TECHNICAL DATASHEET
Chrome DIN Rail Power Supply
24V 91.2W 1 Phase (Class II & NEC Class 2) / DRC-24V100W1A□
Highlights & Features
Class II Double Isolation (No Earth connection is required)
Universal AC input voltage range and full power up to 55°C
Power will not de-rate for the entire input voltage range
Efficiency > 89.0% @ 230 Vac
Can be installed in compact cabinets
NEC Class 2 and Limited Power Source (LPS) approvals
Conforms to harmonic current IEC/EN 61000-3-2, Class A
Safety approval according to IEC/EN/UL 60950-1,
IEC/EN/UL 62368-1 and UL 508
•
•
•
•
•
•
•
•
Safety Standards
CB Certified for worldwide use
Model Number:
DRC-24V100W1A☐
Unit Weight:
0.35 kg (0.77 lb)
Dimensions (L x W x D): 91.0 x 89.9 x 55.6 mm
*This picture is for reference to DRC-24V100W series only.
(3.58 x 3.54 x 2.19 inch)
General Description
The DRC-24V100W1A☐ is part of the Chrome DIN rail power supply series, which is designed for use in compact cabinets for home
automations and the food and beverage industry. Delta’s Chrome DIN rail power supply series offers double isolated input. This means
that no Earth connection is required thus resulting in low leakage current. This product provides a universal input voltage range of 90264 Vac, and a wide temperature range of -25°C to 71°C. The Chrome series is certified to safety standard according to IEC 60950-1,
IEC/EN/BS EN UL 62368-1 and UL 508. NEC Class 2 and Limited Power Source (LPS) approvals are available for this product.
Model Information
Chrome DIN Rail Power Supply
Model Number
Input Voltage Range
Rated Output Voltage
Rated Output Current
DRC-24V100W1A☐
90-264 Vac (125-375 Vdc)
24 Vdc
3.80 A
Model Numbering
DR
C–
24V
100W
1
A
□
DIN Rail
Product Series
C - Isolation Class II
Power Supply
Output Voltage
Output Power
(100 W series)
Single Phase
No PFC
C – Black Plastic case with
conformal Coating
Z – Black Plastic case without
conformal Coating
G – Grey Plastic case without
conformal Coating
1
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (June 2021, Rev.08)
TECHNICAL DATASHEET
Chrome DIN Rail Power Supply
24V 91.2W 1 Phase (Class II & NEC Class 2) / DRC-24V100W1A□
Specifications
Input Ratings / Characteristics
Nominal Input Voltage
100-240 Vac
Input Voltage Range
90-264 Vac
Nominal Input Frequency
50-60 Hz
Input Frequency Range
47-63 Hz
Nominal DC Input Voltage*
125-250 Vdc
DC Input Voltage Range*
125-375 Vdc
Input Current
< 2.20 A @ 115 Vac, < 1.00 A @ 230 Vac
Efficiency at 100% Load
> 87.0% @ 115 Vac, > 89.0% @ 230 Vac
Max Power Dissipation
0% load
100% load
< 0.4 W @ 115 Vac & 230 Vac
< 13.6 W @ 115 Vac, < 11.2 W @ 230 Vac
Max Inrush Current (Cold Start)
< 30 A @ 115 Vac, < 60 A @ 230 Vac
Leakage Current
< 0.25 mA @ 240 Vac
*Safety approval according to IEC/EN/UL 60950-1.
Output Ratings / Characteristics**
Nominal Output Voltage
24 Vdc
Factory Set Point Tolerance
24 Vdc ± 2%
Output Voltage Adjustment Range
22-24 Vdc
Output Current
0-3.80 A (3.80 A max.)
Output Power
91.2 W
Line Regulation
< 0.5% (@ 90-264 Vac input, 100% load)
Load Regulation
< 1.0% (@ 90-264 Vac input, 0-100% load)
PARD*** (20 MHz)
< 100 mVpp
Rise Time
< 70 ms @ nominal input (100% load)
Start-up Time
< 2,000 ms @ nominal input (100% load)
Hold-up Time
> 10 ms @ 115 Vac,
> 60 ms @ 230 Vac (100% load)
Dynamic Response
(Overshoot & Undershoot O/P Voltage)
± 5% @ 90-264 Vac input, 10-100% load
(Slew Rate: 0.1 A/μs, 50% duty cycle @ 5 Hz to 100 Hz)
Start-up with Capacitive Loads
3,000 µF Max
**For power de-rating from 55°C to 70°C, see power de-rating on page 3.
***PARD is measured with an AC coupling mode, 5 cm wires, and in parallel with 0.1 μF ceramic capacitor & 47 μF electrolytic capacitor.
2
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (June 2021, Rev.08)
TECHNICAL DATASHEET
Chrome DIN Rail Power Supply
24V 91.2W 1 Phase (Class II & NEC Class 2) / DRC-24V100W1A□
Mechanical
Case Cover
Plastic
Dimensions (L x W x D)
91.0 x 89.9 x 55.6 mm (3.58 x 3.54 x 2.19 inch)
Unit Weight
0.35 kg (0.77 lb)
Indicator
Green LED
Cooling System
Terminal
Wire
DC OK
Convection
Input
2 Pins (Rated 300 V/25 A)
Output
4 Pins (Rated 300 V/25 A)
Input / Output
AWG 20-12
Mounting Rail
Standard TS35 DIN Rail in accordance with EN 60715
Noise (1 Meter from power supply)
Sound Pressure Level (SPL) < 25 dBA
Environment
Surrounding Air Temperature
Power De-rating
Operating
-25°C to +71°C
Storage
-25°C to +85°C
Temperature
> 55°C de-rate power by 2.5% / °C
Operating Humidity
5 to 95% RH (Non-Condensing)
Operating Altitude
0 to 2,000 Meters (6,560 ft.)
Shock Test
Operating
IEC 60068-2-27, Half Sine Wave: 4 G for a duration of 22 ms,
3 shocks for each 3 directions, 9 times in total
Vibration
Operating
IEC 60068-2-6, Sine Wave: 10-500 Hz @ 19.6 m/S²
(2 G peak); 10 min per cycle, 60 min for all X, Y, Z directions
Over Voltage Category
II
Pollution Degree
2
Protections
Overvoltage
< 34.8 V, SELV Output, Latch Mode
Overload / Overcurrent
> 102~108% of rated load current,
Fold Forward Mode (current rises, voltage drops)
Non-Latching (Auto-Recovery)
Over Temperature
> 75°C Surrounding Air Temperature @ 100% load,
Latch Mode
Short Circuit
Hiccup Mode, Non-Latching
(Auto-Recovery when the fault is removed)
Internal Fuse at L pin
T3.15 AH
Degree of Protection
IP20
Protection Against Shock
Class II (No PE* connection is required)
*PE: Primary Earth
Reliability Data
MTBF
> 500,000 hrs. as per Telcordia SR-332
I/P: 100 Vac, O/P: 100% load, Ta: 35°C
Expected Cap Life Time
10 years (115 Vac & 230 Vac, 50% load @ 40°C)
3
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (June 2021, Rev.08)
TECHNICAL DATASHEET
Chrome DIN Rail Power Supply
24V 91.2W 1 Phase (Class II & NEC Class 2) / DRC-24V100W1A□
Safety Standards / Directives
Safety Entry Low Voltage
Electrical Safety
SELV (IEC 60950-1)
TUV Bauart
UL/cUL recognized
CB scheme
UKCA
Industrial Control Equipment
Class 2 Power Supply
UL/cUL listed
UL/cUL recognized
BIS
CE
UKCA
Galvanic Isolation
Input to Output
EN 62368-1
UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E131881)
UL 62368-1 and CSA C22.2 No. 62368-1 (File No. E131881)
IEC 60950-1, IEC 62368-1, Limited Power Source (LPS)
BS EN 62368-1
UL 508 and CSA C22.2 No. 107.1-01 (File No. E338991)
UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E131881)
UL 62368-1 and CSA C22.2 No. 62368-1 (File No. E131881)
IS 13152-1
In conformance with EMC Directive 2014/30/EU and
Low Voltage Directive 2014/35/EU
In conformance with Electrical Equipment (Safety) Regulations
2016 No. 1011 and The Electromagnetic Compatibility
Regulations 2016 No. 1091
3.0 KVac
EMC
Emissions (CE & RE)
Generic Standards: CISPR 32, EN/BS EN 55032,
FCC Title 47: Class B
Immunity
Generic Standards: EN/BS EN 55024
Electrostatic Discharge
IEC 61000-4-2
Level 3 Criteria A1)
Air Discharge: 8 kV
Contact Discharge: 4 kV
Radiated Field
IEC 61000-4-3
Level 2 Criteria A1)
80 MHz - 1 GHz, 3 V/M with 1 kHz tone / 80% modulation
Electrical Fast Transient / Burst
IEC 61000-4-4
Level 3 Criteria A1)
1 kV
Surge
IEC 61000-4-5
Level 3 Criteria A1)
Differential Mode3): 1 kV
Conducted
IEC 61000-4-6
Level 2 Criteria A1)
150 kHz - 80 MHz, 3 Vrms
Power Frequency Magnetic Fields
IEC 61000-4-8
Criteria A1)
1 A/Meter
Voltage Dips and Interruptions
IEC 61000-4-11
0% of 100 Vac, 20 ms
40% of 100 Vac, 200 ms
70% of 100 Vac, 500 ms
0% of 100 Vac, 5,000 ms
0% of 240 Vac, 20 ms
40% of 240 Vac, 200 ms
70% of 240 Vac, 500 ms
0% of 240 Vac, 5,000 ms
Criteria B2)
Criteria B2)
Criteria A1)
Criteria B2)
Criteria A1)
Criteria A1)
Criteria A1)
Criteria B2)
Harmonic Current Emission
IEC/EN/BS EN 61000-3-2, Class A
Voltage Fluctuation and Flicker
IEC/EN/BS EN 61000-3-3
1) Criteria A: Normal performance within the specification limits
2) Criteria B: Temporary degradation or loss of function which is self-recoverable
3) Symmetrical: Differential mode (Line to line)
4
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (June 2021, Rev.08)
TECHNICAL DATASHEET
Chrome DIN Rail Power Supply
24V 91.2W 1 Phase (Class II & NEC Class 2) / DRC-24V100W1A□
Block Diagram
Device Description
1)
2)
3)
4)
5)
5
Input terminal block connector
Output terminal block connector
DC voltage adjustment potentiometer
DC OK control LED (Green)
Universal mounting system
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (June 2021, Rev.08)
TECHNICAL DATASHEET
Chrome DIN Rail Power Supply
24V 91.2W 1 Phase (Class II & NEC Class 2) / DRC-24V100W1A□
Dimensions
L x W x D: 91.0 x 89.9 x 55.6 mm (3.58 x 3.54 x 2.19 inch)
Engineering Data
Output Load De-rating VS Surrounding Air Temperature
Note
1.
2.
3.
4.
Fig. 1
6
De-rating for Vertical Mounting Orientation
> 55°C de-rate power by 2.5% / °C
5.
Power supply components may degrade, or
be damaged, when the power supply is
continuously used outside the shaded region,
refer to the graph shown in Fig. 1.
If the output capacity is not reduced when the
surrounding air temperature exceeds its
specification as defined on Page 3 under
“Environment”, the device may run into Over
Temperature Protection. When activated, the
output voltage will go into latch mode and
recover when AC power recycles.
In order for the device to function in the
manner intended, it is also necessary to keep
a safety distance as recommended in the
safety instructions while the device is in
operation.
Depending on the surrounding air temperature
and output load delivered by the power
supply, the device can be very hot!
If the device has to be mounted in any other
orientation, please contact info@deltapsu.com
for more details.
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (June 2021, Rev.08)
TECHNICAL DATASHEET
Chrome DIN Rail Power Supply
24V 91.2W 1 Phase (Class II & NEC Class 2) / DRC-24V100W1A□
Output Load De-rating VS Input Voltage
No output power de-rating across the entire
input voltage range
Assembly & Installation
The power supply unit (PSU) can be mounted on 35 mm DIN rails in accordance with EN60715. The device should be installed with input
terminal block at the bottom.
Each device is delivered ready to install.
Mounting
Dismounting
Fig. 2.1 Mounting
Fig. 2.2 Dismounting
Snap on the DIN rail as shown in Fig. 2.1:
1. Pull the unit’s DIN rail latch OUT.
2. Tilt the unit slightly upwards, hook the top end onto the DIN
rail and push downwards until stopped.
3. Position the bottom front end against the DIN rail.
4. Push the unit’s latch DIN rail IN to lock.
To uninstall, pull the unit’s DIN rail latch OUT as shown in Fig.
2.2. Tilt the bottom part of the unit out. Push the unit up and pull
out from the DIN rail.
7
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (June 2021, Rev.08)
TECHNICAL DATASHEET
Chrome DIN Rail Power Supply
24V 91.2W 1 Phase (Class II & NEC Class 2) / DRC-24V100W1A□
Safety Instructions
•
•
•
•
•
•
ALWAYS switch mains of input power OFF before
connecting and disconnecting the input voltage to the unit.
If mains are not turned OFF, there is risk of explosion /
severe damage.
To guarantee sufficient convection cooling, keep a
distance of 50 mm (1.97 inch) above and below the
device as well as a lateral distance of 25 mm (0.98 inch)
to other units.
Note that the enclosure of the device can become very hot
depending on the surrounding air temperature and load of
the power supply. Risk of burns!
DO NOT insert any objects into the unit.
Hazardous voltages may be present for up to 5 minutes
after the input mains voltage is disconnected. Do not touch
the unit during this time.
The power supplies are built in units and must be installed
in a cabinet or room (condensation free environment and
indoor location) that is relatively free of conductive
contaminants.
Functions
Graph illustrating the Start-up Time, Rise Time, and Hold-up Time
Start-up Time
The time required for the output voltage to reach 90% of its final steady state set value, after the input voltage is applied.
Rise Time
The time required for the output voltage to change from 10% to 90% of its final steady state set value.
Hold-up Time
Time between the collapse of the AC input voltage, and the output falling to 95% of its steady state set value.
8
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (June 2021, Rev.08)
TECHNICAL DATASHEET
Chrome DIN Rail Power Supply
24V 91.2W 1 Phase (Class II & NEC Class 2) / DRC-24V100W1A□
Inrush Current
Dynamic Response
Inrush current is the peak, instantaneous, input current measured
and, occurs when the input voltage is first applied. For AC input
voltages, the maximum peak value of inrush current will occur
during the first half cycle of the applied AC voltage. This peak value
decreases exponentially during subsequent cycles of AC voltage.
The power supply output voltage will remains within ± 5% of its
steady state value, when subjected to a dynamic load from 10% to
100% of its rated current.
50% duty cycle / 5 Hz to 100 Hz
External Input Protection Device
The unit is protected with internal fuse (not replaceable) at L pin and it has been tested and approved on 20 A (UL) and 16 A (IEC) branch
circuits without additional protection device. An external protection device is only required if the supplying branch has an ampacity greater
than above. Thus, if an external protective device is necessary, or, utilized, a minimum value of 16 A B- or 8 A C- characteristic breaker
should be used.
9
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (June 2021, Rev.08)
TECHNICAL DATASHEET
Chrome DIN Rail Power Supply
24V 91.2W 1 Phase (Class II & NEC Class 2) / DRC-24V100W1A□
Overload & Overcurrent Protections (Auto-Recovery)
Overvoltage Protection (Latch Mode)
The power supply’s Overload (OLP) and Over current (OCP)
Protections will be activated when output current is 3.8 A < IO (Max
load) < 5.7 A. In such occurrence, the output voltage (VO) will start
to droop and once the output voltage is below 13 Vdc typ., the
power supply will go into “Hiccup mode” (Auto-Recovery). The
power supply will recover once the fault condition of the OLP and
OCP is removed and IO is back within the specifications.
The power supply’s overvoltage circuit will be activated when its
internal feedback circuit fails. The output voltage shall not exceed
its specifications defined on Page 3 under “Protections”. Power
supply will latch, and require removal/re-application of input AC
voltage in order to restart.
Additionally, if the IO is >102~108% for a prolong period of time
(depending on the load), the Over Temperature Protection (OTP)
will be activated due to high temperature on critical components.
The power supply will then go into “Latch mode” until the PSU cools
down and the AC power is recycled.
Over Temperature Protection (Latch Mode)
Short Circuit Protection (Auto-Recovery)
The power supply’s output OLP/OCP function also provides
protection against short circuits. When a short circuit is applied, the
output current will operate in “Hiccup mode”, as shown in the
illustration in the OLP/OCP section on this page. The power supply
will return to normal operation after the short circuit is removed.
10
The power supply should be latch.
As described in load de-rating section, the power supply also has
Over Temperature Protection (OTP). In the event of a higher
operating temperature at 100% load; or, when the operating
temperature is beyond what is recommended in the de-rating
graph, the OTP circuit will be activated. When activated, power
supply will latch, until the surrounding air temperature drops to its
normal operating temperature or the load is reduced as
recommended in the de-rating graph. Removal/re-application of
input AC voltage will then be required in order to restart.
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (June 2021, Rev.08)
TECHNICAL DATASHEET
Chrome DIN Rail Power Supply
24V 91.2W 1 Phase (Class II & NEC Class 2) / DRC-24V100W1A□
Operating Mode
Redundant Operation
In order to ensure proper redundant operation for the
power supply units (PSUs), the output voltage difference
between the two units must be kept at 0.45~0.50 V for
these 24 V supplies. Follow simple steps given below to
set them up for the redundant operation:
Step 1.
Measure output voltage of PSU 1 and PSU 2. If PSU 1 is
the master unit, then VO of PSU 1 must be higher than PSU
2. In order to set the output voltage, individually connect
each power supply to 50% of rated load at any line voltage,
and set the PSU 1 and PSU 2 output voltage.
Step 2.
Connect the power supply units PSU 1 and PSU 2 to Vin 1
& Vin 2, respectively, of the DRR-20N (or 20 A) module
shown on the right of above diagram.
**The Signal GND in the DRR module is for the built-in LED and DC OK signals. The Output
GND terminals from the two PSU’s do not need to be connected to the Signal GND terminal.
Fig. 3
Redundant Operation Connection Diagram
Fig. 4
Parallel Operation Connection Diagram
Step 3.
Connect the system load to Vout. Please note that output
voltage Vout from DRR module will be = VO (output voltage
of power supply) – Vdrop* (in DRR module).
*Vdrop will vary from 0.60 V to 0.90 V (Typical 0.65 V) depending on
the load current and surrounding air temperature.
Parallel Operation
The power supply units (PSUs) can also be used for
parallel operation in order to increase the output power.
The difference in output voltage between the two units
must be kept to within 25 mV of each other. This difference
must be verified with the same output load connected
independently to each unit.
Parameters such as EMI, inrush current, leakage current,
PARD, start up time will be different from those on the
datasheet, when two units are connected in parallel. The
user will need to verify that any differences will still allow
the two power supplies connected in parallel will work
properly in their product/application.
11
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (June 2021, Rev.08)
TECHNICAL DATASHEET
Chrome DIN Rail Power Supply
24V 91.2W 1 Phase (Class II & NEC Class 2) / DRC-24V100W1A□
Fig. 5
DC Input Operation Connection Diagram
DC Input Operation
Step 1.
Use a battery or similar DC source.
Step 2.
Connect +pole to L and -pole to N.
Step 3.
Connect the PE terminal to an earth wire or to the machine ground.
Fig. 6
2 of 3 Phase System Input Operation Connection Diagram
2 of 3 Phase System Input Operation
Delta's Chrome can use on 2 of 3 phase system. Please refer to the following step.
Step 1.
The input voltage applied from Line to Neutral is below the maximum rated input. The input voltage shall be below 240 Vac +10%.
Step 2.
The external protector is needed on N (Neutral) input line to secure a safety. N line does not have internal fuse protection. An appropriate
fuse or circuit breaker should be connected in series with N input line connection like the following.
12
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (June 2021, Rev.08)
TECHNICAL DATASHEET
Chrome DIN Rail Power Supply
24V 91.2W 1 Phase (Class II & NEC Class 2) / DRC-24V100W1A□
Others
PFC – Norm EN 61000-3-2
Line Current Harmonic content
Typically, the input current waveform is not sinusoidal due to the periodical peak charging of the input capacitor.
In industrial environment, complying with EN 61000-3-2 is only necessary under special conditions. Complying to
this standard can have some technical drawbacks, such as lower efficiency as well as some commercial aspects
such as higher purchasing costs. Frequently, the user does not profit from fulfilling this standard, therefore, it is
important to know whether it is mandatory to meet this standard for a specific application.
Attention
Delta provides all information in the datasheets on an “AS IS” basis and does not offer any kind of warranty through the information for
using the product. In the event of any discrepancy between the information in the catalog and datasheets, the datasheets shall prevail
(please refer to www.DeltaPSU.com for the latest datasheets information). Delta shall have no liability of indemnification for any claim
or action arising from any error for the provided information in the datasheets. Customer shall take its responsibility for evaluation of using
the product before placing an order with Delta.
Delta reserves the right to make changes to the information described in the datasheets without notice.
Manufacturer and Authorized Representatives Information
Manufacturer
Thailand
Delta Electronics (Thailand) PCL.
909 Pattana 1 Rd., Muang, Samutprakarn, 10280 Thailand
Taiwan
Delta Electronics, Inc.
3 Tungyuan Road, Chungli Industrial Zone, Taoyuan County
32063, Taiwan
Authorized Representatives
The Netherlands
Delta Greentech (Netherlands) B.V.
Zandsteen 15, 2132 MZ Hoofddorp, The Netherlands
13
United Kingdom
Delta Electronics Europe Limited
1 Redwood Court, Peel Park Campus,
East Kilbride, Glasgow, G74 5PF, United Kingdom
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (June 2021, Rev.08)