]
tolerance: ±0.020 [±0.50]
1
ACL
2
-
3
ACN
+Vo
ACN
FAN V+
2
FAN V-
Air flow
direction
GBO
10CFM
0.236 6.00
0.197 5.00
Function
1
0.370 9.40
PIN
-Vo
ACL
10mm
FAN
0.157 4.00
4.29 109.00
cui.com
1.575 40.00
Function
1.701 43.20
PIN
2.441 62.00
4.606 117.00
CN1
FAN V+
FAN VLED
Additional Resources:
Product Page
|
3D Model
CUI Inc │ SERIES: VMS-200 │ DESCRIPTION: AC-DC POWER SUPPLY
date 05/06/2021 │ page 7 of 10
EMI RECOMMENDATION
To Meet EN 55011 Class B, Class II
VMS-200
VMS-200-CNF
Table 1
Specification
Inductance
Duplex Winding/
Turns
Manufacturers
T16*10*5C
R12
1 mH
TEX-E Ø0.65/11T
VAKOS
cui.com
Additional Resources:
Product Page
|
3D Model
CUI Inc │ SERIES: VMS-200 │ DESCRIPTION: AC-DC POWER SUPPLY
date 05/06/2021 │ page 8 of 10
INSTALLATION INSRUCTIONS
The VMS-200 series has (4) 3.2 mm diameter mounting holes that can be used in (4) types of installations.
Type 1
Mounting from top with spacers (VMS-200 models)
Type 2
Mounting from bottom (VMS-200-CNF models)
Spacer: 5.5 mm diameter max, 5 mm high minimum
Screw Size: (4) M3X0.5 (head & washer OD not to exceed
6 mm)
Mounting torque: 3 kgf-cm
Screw Size: (4) M3X0.5
Mounting torque: 3 kgf-cm
Type 3 (External Baseplate Cooling)
Mounting from top with spacers (VMS-200 models)
Type 4 (External Baseplate Cooling)
Mounting from bottom (VMS-200-CNF models)
Heat Sink: 280 x 100 x 10 mm
Spacer: 5.5 mm diameter max, 5 mm high minimum
Screw Size: (4) M3X0.5 (head & washer OD not to exceed
6 mm)
Mounting torque: 3 kgf-cm
Heat Sink: 280 x 100 x 10 mm
Screw Size: (4) M3X0.5
Mounting torque: 3 kgf-cm
cui.com
Additional Resources:
Product Page
|
3D Model
CUI Inc │ SERIES: VMS-200 │ DESCRIPTION: AC-DC POWER SUPPLY
date 05/06/2021 │ page 9 of 10
INSTALLATION INSRUCTIONS (CONTINUED)
Output Terminals
Mate with round or Y terminals
Terminal Size: (2) M3
Torque: 3 kgf-cm
Output Connectors
with M3 Screws*2
3(kgf-cm)
or
Mounting Clearance
Allow at least 4 mm side clearance and 5 mm height clearance. If clearances aren’t met, the isolation and withstand
specifications may not be met.
Protective Earth
PE should be connected to the earth (ground) terminal of the apparatus otherwise conducted noise and output noise will
increase.
cui.com
Additional Resources:
Product Page
|
3D Model
CUI Inc │ SERIES: VMS-200 │ DESCRIPTION: AC-DC POWER SUPPLY
date 05/06/2021 │ page 10 of 10
REVISION HISTORY
rev.
description
date
1.0
initial release
12/12/2017
1.01
company logo updated
12/21/2020
1.02
derating and efficiency curves updated
05/06/2021
The revision history provided is for informational purposes only and is believed to be accurate.
Headquarters
20050 SW 112th Ave.
Tualatin, OR 97062
800.275.4899
Fax 503.612.2383
cui.com
techsupport@cui.com
CUI offers a two (2) year limited warranty. Complete warranty information is listed on our website.
CUI reserves the right to make changes to the product at any time without notice. Information provided by CUI is believed to be accurate and reliable. However, no responsibility is
assumed by CUI for its use, nor for any infringements of patents or other rights of third parties which may result from its use.
CUI products are not authorized or warranted for use as critical components in equipment that requires an extremely high level of reliability. A critical component is any component of a
life support device or system whose failure to perform can be reasonably expected to cause the failure of the life support device or system, or to affect its safety or effectiveness.