TECHNICAL DATASHEET
Sync DIN Rail Power Supply
5 V 15 W 1 Phase (NEC Class 2) / DRS-5V30W1NZ
Highlights & Features
•
•
•
•
•
•
•
•
Ultra compact size and galvanic isolation up to 3.0KVac
Universal AC input voltage range and full power from
-10°C to +55°C operation
Up to 79.0% efficiency
Low earth leakage current < 0.5mA @ 264Vac
Built-in DC OK relay contact option available
Extreme low temperature cold start at -40°C
NEC Class 2 / Limited Power Source (LPS) certified
Certified according to IEC/EN/UL 62368-1
Safety Standards
CB Certified for worldwide use
Model Number:
DRS-5V30W1NZ
Unit Weight:
0.11 kg (0.24 lb)
Dimensions (L x W x D): 75 x 21 x 89.5 mm
(2.95 x 0.83 x 3.52 inch)
General Description
The ultra-compact and competitively priced Delta Sync DIN rail power supply series is designed for industrial applications requiring
highly reliable power supply within a tight space. The Sync series operates with universal AC input range and offers full power up to
55°C. The output is adjustable from 5.0-5.5 volts, and can support up to 3000 microfarads of load capacitance. A green LED indicates
output is present. All models in the series are certified according to IEC/UL 60950-1, IEC/EN/UL 62368-1 Information Technology
Equipment (ITE) and UL 508 Industrial Control Equipment (ICE). The series is also fully compliant with RoHS Directive (EU) 2015/863
for environmental protection. NEC Class 2 and Limited Power Source (LPS) approvals are available for this product.
Model Information
Sync DIN Rail Power Supply
Model Number
Input Voltage Range
Rated Output Voltage
Rated Output Current
DRS-5V30W1NZ
85-264 Vac (120-375 Vdc)
5 Vdc
3.0 A
Model Numbering
DR
S–
5V
30W
1
N
Z
DIN Rail
Product Series
S – Sync Series
Output Voltage
30W series
Single Phase
NEC Class 2
Without DC OK
Relay Contact
1
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (November 2021, Rev. 05)
TECHNICAL DATASHEET
Sync DIN Rail Power Supply
5 V 15 W 1 Phase (NEC Class 2) / DRS-5V30W1NZ
Specifications
Input Ratings / Characteristics
Nominal Input Voltage
100-240 Vac
Input Voltage Range
85-264 Vac
Nominal Input Frequency
50-60 Hz
Input Frequency Range
47-63 Hz
DC Input Voltage Range*
120-375 Vdc
Input Current
< 0.40 A @ 115 Vac, < 0.20 A @ 230 Vac
Efficiency at 100% Load
> 79.0% @ 115 Vac & 230 Vac
Max Power Dissipation
0% load
< 0.3 W @ 115 Vac & 230 Vac
100% load
< 4.0 W @ 115 Vac & 230 Vac
Max Inrush Current (Cold Start)
< 20 A @ 115 Vac, < 40 A @ 230 Vac
Leakage Current
< 0.5 mA @ 264 Vac
*Fulfills test conditions for DC input. Safety approval for DC input can be obtained upon request.
Output Ratings / Characteristics**
Nominal Output Voltage
5 Vdc
Factory Set Point Tolerance
5 Vdc ± 2%
Output Voltage Adjustment Range
5.0-5.5 Vdc
Output Current
3.0 A (15 W max.)
Output Power
15 W
Line Regulation
< 0.5% (@ 85-264 Vac, 100% load)
Load Regulation
< 1.0% (@ 85-264 Vac, 0-100% load)
PARD*** (20 MHz)
< 75 mVpp @ > 0°C to 70°C
< 150 mVpp @ 0°C to -20°C
Rise Time
< 30 ms @ nominal input (100% load)
Start-up Time
< 2,000 ms @ 115 Vac (100% load)
< 1,000 ms @ 230 Vac (100% load)
Hold-up Time
> 20 ms @ 115 Vac (100% load)
> 100 ms @ 230 Vac (100% load)
Dynamic Response
(Overshoot & Undershoot O/P Voltage)
± 5% @ 85-264 Vac input, 5-100% load
(Slew Rate: 0.1 A/μS, 50% duty cycle @ 5 Hz to 1 KHz)
Start-up with Capacitive Loads
3,000 µF Max
**For power de-rating from < -10°C to -20°C, and 55°C to 70°C, see power de-rating on page 3.
***PARD is measured with an AC coupling mode, 5cm wires, and in parallel with 0.1 μF ceramic capacitor & 47 μF electrolytic capacitor.
2
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (November 2021, Rev. 05)
TECHNICAL DATASHEET
Sync DIN Rail Power Supply
5 V 15 W 1 Phase (NEC Class 2) / DRS-5V30W1NZ
Mechanical
Case Cover / Chassis
Plastic
Dimensions (L x W x D)
75 x 21 x 89.5 mm (2.95 x 0.83 x 3.52 inch)
Unit Weight
0.11 kg (0.24 lb)
Indicator
Green LED
Cooling System
Terminal
Wire
DC OK
Convection
Input
3 Pins (Rated 300 V/16A)
Output
2 Pins (Rated 300 V/16 A)
Input / Output
AWG 22-12 / AWG 20-12
Mounting Rail
Standard TS35 DIN Rail in accordance with EN 60715
Noise (1 Meter from power supply)
Sound Pressure Level (SPL) < 25 dBA
Environment
Surrounding Air Temperature
Operating
Storage
-20°C to +70°C (Cold start at -40°C @ 40% load)
-40°C to +85°C
Power De-rating
-10°C to -20°C de-rate power by 2% / °C
> 55°C de-rate power by 3.33% / °C
Operating Humidity
5 to 95% RH (Non-Condensing)
Operating Altitude
Shock Test
Vibration
0 to 2,000 Meters (6,560 ft.)
Non-Operating
IEC 60068-2-27, Half Sine Wave: 50 G for a duration of 11 ms;
3 times per direction, 9 times in total
Operating
IEC 60068-2-27, Half Sine Wave: 10 G for a duration of 11 ms;
1 time in X axis
Non-Operating
Operating
IEC 60068-2-6, Random: 5-500 Hz; 2.09 Grms, 20 min per axis
for all X, Y, Z directions
IEC 60068-2-6, Sine Wave: 10-500 Hz; 2G peak; displacement
of 0.35 mm; 1 octave per min; 60 min per axis for all X, Y, Z
directions
Over Voltage Category
II
Pollution Degree
2
Protections
Overvoltage
< 7.245 V, SELV Output, Latch Mode
Overload / Overcurrent
105~140% of rated load current, Hiccup Mode,
Non-Latching (Auto-Recovery)
Over Temperature
< 75°C Surrounding Air Temperature @ 100% load,
Latch Mode
Short Circuit
Hiccup Mode, Non-Latching
(Auto-recovery when the fault is removed)
Internal Fuse at L pin
T3.15 A
Degree of Protection
IP20
Protection Against Shock
Class I with PE* connection
*PE: Primary Earth
3
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (November 2021, Rev. 05)
TECHNICAL DATASHEET
Sync DIN Rail Power Supply
5 V 15 W 1 Phase (NEC Class 2) / DRS-5V30W1NZ
Reliability Data
MTBF
Telcordia SR-332
MIL-HDBK-217F
Expected Cap Life Time
> 700,000 hrs
I/P: 115 Vac & 230 Vac,
O/P: 100% load, Ta: 25°C
305,000 hrs
I/P: 115 Vac & 230 Vac,
O/P: 100% load, Ta: 25°C
10 years (115 ac & 230 Vac, 50% load @ 40°C)
Safety Standards / Directives
Safety Entry Low Voltage
Electrical Safety
SELV (IEC 60950)
TUV Bauart
UL/cUL recognized
CB Scheme
UKCA
Industrial Control Equipment
Class 2 Power Supply
UL/cUL listed
UL/cUL recognized
CE
UKCA
Galvanic Isolation
4
Input to Output
EN 62368-1
UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E191395)
UL 62368-1 and CSA C22.2 No. 62368-1 (File No. E191395)
IEC 60950-1, IEC 62368-1, Limited Power Source (LPS)
BS EN 62368-1
UL 508 and CSA C22.2 No. 107.1-01 (File No. E315335)
UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E191395)
UL 62368-1 and CSA C22.2 No. 62368-1 (File No. E191395)
In conformance with EMC Directive 2014/30/EU and Low
Voltage Directive 2014/35/EU
In conformance with Electrical Equipment (Safety)
Regulations 2016 No. 1011 and
The Electromagnetic Compatibility Regulations 2016 No. 1091
3.0 KVac
Input to Ground
3.0 KVac
Output to Ground
0.5 KVac
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (November 2021, Rev. 05)
TECHNICAL DATASHEET
Sync DIN Rail Power Supply
5 V 15 W 1 Phase (NEC Class 2) / DRS-5V30W1NZ
EMC
Emissions (CE & RE)
Generic Standards: EN/BS EN 61000-6-3,
EN/BS EN 61000-6-4, CISPR 32, EN/BS EN 55032,
EN/BS EN 55011, FCC Title 47: Class B
Component Power Supply for General Use
EN 61204-3
Immunity
Generic Standards: EN/BS EN 55024, EN/BS EN 61000-6-1,
EN/BS EN 61000-6-2
Electrostatic Discharge
IEC 61000-4-2
Level 3 Criteria A1)
Air Discharge: 8 kV
Contact Discharge: 6 kV
Radiated Field
IEC 61000-4-3
Level 3 Criteria A1)
80 MHz-1 GHz, 10 V/M with 1 kHz tone / 80% modulation
1.4 GHz-2 GHz, 3 V/M with 1 kHz tone / 80% modulation
2 GHz-2.7 GHz, 1 V/M with 1 kHz tone / 80% modulation
Electrical Fast Transient / Burst
IEC 61000-4-4
Level 3 Criteria A1)
2 kV
Surge
IEC 61000-4-5
Level 3 Criteria A1)
Common Mode3): 2 kV
Differential Mode4): 1 kV
Conducted
IEC 61000-4-6
Level 3 Criteria A1)
150 kHz-80 MHz, 10 Vrms
Power Frequency Magnetic Fields
IEC 61000-4-8
Criteria A1)
30 A/Meter
Voltage Dips and Interruptions
IEC 61000-4-11
0% of 100 Vac, 20 ms
30% of 100 Vac, 10 ms
30% of 100 Vac, 500 ms
40% of 100 Vac, 200 ms
70% of 100 Vac, 500 ms
0% of 100 Vac, 5000 ms
0% of 240 Vac, 20 ms
70% of 240 Vac, 500 ms
0% of 240 Vac, 5000 ms
Low Energy Pulse Test (Ring Wave)
IEC 61000-4-12
Level 3 Criteria A1)
Common Mode3): 2 kV
Differential Mode4): 1 kV
Criteria A1)
Criteria A1)
Criteria B2)
Criteria B2)
Criteria A1)
Criteria B2)
Criteria A1)
Criteria A1)
Criteria B2)
Harmonic Current Emission
IEC/EN/BS EN 61000-3-2, Class A
Voltage Fluctuation and Flicker
IEC/EN/BS EN 61000-3-3
1) Criteria A: Normal performance within the specification limits
2) Criteria B: Temporary degradation or loss of function which is self-recoverable
3) Asymmetrical: Common mode (Line to earth)
4) Symmetrical: Differential mode (Line to line)
5
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (November 2021, Rev. 05)
TECHNICAL DATASHEET
Sync DIN Rail Power Supply
5 V 15 W 1 Phase (NEC Class 2) / DRS-5V30W1NZ
Block Diagram
Device Description
1)
2)
3)
4)
5)
6
Input terminal block connector
Output terminal block connector
DC voltage adjustment potentiometer
DC OK LED (Green)
Universal mounting system
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (November 2021, Rev. 05)
TECHNICAL DATASHEET
Sync DIN Rail Power Supply
5 V 15 W 1 Phase (NEC Class 2) / DRS-5V30W1NZ
Dimensions
L x W x D: 75 x 21 x 89.5 mm [2.95 x 0.83 x 3.52 inch]
Engineering Data
Output Load De-rating VS Surrounding Air Temperature
Note
1.
2.
3.
Fig. 1
De-rating for Vertical Mounting Orientation
-10°C to -20°C de-rate power by 2% / °C
> 55°C de-rate power by 3.33% / °C
4.
5.
7
Power supply components may degrade, or
be damaged, when the power supply is
continuously used outside the shaded region,
refer to the graph shown in Fig. 1.
If the output capacity is not reduced when the
surrounding air temperature exceeds its
specification as defined on Page 3 under
“Environment”, the device will run into Over
Temperature Protection. When activated,
power supply will latch, until the surrounding
air temperature is lowered or the load is
reduced as far as necessary to keep the
device in working condition, and require
removal/re-application of input AC voltage in
order to restart.
In order for the device to function in the
manner intended, it is also necessary to keep
a safety distance as recommended in the
safety instructions while the device is in
operation.
Depending on the surrounding air temperature
and output load delivered by the power
supply, the device can be very hot!
If the device has to be mounted in any other
orientation,
please
contact
info@deltapsu.com for more details.
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (November 2021, Rev. 05)
TECHNICAL DATASHEET
Sync DIN Rail Power Supply
5 V 15 W 1 Phase (NEC Class 2) / DRS-5V30W1NZ
Output Load De-rating VS Input Voltage
No output power de-rating across the entire
input voltage range
Assembly & Installation
The power supply unit (PSU) can be mounted on 35mm DIN rails in accordance with EN60715. The device should be installed with input
terminal block at the bottom.
Each device is delivered ready to install.
Mounting
Dismounting
Fig. 2.1 Mounting
Fig. 2.2 Dismounting
Snap on the DIN rail as shown in Fig. 2.1:
1. Tilt the unit slightly upwards and put it onto the DIN rail.
2. Push downwards until stopped.
3. Press against the bottom front side for locking.
4. Shake the unit slightly to ensure that it is secured.
To uninstall, pull or slide down the latch with screw driver as
shown in Fig. 2.2. Then slide the power supply unit (PSU) in
the opposite direction, release the latch and pull out the power
supply unit (PSU) from the rail.
8
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (November 2021, Rev. 05)
TECHNICAL DATASHEET
Sync DIN Rail Power Supply
5 V 15 W 1 Phase (NEC Class 2) / DRS-5V30W1NZ
Safety Instructions
•
•
•
•
•
•
•
•
9
ALWAYS switch mains of input power OFF before connecting and
disconnecting the input voltage to the device. If mains are not turned OFF,
there is risk of explosion / severe damage.
To guarantee sufficient convection cooling, keep a distance of > 40 mm
(1.57 inch) above and > 20 mm (0.79 inch) below the device as well as a
lateral distance of > 15 mm (0.59 inch) to other units including heat
source.
Note that the enclosure of the device can become very hot depending on the
surrounding air temperature and output load connected to the device. Risk of
burns!
The main power must be turned off before connecting or disconnecting the
wires to the terminals!
DO NOT insert any objects into the device.
Dangerous voltages present for at least 5 minutes after disconnecting all
sources of power.
The power supplies unit should be installed in minimum IP54 rated enclosure.
The power supplies are built in units and must be installed in a cabinet or
room (condensation free environment and indoor location) that is relatively
free of conductive contaminants.
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (November 2021, Rev. 05)
TECHNICAL DATASHEET
Sync DIN Rail Power Supply
5 V 15 W 1 Phase (NEC Class 2) / DRS-5V30W1NZ
Functions
Graph illustrating the Start-up Time, Rise Time, and Hold-up Time
Start-up Time
The time required for the output voltage to reach 90% of its final steady state set value, after the input voltage is applied.
Rise Time
The time required for the output voltage to change from 10% to 90% of its final steady state set value.
Hold-up Time
Time between the collapse of the AC input voltage, and the output falling to 95% of its steady state set value.
Inrush Current
Dynamic Response
Inrush current is the peak, instantaneous, input current measured
and, occurs when the input voltage is first applied. For AC input
voltages, the maximum peak value of inrush current will occur
during the first half cycle of the applied AC voltage. This peak value
decreases exponentially during subsequent cycles of AC voltage.
The power supply output voltage will remains within ±5% of its
steady state value, when subjected to a dynamic load from 5% to
100% of its rated current.
10
50% duty cycle / 5Hz to 1KHz
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (November 2021, Rev. 05)
TECHNICAL DATASHEET
Sync DIN Rail Power Supply
5 V 15 W 1 Phase (NEC Class 2) / DRS-5V30W1NZ
Overload & Overcurrent Protections (Auto-Recovery)
Overvoltage Protection (Latch Mode)
The power supply’s Overload (OLP) and Overcurrent (OCP)
Protections will be activated when output current (IO) exceeds its
specification as defined on Page 3 under “Protections”. In such
occurrence, the output voltage (VO) will start to droop and once the
power supply has reached its maximum power limit, the protection
is activated and the power supply will go into “Hiccup mode” (AutoRecovery). The power supply will recover once the fault condition
of the OLP and OCP is removed and IO is back within the
specifications.
The power supply’s overvoltage circuit will be activated when its
internal feedback circuit fails. The output voltage shall not exceed
its specifications defined on Page 3 under “Protections”. Power
supply will latch off, and require removal/re-application of input AC
voltage in order to restart.
The power supply should be latch.
Over Temperature Protection (Latch Mode)
It is not recommended to prolong the duration of IO when it is less
than OLP/OCP point, but greater than 100%, since it may cause
damage to the PSU.
Short Circuit Protection (Auto-Recovery)
The power supply’s output Short Circuit Protection function also
provides protection against short circuits. When a short circuit is
applied, the output current will operate in “Hiccup mode”. The
power supply will return to normal operation after the short circuit
is removed.
As described in load de-rating section, the power supply also has
Over Temperature Protection (OTP). In the event of a higher
operating temperature at 100% load; or, when the operating
temperature is beyond what is recommended in the de-rating
graph, the OTP circuit will be activated. When activated, power
supply will latch off, until the surrounding air temperature drops to
its normal operating temperature or the load is reduced as
recommended in the de-rating graph. Removal/re-application of
input AC voltage will then be required in order to restart.
External Input Protection Device
The unit is protected with internal fuse (not replaceable) at L pin and it has been tested and approved on 20A (UL) and 16A (IEC) branch
circuits without additional protection device. An external protection device is only required if the supplying branch has an ampacity greater
than above. Thus, if an external protective device is necessary, or, utilized, a minimum value of 10A B- or 6A C- characteristic breaker
should be used.
11
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (November 2021, Rev. 05)
TECHNICAL DATASHEET
Sync DIN Rail Power Supply
5 V 15 W 1 Phase (NEC Class 2) / DRS-5V30W1NZ
Others
Attention
Delta provides all information in the datasheets on an “AS IS” basis and does not offer any kind of warranty through the information for
using the product. In the event of any discrepancy between the information in the catalog and datasheets, the datasheets shall prevail
(please refer to www.DeltaPSU.com for the latest datasheets information). Delta shall have no liability of indemnification for any claim
or action arising from any error for the provided information in the datasheets. Customer shall take its responsibility for evaluation of using
the product before placing an order with Delta.
Delta reserves the right to make changes to the information described in the datasheets without notice.
Manufacturer and Authorized Representatives Information
Manufacturer
Thailand
Delta Electronics (Thailand) PCL.
909 Pattana 1 Rd., Muang, Samutprakarn, 10280 Thailand
Taiwan
Delta Electronics, Inc.
3 Tungyuan Road, Chungli Industrial Zone, Taoyuan County
32063, Taiwan
Authorized Representatives
The Netherlands
Delta Greentech (Netherlands) B.V.
Zandsteen 15, 2132 MZ Hoofddorp, The Netherlands
12
United Kingdom
Delta Electronics Europe Limited
1 Redwood Court, Peel Park Campus,
East Kilbride, Glasgow, G74 5PF, United Kingdom
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.