\ Basic Wiring Diagram
Thank you for choosing DELTA’s braking module. VFDB braking units are applied to absorb the motor regeneration energy
when the three-phase induction motor stops by deceleration. With VFDB braking unit, the regeneration energy will be
dissipated in dedicated braking resistors. To prevent mechanical or human injury, please refer to this instruction sheet before
wiring. VFDB braking units are suitable for DELTA AC Motor Drives VFD Series 460V. VFDB braking units need to be used in
conjunction with BR series braking resistors to provide the optimum braking characteristics. The content of this instruction
sheet may be revised without prior notice. Please consult our distributors or download the most updated version at
http://www.delta.com.tw/industrialautomation.
Y Specifications
VFDB Braking Units
Specification
460V Series
Model VFDB□□□□
Input
Rating
Output
Rating
Max. Motor Capacity (KW)
Max. Discharge Current
(A) 10%ED
Continuous Discharge
Current (A)
Braking Start-up Voltage
(DC)
Protection
Over-current level (A)
Model no.
Specification
4110
4160
4185
BR1K5W005
1500W 5.0Ω
110
160
185
BR1K2W6P8
1200W 6.8Ω
126
190
225
BR1K2W008
1200W 8.0Ω
45
50
100
BR1K5W012
1500W 12Ω
618/642/667/690/725/750±6V
BR1K2W015
1200W 15Ω
400-750VDC
BR1K5W040
1500W 40Ω
DC Voltage
Min. Equivalent Resistor for
Each Braking Unit
Environment
Braking Resistors
6Ω
4Ω
3.4Ω
BR1K0W050
1000W 50Ω
190
290
340
BR1K0W075
1000W 75Ω
Power Charge Display
Blackout until bus(DC+~DC-)voltage is below
100VDC
Overheat Alarm Output
Relay contact 3A 250Vac/28Vdc(RA.RC)
Installation Location
Indoor(no corrosive gases, metallic dust)
Operating Temperature
-10℃~+50℃ (14oF to 122oF)
Storage Temperature
-20℃~+60℃ (-4oF to 140oF)
Humidity
Less than 90%RH Non-condensing
2
Z Dimensions
-Braking Resistors
Mechanical Configuration
Do not proceed with wiring while power is applied to the circuit.
The wiring gauge and distance must comply with the electrical code.
The +(P), -(N) terminals of the AC motor drive (VFD Series), connected to the braking unit (VFDB), must be
confirmed for correct polarity lest the drive and the braking unit be damaged when power on.
When the braking unit performs braking, the wires connected to DC+, DC-, B1 and B2 would generate a
powerful electromagnetic field for a moment due to high current passing through. These wires should be wired
separately from other low voltage control circuits lest they make interference or mis-operation.
To prevent personal injury, do not connect/disconnect wires or Inflammable solids, gases or liquids must be avoided at
regulate the setting of the braking unit while power on. Do not
the location where the braking resistor is installed. The
touch the terminals of related wiring and any component on
braking resistor had better be installed in individual
PCB lest users be damaged by extreme dangerous DC high
metallic box with forced air-cooling.
voltage.
Connect the ground terminal to the Earth Ground. The
ground lead must be at least the same gauge wire as
Do not connect DC reactor between the braking unit and the
DC-bus capacitor of the AC motor driver.
leads +(P), -(N).
Wiring distance
Please install the braking resistor with forced air-cooling
or the equivalent when frequent deceleration braking is
performed (over 10%ED).
The ring terminals are suggested to be used for main
circuit wiring. Make sure the terminals are fastened
before power on.
Braking Time
Function Explanation
T1
Cycle Time
OC
The SLAVE braking application of three braking
units is shown as the above diagram. After wiring,
the jumper of first unit shall be set as “MASTER”
and that of others must be set as “SLAVE” to
complete the system installation.
OH
-(N)
Circuit
SLAVE Circuit
Fault Circuit
Wire Gauge AWG (mm )
Screw
Torque
DC+,DC-
4~6AWG (21.2~13.3mm2)
M8
30 kgf-cm (26 in-lbf)
B1,B2
4~6AWG (21.2~13.3mm2)
M8
30 kgf-cm (26 in-lbf)
2
18~20AWG (0.8~0.5mm )
(with shielded wires)
M2
4 kgf-cm (3 in-lbf)
18~20AWG (0.8~0.5mm2)
M2
4 kgf-cm (3 in-lbf)
M1,M2
Input
S1,S2
RA,RC
380Vac
400Vac
415Vac
440Vac
460Vac
480Vac
Braking Start-up voltage
DC Bus (DC+,DC-) Voltage
618Vdc
642Vdc
667Vdc
690Vdc
725Vdc
750Vdc
NOTE: Input Power With Tolerance ±10%
480V
460V
440V Input Voltage Se tting
415V
400V
380V
M
DC+ DC -
DC+ DC -
S1
S2
S1
S2
M1
M2
M1: SLAVE output signal+
M2: SLAVE output signalS1: SLAVE input signal+
S2: SLAVE input signal-
M
B2
BR
B1
O.L.
B2
BR
M1 M2
S
S
B1
O.L.
S1 S2
RA RC
SLAVE output/input terminal
NOTE: Please use shielded
wires while wiring.
B2
BR
` Braking Resistors & Braking Units Use in the AC Drives
Applicable
Motor
125% Braking Torque/ 10%ED
HP
KW
Braking
Torque
(kg-M)
Resistor Value
Spec. for Each
AC Motor Drive
150
175
215
250
300
375
425
475
110
132
160
185
220
280
315
355
74.5
89.4
108.3
125.3
148.9
189.6
213.3
240.3
12000W 6Ω
18000W 4Ω
18000W 4Ω
21000W 3.4Ω
24000W 3Ω
36000W 2Ω
36000W 2Ω
42000W 1.7Ω
Braking Unit
Part No. and
Quantity
4110
4160
4160
4185
4110
4160
4160
4185
1
1
1
1
2
2
2
2
Braking Resistors
Part No. and Quantity
BR1K2W015
BR1K5W012
BR1K5W012
BR1K5W012
BR1K2W015
BR1K5W012
BR1K5W012
BR1K5W012
10
12
12
14
20
24
24
28
Max.
Discharge
Current (A)
Min. Equivalent
Resistor Value
126
190
190
225
252
380
380
450
6Ω
4Ω
4Ω
3.4Ω
3Ω
2Ω
2Ω
1.7Ω
a Wiring Examples of Braking Resistors
NOTE: Before wiring, please notice equivalent resistors value shown in the column “Equivalent resistors specification for each
braking unit” in the above table to prevent damage.
460V 150HP
460V 175HP/215HP
460V 250HP
460V 375HP/425HP
Before regulating the power voltage, make sure the power has been turned off. Please set power voltage as the possible
highest voltage for unstable power system. Take 380VAC power system for example. If the voltage may be up to 410Vac,
415VAC should be regulated.
For DELTA’s AC motor drive VFD Series, please set parameter (Over Voltage Stall Prevention) as “close” to disable
over-voltage stall prevention, to ensure stable deceleration characteristic.
460V Model AC Power Voltage
Terminal Mark
Output
M1
M2
B1
The Selection of Power Voltage and Operation Potential of PN DC Voltage
Terminal Wire Gauge
Power Input
Circuit
Braking
Resistor
DC+ DC -
VFD
Series
NOTE
2
The position of the jumper
MASTER/SLAVE
SETTING JUMPER
ED% = T1/T0x100(%)
1. Regulation of power voltage: the power source of the braking unit is DC voltage from +(P), -(N) terminals of the AC motor
drive. It is very important to set the power voltage of the braking unit based on the input power of the AC motor drive before
operation. The setting has a great influence on the potential of the operation voltage for the braking unit. Please refer to the
table below.
480V
460V
440V
415V
400V
380V
S
+( P)
_ The Voltage Settings
VFDB
OH
Overheat lamp
2. MASTER/SLAVE setting: The MASTER/SLAVE jumper is set “MASTER” as factory setting. The “SLAVE” setting is applied to
two or more braking units in parallel, making these braking units be enabled/disabled synchronously. Then the power
dissipation of each unit will be equivalent so that they can perform the braking function completely.
T0
Explanation: The definition of the barking usage ED(%) is for assurance of enough time for the braking unit and braking resistor
to dissipate away heat generated by braking. When the braking resistor heats up, the resistance would increase with
temperature, and braking torque would decrease accordingly.
CHARGE ACT
OC
Over-current
lamp
100%
[ Individual Parts and
- VFDB Braking Units
Brake lamp
Input Voltage Setting
Factory setting:440V
] Wiring Notice
Wall-mounted enclosed type IP10
Z Dimensions
Power lamp
O.L.
^ Definition for Braking Usage ED%
2
9.8m/s (1G)under 20Hz、2m/s (0.2G)at
20~50Hz
Vibration
6. Besides using thermal overload relay to be the protection system and braking resistor, temperature switch can be installed on
braking resistor side as the protection. The temperature switch must comply with the braking resistor specification or contact your
dealer.
CHARGE ACT
Voltage
X Preface
Operation Explanation:
1. For safety consideration, install an overload relay between the braking unit and the braking resistor. In conjunction with the
magnetic contactor (MC) prior to the drive, it can perform complete protection against abnormality.
2. The purpose of installing the thermal overload relay is to protect the braking resistor from damage due to frequent braking,
or due to braking unit keeping operating resulted from unusual high input voltage. Under such circumstance, just turn off
the power to prevent damaging the braking resistor.
3. Please refer to the specification of the thermal overload relay.
4. The alarm output terminals (RA, RC) of the braking unit will be activated when the temperature of the heat sink exceeds
o
o
80 C. It means that the temperature of the installation environment may exceed 50 C, or the braking %ED may exceed
10%ED. With this kind of alarm, please install a fan to force air-cooling or reduce the environment temperature. If the
condition isn’t due to the temperature, the control circuit or the temperature sensor may have been damaged. At this time,
please send the braking unit back to the manufacturer or agency for repair.
NFB
5. The AC Motor Drive and braking unit
MC
Motor
R/L1
U/T1
R/L1
will be electrified at the same time while
S/L2
V/T2
S/L2
IM
turning on the NFB (No-fuse breaker). For
Thermal
T/L3
W/T3
T/L3
the operation/stop method of the motor,
Overload
please refer to the user manual of the AC
O.L.
VFD Series
Relay
MC
+(P)
DC+
B1
Motor Drives VFD Series. The braking unit
O.L.
DC- VFDB
-(N)
will detect the inner DC voltage of the AC
SA
BR
Brake
E.F
RA
Surge Absorber
motor drive when it stops the motor by
Brake
Unit
DCM
RC
B2
Resistor
deceleration. The extra regeneration will
Therm al Overload
be dissipated away rapidly by the braking
Relay or Tem perature switch
Temperature switch
resistor in the form of heat. It can ensure
the stable deceleration characteristic.
460V
VFDB Series Braking Modules Instruction Sheet
Input voltage setting for VFD B 4110/4160/4185
460V 475HP
460V 300HP
很抱歉,暂时无法提供与“VFDB4045”相匹配的价格&库存,您可以联系我们找货
免费人工找货