TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24 V 60 W 1 Phase, NEC Class 2 / DRP024V060W1N□
Highlights & Features
•
•
•
•
•
•
•
•
Universal AC input voltage range
Power will not de-rate for the entire input voltage range
UL 1310 safety approval
NEC Class 2 and Limited Power Source (LPS) approvals
Conforms to harmonic current IEC/EN 61000-3-2, Class A
Conformal coating on PCBAs to protect against common
dust and chemical pollutants
Hazardous Locations approval for ATEX and Class I, Div 2
(DRP024V060W1NY)
Certified according to IEC/EN/UL 62368-1
Safety Standards
CB Certified for worldwide use
Model Number:
DRP024V060W1N☐
Unit Weight:
0.33 kg (0.73 lb)
Dimensions (L x W x D): 120.6 x 32 x 119.3 mm
(4.75 x 1.26 x 4.70 inch)
General Description
Delta’s CliQ II DIN rail power supply series with UL 1310 and NEC Class 2 approvals offers start-of-the-art designs made to withstand
harsh industrial environments. The rugged plastic case is both shock and vibration resistant according to IEC 60068-2 and adheres to
IP20 protection level. The products can be used in general industrial applications, especially for dry indoor condition with the advantage
of lower wiring costs for a system due to its compliance with NEC Class 2 requirements. The NEC (National Electrical Code) is a North
American standard, which is regarded as a law in most North American states. The NEC describes the installation of electric conductors
and equipment within or on buildings. The Class 2 power units can operate over a wide temperature range of -25°C to +80°C (Cold Start
at -40°C). The products also feature universal AC input voltage range from 85 Vac to 264 Vac and the power will not de-rate throughout
the entire range. Another great feature is the conformal coating on the PCBA, which allows selected models to be certified to ATEX and
Class I, Div 2 for use in hazardous locations.
Model Information
CliQ II DIN Rail Power Supply
Model Number
Input Voltage Range
Rated Output Voltage
Rated Output Current
DRP024V060W1N☐
85-264 Vac (120-375 Vdc)
24 Vdc
2.50 A
Model Numbering
DR
P
024V
DIN Rail
Power Supply
Output Voltage Output Power
1
060W
1
N
□
Single Phase
NEC Class 2
Y - Plastic Case,
with Class I, Div 2 and ATEX
Z - Plastic Case,
without Class I, Div 2 and ATEX
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (June 2021, Rev. 08)
TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24 V 60 W 1 Phase, NEC Class 2 / DRP024V060W1N□
Specifications
Input Ratings / Characteristics
Nominal Input Voltage
100-240 Vac
Input Voltage Range
85-264 Vac
Nominal Input Frequency
50-60 Hz
Input Frequency Range
47-63 Hz
DC Input Voltage Range*
120-375 Vdc
Input Current
< 1.50A @ 115 Vac, < 0.80A @ 230 Vac
Efficiency at 100% Load
> 89.0% @ 115 Vac & 230 Vac
Max Power Dissipation
0% load
100% load
< 0.4 W @ 115 Vac, < 0.9 W @ 230 Vac
< 7.4 W @ 115 Vac & 230 Vac
Max Inrush Current (Cold Start)
< 40 A @ 115 Vac, < 80 A @ 230 Vac
Leakage Current
< 0.5 mA @ 240 Vac
*Fulfills test conditions for this range. DC input safety approval can be obtained upon request.
Output Ratings / Characteristics**
Nominal Output Voltage
24 Vdc
Factory Set Point Tolerance
24 Vdc ± 2%
Output Voltage Adjustment Range
22-28 Vdc
Output Current
2.50 A (60 W Max.)
Output Power
60 W
Line Regulation
< 0.5% (@ 85-264 Vac input, 100% load)
Load Regulation
< 1.0% (@ 85-264 Vac input, 0-100% load)
PARD*** (20 MHz)
< 240 mVpp
Rise Time
< 100 ms @ nominal input (100% load)
Start-up Time
< 3,000 ms @ nominal input (100% load)
Hold-up Time
> 20 ms @ 115 Vac,
> 125 ms @ 230 Vac (100% load)
Dynamic Response
(Overshoot & Undershoot O/P Voltage)
± 5% @ 85-264 Vac input, 0-100% load
(Slew Rate: 0.1 A/μs, 50% duty cycle @ 5 Hz to 1 KHz)
Start-up with Capacitive Loads
8,000 µF Max
**For power de-rating from 50°C to 80°C, see power de-rating on page 3.
***PARD is measured with an AC coupling mode, 5 cm wires, and in parallel with 0.1 μF ceramic capacitor & 47 μF electrolytic capacitor.
2
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (June 2021, Rev. 08)
TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24 V 60 W 1 Phase, NEC Class 2 / DRP024V060W1N□
Mechanical
Case Cover / Chassis
Plastic
Dimensions (L x W x D)
120.6 x 32 x 119.3 mm (4.75 x 1.26 x 4.70 inch)
Unit Weight
0.33 kg (0.73 lb)
Indicator
Green LED
Cooling System
Terminal
Wire
DC OK
Convection
Input
3 Pins (Rated 300 V / 30 A)
Output
2 Pins (Rated 300 V / 30 A)
Input / Output
AWG 20-10
Mounting Rail
Standard TS35 DIN Rail in accordance with EN 60715
Noise (1 Meter from power supply)
Sound Pressure Level (SPL) < 40 dBA
Environment
Surrounding Air Temperature
Operating
Storage
Power De-rating
-25°C to +80°C (Cold Start at -40°C)
-40°C to +85°C
Vertical Mounting
> 50°C de-rate power by 2.5% / °C,
> 70°C de-rate power by 4% / °C
Horizontal Mounting
> 50°C de-rate power by 2.5% / °C,
> 70°C de-rate power by 4% / °C
Operating Humidity
5 to 95% RH (Non-Condensing)
Operating Altitude
0 to 2,500 Meters (8,200 ft.)
Shock Test
Non-Operating
IEC 60068-2-27, 30 G (300 m/S²) for a duration of 18 ms,
1 time per direction, 2 times in total
Vibration
Non-Operating
IEC 60068-2-6, 10 Hz to 500 Hz @ 30 m/S² (3 G peak);
60 min per axis for all X, Y, Z direction
Bump Test
Operating
IEC 60068-2-29, Half Sine Wave: 10 G for a duration of 11 ms,
1,000 times per direction, 6,000 times in total
Over Voltage Category
III
Pollution Degree
2
According to IEC/EN 62477-1 / EN 60204-1
(clearance and creepage distances) and
IEC 62103 (safety part)
Protections
Overvoltage
< 32V, ±10%, SELV Output, Hiccup Mode,
Non-Latching (Auto-Recovery)
Overload / Overcurrent
> 110-150% of rated load current, Hiccup Mode,
Non-Latching (Auto-Recovery)
Over Temperature
< 80°C Surrounding Air Temperature @ 100% load,
Non-Latching (Auto-Recovery)
Short Circuit
Hiccup Mode, Non-Latching
(Auto-Recovery when the fault is removed)
Internal Fuse at L pin
T 3.15 A H
Degree of Protection
IP20
Protection Against Shock
Class I with PE* connection
*PE: Primary Earth
3
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (June 2021, Rev. 08)
TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24 V 60 W 1 Phase, NEC Class 2 / DRP024V060W1N□
Reliability Data
MTBF
> 800,000 hrs. as per Telcordia SR-332
I/P: 115 Vac & 230 Vac, O/P: 100% load, Ta: 25°C
Expected Cap Life Time
10 years (115 Vac & 230 Vac, 50% load @ 40°C)
Safety Standards / Directives
Electrical Equipment of Machines
EN/BS EN 60204-1 (over voltage category III)
Electrical Equipment for use in Electrical Power Installations
IEC/EN/BS 62477-1 / IEC 62103
Safety Entry Low Voltage
SELV (IEC 60950-1)
Electrical Safety
SIQ Bauart
UL/cUL recognized
CB Scheme
UKCA
Industrial Control Equipment
UL/cUL listed
CSA
Hazardous Location / ATEX
(For DRP024V060W1NY)
cCSAus
ATEX
Class 2 Power Supply
UL/cUL recognized
CE
UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E191395)
UL 62368-1 and CSA C22.2 No. 62368-1 (File No. E191395)
IEC 60950-1, IEC 62368-1, Limited Power Source (LPS)
BS EN 62368-1
UL 508 and CSA C22.2 No. 107.1-01 (File No. E315355)
CSA C22.2 No. 107.1-01 (File No. 181564)
CSA C22.2 No. 213-M1987, ANSI / ISA 12.12.01:2007
[Class I, Division 2, Group A, B, C, D T4, Ta= -25°C to +80°C
(> +50°C derating)]
EN 60079-0:2009, EN 60079-15:2010 [
II 3G Ex nA nC IIC
T4 Gc, Ta= -25°C to +80°C (> +50°C derating)]
Certificate No. EPS 12 ATEX 1 491 X
UL 1310 and CSA C22.2 No. 223 (File No. E350883)
In conformance with EMC Directive 2014/30/EU and
Low Voltage Directive 2014/35/EU
UKCA
Galvanic Isolation
4
EN 62368-1
Input to Output
For DRP024V060W1NY:
In conformance with Equipment for explosive atmospheres
(ATEX) directive 2014/34/EU
In conformance with Electrical Equipment (Safety) Regulations
2016 No. 1011 and
The Electromagnetic Compatibility Regulations 2016 No. 1091
4.0 KVac
Input to Ground
1.5 KVac
Output to Ground
1.5 KVac
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (June 2021, Rev. 08)
TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24 V 60 W 1 Phase, NEC Class 2 / DRP024V060W1N□
EMC
Emissions (CE & RE)
Generic Standards: CISPR 32, EN/BS EN 55032, CISPR 11,
EN/BS EN 55011, FCC Title 47: Class B
Component Power Supply for General Use
EN/BS EN 61204-3
Immunity
Generic Standards: EN/BS EN 55024, EN/BS EN 61000-6-2
Electrostatic Discharge
IEC 61000-4-2
Level 4 Criteria A1)
Air Discharge: 15 kV
Contact Discharge: 8 kV
Radiated Field
IEC 61000-4-3
Level 3 Criteria A1)
80 MHz-1 GHz, 10 V/M, 80% modulation (1 kHz)
Electrical Fast Transient / Burst
IEC 61000-4-4
Level 3 Criteria A1)
2 kV
Surge
IEC 61000-4-5
Level 3 Criteria A1)
Common Mode2): 2 kV
Differential Mode3): 2 kV
Conducted
IEC 61000-4-6
Level 3 Criteria A1)
150 kHz-80 MHz, 10 Vrms
Power Frequency Magnetic Fields
IEC 61000-4-8
Criteria A1)
10 A/Meter
Voltage Dips and Interruptions
IEC 61000-4-11
100% dip; 1 cycle (20 ms); Self Recoverable
Low Energy Pulse Test (Ring Wave)
IEC 61000-4-12
Harmonic Current Emission
Level 3 Criteria A1)
Common Mode2): 2 kV
Differential Mode3): 1 kV
IEC/EN/BS EN 61000-3-2, Class A
Voltage Fluctuation and Flicker
IEC/EN/BS EN 61000-3-3
1) Criteria A: Normal performance within the specification limits
2) Asymmetrical: Common mode (Line to earth)
3) Symmetrical: Differential mode (Line to line)
5
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (June 2021, Rev. 08)
TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24 V 60 W 1 Phase, NEC Class 2 / DRP024V060W1N□
Block Diagram
6
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (June 2021, Rev. 08)
TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24 V 60 W 1 Phase, NEC Class 2 / DRP024V060W1N□
Device Description
1)
2)
3)
4)
5)
Input terminal block connector
Output terminal block connector
DC Voltage adjustment potentiometer
DC OK control LED (Green)
Universal mounting rail system
Dimensions
L x W x D: 120.6 x 32 x 119.3 mm (4.75 x 1.26 x 4.70 inch)
7
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (June 2021, Rev. 08)
TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24 V 60 W 1 Phase, NEC Class 2 / DRP024V060W1N□
Engineering Data
Output Load De-rating VS Surrounding Air Temperature
Note
1.
2.
3.
Fig. 1
De-rating for Vertical and Horizontal Mounting Orientation
> 50°C de-rate power by 2.5% / °C,
> 70°C de-rate power by 4% / °C
4.
5.
Power supply components may degrade, or
be damaged, when the power supply is
continuously used outside the shaded region,
refer to the graph shown in Fig. 1.
If the output capacity is not reduced when
surrounding air temperature exceeds its
specification as defined on Page 3 under
“Environment”, the device will run into Over
Temperature Protection. When activated, the
output voltage will go into bouncing mode and
will recover when the surrounding air
temperature is lowered or the load is reduced
as far as necessary to keep the device in
working condition.
In order for the device to function in the
manner intended, it is also necessary to keep
a safety distance as recommended in the
safety instructions while the device is in
operation.
Depending on the surrounding air temperature
and output load delivered by the power
supply, the device can be very hot!
If the device has to be mounted in any other
orientation, please contact info@deltapsu.com
for more details.
Output Load De-rating VS Input Voltage
8
No output power de-rating across the entire
input voltage range
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (June 2021, Rev. 08)
TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24 V 60 W 1 Phase, NEC Class 2 / DRP024V060W1N□
Assembly & Installation
The power supply unit (PSU) can be mounted on 35 mm DIN rails in accordance with EN 60715. The device should be installed with
input terminal block at the bottom.
Each device is delivered ready to install.
Mounting
Dismounting
Fig. 2.1 Mounting
Fig. 2.2 Dismounting
Snap on the DIN rail as shown in Fig. 2.1:
1. Tilt the unit upwards and insert it onto the DIN rail.
2. Push downwards until stopped.
3. Press against the bottom front side for locking.
4. Shake the unit slightly to ensure that it is secured.
To uninstall, pull or slide down the latch with screw driver as
shown in Fig. 2.2. Then slide the power supply unit (PSU) in the
opposite direction, release the latch and pull out the power
supply unit (PSU) from the rail.
In accordance to EN 60950 / UL 60950 and EN 62368 / UL 62368, flexible cables require ferrules.
Use appropriate copper cables designed to sustain operating temperature of:
1. 60°C, 60°C / 75°C for USA
2. At least 75°C for ambient not exceeding 60°C, and 90°C for ambient exceeding 60°C for Canada.
9
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (June 2021, Rev. 08)
TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24 V 60 W 1 Phase, NEC Class 2 / DRP024V060W1N□
Safety Instructions
Horizontal Mounting
Vertical Mounting
•
ALWAYS switch mains of input power OFF before connecting and disconnecting the input voltage to the unit. If mains are not turned
OFF, there is risk of explosion / severe damage.
To guarantee sufficient convection cooling, keep a distance of 50 mm (1.97 inch) above and below the device as well as a
lateral distance of 20 mm (0.79 inch) to other units.
Note that the enclosure of the device can become very hot depending on the surrounding air temperature and load of the power
supply. Risk of burns!
Only plug in and unplug connectors when power is turned off!
DO NOT insert any objects into the unit.
Hazardous voltages may be present for up to 5 minutes after the input mains voltage is disconnected. Do not touch the unit during
this time.
The power supplies are built in units and must be installed in a cabinet or room (condensation free environment and indoor location)
that is relatively free of conductive contaminants.
CAUTION: “For use in a controlled environment”.
•
•
•
•
•
•
•
For DRP024V060W1NY:
•
The power supplies unit must be installed in an IP54 enclosure or cabinet in the final installation. The enclosure or cabinet must
comply with EN 60079-0 or EN 60079-15.
•
Warning: Explosion Hazard - Substitution of components may impair suitability for Class I, Division 2.
•
Warning: Explosion Hazard - Do not disconnect equipment or adjust potentiometer unless the power has been switched off or the
area is known to be non-hazardous.
10
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (June 2021, Rev. 08)
TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24 V 60 W 1 Phase, NEC Class 2 / DRP024V060W1N□
Functions
Graph illustrating the Start-up Time, Rise Time, and Hold-up Time
Start-up Time
The time required for the output voltage to reach 90% of its final steady state set value, after the input voltage is applied.
Rise Time
The time required for the output voltage to change from 10% to 90% of its final steady state set value.
Hold-up Time
Time between the collapse of the AC input voltage, and the output falling to 95% of its steady state set value.
Inrush Current
Dynamic Response
Inrush current is the peak, instantaneous, input current measured
and, occurs when the input voltage is first applied. For AC input
voltages, the maximum peak value of inrush current will occur
during the first half cycle of the applied AC voltage. This peak value
decreases exponentially during subsequent cycles of AC voltage.
The power supply output voltage will remains within ±5% of its
steady state value, when subjected to a dynamic load from 0 to
100% of its rated current.
50% duty cycle / 5Hz to 1KHz
External Input Protection Device
The unit is protected at the L pin, with an internal fuse that cannot be replaced. The power supply has been tested and approved on 20 A
(UL) and 16 A (IEC) branch circuits without additional protection device. An external protection device is only required if the supplying
branch has an ampacity greater than above. Thus, if an external protective device is necessary, or, utilized, please refer a minimum value
of 16 A B- or 8 A C- characteristic breaker.
11
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (June 2021, Rev. 08)
TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24 V 60 W 1 Phase, NEC Class 2 / DRP024V060W1N□
Overload & Overcurrent Protections (Auto-Recovery)
Overvoltage Protection (Auto-Recovery)
The power supply’s Overload (OLP) and Overcurrent (OCP)
Protections will be activated when output current (IO) exceeds its
specification as defined on Page 3 under “Protections”. In such
occurrence, the output voltage (VO) will start to droop and once the
power supply has reached its maximum power limit, the protection
is activated and the power supply will go into “Hiccup mode” (AutoRecovery). The power supply will recover once the fault condition
of the OLP and OCP is removed and IO is back within the
specifications.
The power supply’s overvoltage circuit will be activated when its
internal feedback circuit fails. The output voltage shall not exceed
its specifications defined on Page 3 under “Protections”.
Over Temperature Protection (Auto-Recovery)
It is not recommended to prolong the duration of IO when it is less
than OLP/OCP point, but greater than 100%, since it may cause
damage to the PSU.
As described in load de-rating section, the power supply also has
Over Temperature Protection (OTP). In the event of a higher
operating temperature at 100% load, the power supply will run into
OTP when the operating temperature is beyond what is
recommended in the de-rating graph. When activated, the output
voltage will go into bouncing mode until the temperature drops to
its normal operating temperature as recommended in the de-rating
graph.
Short Circuit Protection (Auto-Recovery)
The power supply’s output OLP/OCP function also provides
protection against short circuits. When a short circuit is applied, the
output current will operate in “Hiccup mode”, as shown in the
illustration in the OLP/OCP section on this page. The power supply
will return to normal operation after the short circuit is removed.
12
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (June 2021, Rev. 08)
TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24 V 60 W 1 Phase, NEC Class 2 / DRP024V060W1N□
Operating Mode
Redundant Operation
In order to ensure proper redundant operation for the power
supply unit (PSU), the output voltage difference between the
two units must be kept at 0.45~0.50 V for 24 V supplies. Follow
simple steps given below to set them up for the redundant
operation:
Step 1.
Measure output voltage of PSU 1 and PSU 2. If PSU 1 is the
master unit, then VO of PSU 1 must be higher than PSU 2. In
order to set the output voltage, individually connect the power
supply to 50% of rated load at any line voltage from 85264 Vac, and set the PSU 1 and PSU 2 output voltage.
Step 2.
Connect the power supply units PSU 1 and PSU 2 to Vin 1 &
Vin 2, respectively, of the DRR-20N (or 20 A) module shown
on the diagram on the right.
Step 3.
Connect the system load from Vout. Please note that output
voltage Vout from DRR module will be = VO (output voltage of
power supply) – Vdrop* (in DRR module).
**The Signal GND in the DRR module is for the built-in LED and DC OK signals. The Output
GND terminals from the two PSU’s do not need to be connected to the Signal GND
terminal.
Fig. 3
Redundant Operation Connection Diagram
Fig. 4
Parallel Operation Connection Diagram
*Vdrop will vary from 0.60 V to 0.90 V (Typical 0.65 V) depending on the load
current and surrounding air temperature.
Parallel Operation
The power supply units (PSUs) can also be used for parallel
operation in order to increase the output power. The difference
in output voltage between the two units must be kept to within
25 mV of each other. This difference must be verified with the
same output load connected independently to each unit.
Parameters such as EMI, inrush current, leakage current,
PARD, start up time will be different from those on the
datasheet, when two units are connected in parallel. The user
will need to verify that any differences will still allow the two
power supplies connected in parallel will work properly in their
product/application.
13
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (June 2021, Rev. 08)
TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24 V 60 W 1 Phase, NEC Class 2 / DRP024V060W1N□
Fig. 5
DC Input Operation Connection Diagram
DC Input Operation
Step 1.
Use a battery or similar DC source.
Step 2.
Connect +pole to L and -pole to N.
Step 3.
Connect the PE terminal to an earth wire or to the machine ground.
Fig. 6
2 of 3 Phase System Input Operation Connection Diagram
2 of 3 Phase System Input Operation
Delta's CliQ II can use on 2 of 3 phase system. Please refer to the following step.
Step 1.
The input voltage applied from Line to Neutral is below the maximum rated input. The input voltage shall be below 240 Vac +10%.
Step 2.
The external protector is needed on N (Neutral) input line to secure a safety. N line does not have internal fuse protection. An appropriate
fuse or circuit breaker should be connected in series with N input line connection like the following.
14
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (June 2021, Rev. 08)
TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24 V 60 W 1 Phase, NEC Class 2 / DRP024V060W1N□
Others
Conformal Coating
The Protective Coating Technology
Delta Electronics Group has designed the perfect dipping technique which penetrates everywhere including under
device, and prevents leakage. The conformal coating dipping can be applied to PCBAs or circuit board. The
coating preserves the performance of precision electronic primarily by preventing ionizable contaminants such as
salt from reaching circuit nodes, where the material slumps around sharp edges. This can be a problem especially
in highly conversing atmosphere.
Attention
Delta provides all information in the datasheets on an “AS IS” basis and does not offer any kind of warranty through the information for
using the product. In the event of any discrepancy between the information in the catalog and datasheets, the datasheets shall prevail
(please refer to www.DeltaPSU.com for the latest datasheets information). Delta shall have no liability of indemnification for any claim
or action arising from any error for the provided information in the datasheets. Customer shall take its responsibility for evaluation of using
the product before placing an order with Delta.
Delta reserves the right to make changes to the information described in the datasheets without notice.
Manufacturer and Authorized Representatives Information
Manufacturer
Thailand
Delta Electronics (Thailand) PCL.
909 Pattana 1 Rd., Muang, Samutprakarn, 10280 Thailand
Taiwan
Delta Electronics, Inc.
3 Tungyuan Road, Chungli Industrial Zone, Taoyuan County
32063, Taiwan
Authorized Representatives
The Netherlands
Delta Greentech (Netherlands) B.V.
Zandsteen 15, 2132 MZ Hoofddorp, The Netherlands
15
United Kingdom
Delta Electronics Europe Limited
1 Redwood Court, Peel Park Campus,
East Kilbride, Glasgow, G74 5PF, United Kingdom
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (June 2021, Rev. 08)