DRR-40N

DRR-40N

  • 厂商:

    DELTA(台达)

  • 封装:

    -

  • 描述:

    MODULEREDUNDANCY40ADINRAIL

  • 数据手册
  • 价格&库存
DRR-40N 数据手册
TECHNICAL DATASHEET CliQ II Redundancy Modules 20 A / DRR-20□, 40 A / DRR-40□ Highlights & Features • • • • • • • • Wide input and output range of 22-60 Vdc Very wide operating temperature from -40°C to +80°C Built-in 2 channel DC OK signal and alarm relay contact Support N+1 Redundancy connection Conformal coating on PCBAs to protect against common dust and chemical pollutants Hazardous Locations approval to ATEX and Class I, Div 2 (DRR-20A and DRR-40A) IP20 Certified Certified according to IEC/EN/UL 62368-1 Safety Standards CB Certified for worldwide use Model Number: DRR-20☐, DRR-40☐ Unit Weight: 0.38 kg (0.84 lb), 0.52 kg (1.15 lb) Dimensions (H x W x D): 121 x 50 x 122.1 mm (4.76 x 1.97 x 4.81 inch) General Description Delta’s CliQ II redundancy modules offer a variable input and output voltage from 22 Vdc to 60 Vdc. The DRR-20☐ and DRR-40☐ can operate over a wide temperature range of -40°C to -80°C. The state-of-the-art design is made to withstand harsh industrial environments. The rugged, compact aluminium case is shock and vibration resistant according to IEC 60068-2 standard. Due to the wide input and output voltage range from 22 Vdc to 60 Vdc, the redundancy modules are able to support power supply in parallel operation. These modules also have an alarm relay contact as an indicator. Model Information CliQ II Redundancy Module Model Number Input Voltage Range Rated Output Voltage Rated Output Current DRR-20☐ 22-60 Vdc Vin-0.65 V (typ.) 20.0 A DRR-40☐ 22-60 Vdc Vin-0.65 V (typ.) 40.0 A Model Numbering DR R– XXA □ DIN Rail Redundancy Module Output Current 20 - 20 A 40 - 40 A A - Metal Case, with Class I, Div N - Metal Case, without Class I, Div 2 1 All parameters are specified at 25°C ambient and AC input unless otherwise indicated. www.DeltaPSU.com (August 2022, Rev. 09.1) TECHNICAL DATASHEET CliQ II Redundancy Modules 20 A / DRR-20□, 40 A / DRR-40□ Specifications Input Ratings / Characteristics Nominal Input Voltage 24 Vdc and 48 Vdc Input Voltage Range 22-60 Vdc Input Current DRR-20☐ 20 A Max (1+1 Redundancy) = Nominal 2 x 12.5 A (N+1 Redundancy) = Nominal 2 x 10 A (Single Use) = Nominal 20 A DRR-40☐ 40 A Max (1+1 Redundancy) = Nominal 2 x 25 A (N+1 Redundancy) = Nominal 2 x 20 A (Single Use) = Nominal 40 A Efficiency > 97.0% typ. Max Power Dissipation Standby Mode Operating Mode 18 V ± 5% or < 30 V Max 48 V System: Both Vin1 & Vin2 > 36 V ± 5% or < 60 V Max *The LED will turn on when the Vin1 & Vin2 > 18 V ± 5% (for 24 V system) or > 36 V ± 5% (for 48 V system) and not more than 30 V (for 24 V system) or not more than 60 V (for 48 V system). The relay contacts will be closed. If Vin1 & Vin2 are under or over this range, the LED will turn off. Output Ratings / Characteristics Nominal Output Voltage Range Output Current Vin-0.65 V (typ.) DRR-20☐ 20 A Max DRR-40☐ 40 A Max Voltage Drop (Vin-Vout) 0.65 V typ. Mechanical Case Cover / Chassis Aluminium Dimensions (H x W x D) 121 x 50 x 122.1 mm (4.76 x 1.97 x 4.81 inch) Unit Weight LED Indicators DRR-20☐ 0.38 kg (0.84 lb) DRR-40☐ 0.52 kg (1.15 lb) Green LED Cooling System Terminal Wire DC OK: Vin1 and Vin2 Convection DRR-20☐ Input: 3 Pins (Rated 300 V / 30 A) Output: 4 Pins (Rated 300 V / 30 A) DRR-40☐ Input: 5 Pins (Rated 300 V / 30 A) Output: 5 Pins (Rated 300 V / 30 A) Input / Output AWG 12-10 Mounting Rail Standard TS35 DIN Rail in accordance with EN 60715 Noise (1 Meter from power supply) Sound Pressure Level (SPL) < 40 dBA 2 All parameters are specified at 25°C ambient and AC input unless otherwise indicated. www.DeltaPSU.com (August 2022, Rev. 09.1) TECHNICAL DATASHEET CliQ II Redundancy Modules 20 A / DRR-20□, 40 A / DRR-40□ Environment Surrounding Air Temperature Power De-rating Operating -40°C to +80°C Storage -40°C to +85°C Vertical Mounting > 50°C de-rate power by 2.5% / °C Horizontal Mounting > 50°C de-rate power by 2.5% / °C Operating Humidity 5 to 95% RH (Non-Condensing) Operating Altitude 0 to 2,500 Meters (8,200 ft.) Shock Test Non-Operating IEC 60068-2-27, 30 G (300 m/s²) for a duration of 18 ms, 1 time per direction, 2 times in total Vibration Non-Operating IEC 60068-2-6, 10 Hz to 500 Hz @ 30 m/s² (3 G peak); 60 min per axis for all X, Y, Z direction Over Voltage Category III Pollution Degree 2 According to IEC/EN 62477-1 / EN 60204-1 (clearance and creepage distances) and IEC 62103 (safety part) Protections Overload / Overcurrent* Short Circuit DRR-20☐ < 25 A, No Damage DRR-40☐ < 50 A, No Damage DRR-20☐ < 25 A, No Damage DRR-40☐ < 50 A, No Damage Degree of Protection IP20 Protection Against Shock Class III with PE** connection *The overload condition must be controlled by the PSUs in parallel. The limit of input current should not be more than 25 A (for 20 A module) or not more than 50 A (for 40 A module). **PE: Primary Earth Reliability Data MTBF 3 > 800,000 hrs. as per Telcordia SR-332 I/P: 24 Vdc and 48 Vdc, O/P: 100% load, Ta: 25°C All parameters are specified at 25°C ambient and AC input unless otherwise indicated. www.DeltaPSU.com (August 2022, Rev. 09.1) TECHNICAL DATASHEET CliQ II Redundancy Modules 20 A / DRR-20□, 40 A / DRR-40□ Safety Standards / Directives Electrical Equipment of Machines EN/BS EN 60204-1 (over voltage category III) Electrical Equipment for Use in Electrical Power Installations IEC/EN/BS EN 62477-1 / IEC 62103 Electrical Safety EN 62368-1 SIQ Bauart UL/cUL recognized CB scheme UKCA Industrial Control Equipment Hazardous Location / ATEX (For DRR-20A and DRR-40A) UL/cUL recognized IEC 60950-1, IEC 62368-1 BS EN 62368-1 UL 508 and CSA C22.2 No. 107.1-01 (File No. E315355) cCSAus CSA C22.2 No. 213-M1987 and ANSI / ISA 12.12.01:2007 [Class I, Division 2, Group A, B, C, D T4, Ta= -40°C to +80°C (> +50°C derating)] ATEX EN 60079-0:2009, EN 60079-15:2010 [ II 3G Ex nA nC IIC T4 Gc, Ta= -40°C to +80°C (> +50°C derating)] Certificate No. EPS 12 ATEX 1 491 X K 60950-1 (DRR-40N only) KC CE In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU UKCA Galvanic Isolation 4 UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E191395) UL 62368-1 and CSA C22.2 No. 62368-1 (File No. E191395) Input & Output / PE For DRR-20A and DRR-40A: In conformance with Equipment for explosive atmospheres (ATEX) directive 2014/34/EU In conformance with Electrical Equipment (Safety) Regulations 2016 No. 1011 and The Electromagnetic Compatibility Regulations 2016 No. 1091 1.5 KVac All parameters are specified at 25°C ambient and AC input unless otherwise indicated. www.DeltaPSU.com (August 2022, Rev. 09.1) TECHNICAL DATASHEET CliQ II Redundancy Modules 20 A / DRR-20□, 40 A / DRR-40□ EMC Emissions (CE & RE) Generic Standards: CISPR 32, EN/BS EN 55032, KN 32 (DRR-20N and DRR-40N only), EN/BS EN 55011, FCC Title 47: Class B Immunity Generic Standards: EN/BS EN 55024, EN/BS EN 61000-6-2 KN 35 (DRR-20N and DRR-40N only) Electrostatic Discharge IEC 61000-4-2 Level 4 Criteria A1) Air Discharge: 15 kV Contact Discharge: 8 kV Radiated Field IEC 61000-4-3 Level 3 Criteria A1) 80 MHz – 1 GHz, 10 V/M, 80% modulation (1 kHz) Electrical Fast Transient / Burst IEC 61000-4-4 Level 3 Criteria A1) 2 kV Surge IEC 61000-4-5 Level 3 Criteria A1) Common Mode2): 2 kV Differential Mode3): 1 kV Conducted IEC 61000-4-6 Level 3 Criteria A1) 150 kHz – 80 MHz, 10 Vrms Power Frequency Magnetic Fields IEC 61000-4-8 Criteria A1) 10 A/Meter Voltage Dips and Interruptions IEC 61000-4-11 Level 3 Criteria A 1) Additional 100% dip; 1 cycle (20 ms); No Damage Low Energy Pulse Test (Ring Wave) IEC 61000-4-12 Level 3 Criteria A1) Common Mode2): 2 kV Differential Mode3): 1 kV Note: Product intended to be used as Apparatus with AC-DC Power Supply, EMC compliance to be verified in correspondence to the connected units. 1) Criteria A: Normal performance within the specification limits 2) Asymmetrical: Common (Line to earth) 3) Symmetrical: Differential mode (Line to line) 5 All parameters are specified at 25°C ambient and AC input unless otherwise indicated. www.DeltaPSU.com (August 2022, Rev. 09.1) TECHNICAL DATASHEET CliQ II Redundancy Modules 20 A / DRR-20□, 40 A / DRR-40□ Block Diagram DRR-20☐ DRR-40☐ 6 All parameters are specified at 25°C ambient and AC input unless otherwise indicated. www.DeltaPSU.com (August 2022, Rev. 09.1) TECHNICAL DATASHEET CliQ II Redundancy Modules 20 A / DRR-20□, 40 A / DRR-40□ Device Description DRR-20☐ DRR-40☐ 1) 2) 3) 4) 5) 7 Input terminal block connector Output terminal block connector LED indicator of Vin1 & Vin2 Universal mounting rail system Earth connection All parameters are specified at 25°C ambient and AC input unless otherwise indicated. www.DeltaPSU.com (August 2022, Rev. 09.1) TECHNICAL DATASHEET CliQ II Redundancy Modules 20 A / DRR-20□, 40 A / DRR-40□ Dimensions DRR-20☐ H x W x D: 121 x 50 x 122.1 mm (4.76 x 1.97 x 4.81 inch) DRR-40☐ H x W x D: 121 x 50 x 122.1 mm (4.76 x 1.97 x 4.81 inch) 8 All parameters are specified at 25°C ambient and AC input unless otherwise indicated. www.DeltaPSU.com (August 2022, Rev. 09.1) TECHNICAL DATASHEET CliQ II Redundancy Modules 20 A / DRR-20□, 40 A / DRR-40□ Engineering Data Output Load De-rating VS Surrounding Air Temperature Note 1. 2. 3. 4. 5. Fig. 1 De-rating for Vertical and Horizontal Mounting Orientation > 50°C de-rate power by 2.5% / °C The unit may degrade, or be damaged, when it is continuously used outside the shaded region, refer to the graph shown in Fig. 1. If the output capacity is not reduced when the surrounding air temperature exceeds its specification as defined on Page 3 under “Environment”, the device may have some thermal stress problem and the ORing Diodes may become too hot. In order for the device to function in the manner intended, it is also necessary to keep a safety distance as recommended in the safety instructions while the device is in operation. Depending on the surrounding air temperature and output load delivered by the power supply, the device can be very hot! If the device has to be mounted in any other orientation, please contact info@deltapsu.com for more details. Assembly & Installation The unit can be mounted on 35 mm (1.38 inch) DIN rails in accordance with EN 60715. The device should be installed with input terminal block at the top. Each device is delivered ready to install. Mounting Dismounting Fig. 2.1 Mounting Fig. 2.2 Dismounting Snap on the DIN rail as shown in Fig. 2.1: 1. Tilt the unit upwards and insert it onto the DIN rail. 2. Push downwards until stopped. 3. Press against the bottom front side for locking. 4. Shake the unit slightly to ensure that it is secured. To uninstall, pull or slide down the latch with screw driver as shown in Fig. 2.2. Then slide the unit in the opposite direction, release the latch and pull out the unit from the rail. In accordance to UL 60950 and EN 62368 / UL 62368, flexible cables require ferrules. Use appropriate copper cables designed to sustain operating temperature of 60°C / 75°C or more to fulfill UL requirements. 9 All parameters are specified at 25°C ambient and AC input unless otherwise indicated. www.DeltaPSU.com (August 2022, Rev. 09.1) TECHNICAL DATASHEET CliQ II Redundancy Modules 20 A / DRR-20□, 40 A / DRR-40□ Safety Instructions Horizontal Mounting  Vertical Mounting • ALWAYS switch mains of input power OFF before connecting and disconnecting the input voltage to the unit. If mains are not turned OFF, there is risk of explosion / severe damage. To guarantee sufficient convection cooling, please refer to the following instructions to ensure sufficient clearance around the device. Vertical Mounting: 50 mm (1.97 inch) above and below the device as well as a lateral distance of 20 mm (0.79 inch) to other units. Horizontal Mounting: 50 mm (1.97 inch) above and below the device as well as a lateral distance of 50 mm (1.97 inch) to other units. Note that the enclosure of the device can become very hot depending on the surrounding air temperature and load of the power supply. Risk of burns! The main power must be turned off before connecting or disconnecting wires to the terminals! DO NOT insert any objects into the unit. Hazardous voltages may be present for up to 5 minutes after the input mains voltage is disconnected. Do not touch the unit during this time. The supply of the unit shall comply with any isolated secondary circuit according to UL 508, Clause 32. • • • • • •  For DRR-20A and DRR-40A: • The unit must be installed in an IP54 enclosure or cabinet in the final installation. The enclosure or cabinet must comply with EN 60079-0 or EN 60079-15. • Warning: Explosion Hazard - Substitution of components may impair suitability for Class I, Division 2. • Warning: Explosion Hazard - Do not disconnect equipment unless the power has been switched off or the area is known to be nonhazardous. 10 All parameters are specified at 25°C ambient and AC input unless otherwise indicated. www.DeltaPSU.com (August 2022, Rev. 09.1) TECHNICAL DATASHEET CliQ II Redundancy Modules 20 A / DRR-20□, 40 A / DRR-40□ Functions Typical Application Notes Fig. 3.1 1+1 Redundancy Fig. 3.2 Single Use Using 1 more PSU as the redundant unit. Using more PSUs as the redundant units to increase the reliability. Fig. 3.3 N+1 Redundancy Connecting only one PSU to one DRR module to reduce the stress of the diodes and hence increase the reliability. 11 All parameters are specified at 25°C ambient and AC input unless otherwise indicated. www.DeltaPSU.com (August 2022, Rev. 09.1) TECHNICAL DATASHEET CliQ II Redundancy Modules 20 A / DRR-20□, 40 A / DRR-40□ Operating Mode  Redundant Operation In order to ensure proper redundant operation for the power supply unit (PSU), the output voltage difference between the two units must be kept at 0.45~0.50 V for 24 V supplies. Follow simple steps given below to set them up for the redundant operation: Step 1. Measure output voltage of PSU 1 and PSU 2. If PSU 1 is the master unit, then VO of PSU 1 must be higher than PSU 2. In order to set the output voltage, individually connect the power supply to 50% of rated load at any line voltage, and set the PSU 1 and PSU 2 output voltage. Step 2. Connect the right DRR module as per the system requirement to the power supply units PSU 1 and PSU 2 at Vin 1 & Vin 2 respectively Step 3. Connect the system load from Vout. Please note that output voltage Vout from DRR module will be = VO (output voltage of power supply) – Vdrop* (in DRR module). **The Signal GND in the DRR module is for the built-in LED and DC OK signals. The Output GND terminals from the two PSU’s do not need to be connected to the Signal GND terminal. Fig. 4 Redundant / Parallel Operation Connection Diagram *Vdrop will vary from 0.60 V to 0.90 V (Typical 0.65 V) depending on the load current and surrounding air temperature.  Parallel Operation These DRR modules can also be used for Parallel function in order to increase the output power by N+1 (e.g. 2.5 A + 2.5 A = 5 A or 2.5 A + 2.5 A + 2.5 A = 7.5 A) or current sharing, and thus increasing the power supply and system reliability. A good current sharing between two power supplies can be achieved by following simple steps as below (Refer to Fig. 4 for the Connection Diagram). Step 1. Set output load condition for both supplies at 50% and measure the output voltages. Step 2. Adjust output voltages to the same level or within ±25 mV difference. 12 Step 3. Connect PSU 1 and PSU 2 with the DRR module and measure at Vin 1 & Vin 2 to verify the voltage difference. Ensure the voltages are within ±25 mV. Step 4. Output voltage from DRR module Vout will be = VO (output voltage of power supply) – Vdrop* (in DRR module). All parameters are specified at 25°C ambient and AC input unless otherwise indicated. www.DeltaPSU.com (August 2022, Rev. 09.1) TECHNICAL DATASHEET CliQ II Redundancy Modules 20 A / DRR-20□, 40 A / DRR-40□ Others Conformal Coating The Protective Coating Technology Delta Electronics Group has designed the perfect dipping technique which penetrates everywhere including under device, and prevents leakage. The conformal coating dipping can be applied to PCBAs or circuit board. The coating preserves the performance of precision electronic primarily by preventing ionizable contaminants such as salt from reaching circuit nodes, where the material slumps around sharp edges. This can be a problem especially in highly conversing atmosphere. Attention Delta provides all information in the datasheets on an “AS IS” basis and does not offer any kind of warranty through the information for using the product. In the event of any discrepancy between the information in the catalog and datasheets, the datasheets shall prevail (please refer to www.DeltaPSU.com for the latest datasheets information). Delta shall have no liability of indemnification for any claim or action arising from any error for the provided information in the datasheets. Customer shall take its responsibility for evaluation of using the product before placing an order with Delta. Delta reserves the right to make changes to the information described in the datasheets without notice. Manufacturer and Authorized Representatives Information Manufacturer Thailand Delta Electronics (Thailand) PCL. 909 Pattana 1 Rd., Muang, Samutprakarn, 10280 Thailand Taiwan Delta Electronics, Inc. 3 Tungyuan Road, Chungli Industrial Zone, Taoyuan County 32063, Taiwan Authorized Representatives The Netherlands Delta Greentech (Netherlands) B.V. Zandsteen 15, 2132 MZ Hoofddorp, The Netherlands 13 United Kingdom Delta Electronics Europe Limited 1 Redwood Court, Peel Park Campus, East Kilbride, Glasgow, G74 5PF, United Kingdom All parameters are specified at 25°C ambient and AC input unless otherwise indicated. www.DeltaPSU.com (August 2022, Rev. 09.1)
DRR-40N 价格&库存

很抱歉,暂时无法提供与“DRR-40N”相匹配的价格&库存,您可以联系我们找货

免费人工找货