Additional Resources:
Product Page
date
08/28/2012
page
1 of 4
SERIES: VMS-80 │ DESCRIPTION: AC-DC POWER SUPPLY
®
MODEL
VMS-80-5
output
voltage
output
current
output
power
ripple
and noise1
efficiency
(Vdc)
max
(A)
max
(W)
max
(mVp-p)
typ
(%)
14.0
70
50
85
8.89
80
90
85
6.66
80
120
85
5.33
80
150
85
4.44
80
180
85
24
3.33
80
240
85
30
2.66
80
300
85
36
2.22
80
360
85
5
VMS-80-9
9
12
VMS-80-15
15
VMS-80-18
18
N
VMS-80-12
VMS-80-24
VMS-80-30
VMS-80-36
1. Measured at 20MHz, with 0.1μF ceramic and 47μF electrolytic capacitors
O
Notes:
IEC
60601-1
EN
60601-1
N
RoHS
U
up to 80 W continuous power
universal input (90~260 Vac)
single output from 5~36 V
no minimum load required
over voltage, over current and short circuit protections
full medical safety approvals
efficiency up to 85%
TI
•
•
•
•
•
•
•
ED
FEATURES
VMS-80 - XX
Base Number
Output Voltage
D
IS
C
PART NUMBER KEY
cui.com
Additional Resources:
Product Page
CUI Inc │ SERIES: VMS-80 │ DESCRIPTION: AC-DC POWER SUPPLY
date 08/28/2012
page 2 of 4
INPUT
parameter
conditions/description
min
voltage
typ
90
47
input current
at 100 Vac, full load
at 240 Vac, full load
inrush current
at 115 Vac, full load, cool start at 25 °C
at 230 Vac, full load, cool start at 25 °C
OUTPUT
full load
load regulation
at 230 Vac
hold-up time
at 110 Vac, full load
PROTECTIONS
parameter
conditions/description
over voltage protection
recovers automatically
recovers automatically
short circuit protection
recovers automatically
SAFETY & COMPLIANCE
63
Hz
A
15
30
18
34
A
typ
max
units
±0.5
±1
%
±3
±7
%
16
min
conditions/description
isolation voltage
input to output (for 60 seconds, 10mA)
input to ground (for 60 seconds, 10mA)
max
units
132
%
110
150
%
max
units
min
insulation resistance
at 500 Vdc
N
parameter
typ
ms
112
TI
over current protection
min
Vac
1.2
0.4
U
conditions/description
line regulation
N
parameter
units
260
ED
frequency
max
typ
5,656
2,828
Vdc
50
MΩ
IEC 60601-1, EN 60601-1, UL 60601-1
EMI/EMC
EN 55011 Class B, CISPR 11 Class B, FCC Part 18 Class B, EN 61000-3-2, EN 61000-3-3, IEC 61000-4(2, 3, 4, 5, 6, 8, 11)
leakage current
RoHS compliant
0.1
mA
yes
MIL-HDBK-217F, at 25C, nominal load
IS
C
MTBF
O
safety approvals
100,000
hours
ENVIRONMENTAL
parameter
conditions/description
operating temperature
derating from 50~70°C
min
typ
max
units
0
70
°C
-40
85
°C
operating humidity
95
%
storage humidity
75
%
D
storage temperature
cui.com
Additional Resources:
Product Page
CUI Inc │ SERIES: VMS-80 │ DESCRIPTION: AC-DC POWER SUPPLY
date 08/28/2012
page 3 of 4
DERATING CURVES
output power vs. ambient temperature
ED
Load (%)
100
80
60
(Natural Convection)
40
20
0
10
20
30
40
50
60
70
MECHANICAL DRAWING
units: mm[in]
TOLERANCE: mm: ±0.5
inch: ±0.02
MOUNTING HOLES
4.00 0.16
(4 PLCS)
N
127.00 5.00
U
Ambient Temperature (°C)
115.60 4.55
CN1 MATES WITH
MOLEX HOUSING 09-50-3031
AND MOLEX 2478 SERIES
CRIMP TERMINAL
L
2
No pin
3
AC Neutral
N
N
AC Line
17.00 0.67
AC INPUT
65.15 2.56
3.96 0.16
(11 PLCS)
4.60 0.18
MAX
D
cui.com
76.50 3.01
12
DC OUTPUT
27.90 1.10
MAX
IS
C
1
7.92 0.31
O
CN1
TI
1
CN2
17.05 0.67
CN2 MATES WITH
MOLEX HOUSING 09-50-3121
AND MOLEX 2478 SERIES
CRIMP TERMINAL
1
-Vo
2
-Vo
3
-Vo
4
-Vo
5
-Vo
6
-Vo
7
+Vo
8
+Vo
9
+Vo
10
+Vo
11
+Vo
12
+Vo
Additional Resources:
Product Page
CUI Inc │ SERIES: VMS-80 │ DESCRIPTION: AC-DC POWER SUPPLY
date 08/28/2012
page 4 of 4
REVISION HISTORY
description
date
09/21/2011
1.0
initial release
1.01
V-Infinity branding removed
1.02
safety marks updated
ED
rev.
07/06/2012
08/28/2012
D
IS
C
O
N
TI
N
U
The revision history provided is for informational purposes only and is believed to be accurate.
Headquarters
20050 SW 112th Ave.
Tualatin, OR 97062
800.275.4899
Fax 503.612.2383
cui.com
techsupport@cui.com
CUI offers a two (2) year limited warranty. Complete warranty information is listed on our website.
CUI reserves the right to make changes to the product at any time without notice. Information provided by CUI is believed to be accurate and reliable. However, no responsibility is
assumed by CUI for its use, nor for any infringements of patents or other rights of third parties which may result from its use.
CUI products are not authorized or warranted for use as critical components in equipment that requires an extremely high level of reliability. A critical
component is any component of a life support device or system whose failure to perform can be reasonably expected to cause the failure of the life support device or system, or to
affect its safety or effectiveness.
很抱歉,暂时无法提供与“VMS-80-18”相匹配的价格&库存,您可以联系我们找货
免费人工找货