Nominal data
Type
R2E250-AS47-05
Motor
M2E068-EC
Phase
1~
Nominal voltage
VAC
230
Frequency
Hz
50
Type of data definition
fa
Valid for approval / standard
-
Speed
min-1
2600
Power input
W
155
Current draw
A
0.70
Motor capacitor
µF
5
Capacitor voltage
VDB
400
Capacitor standard
P2 (CE)
Min. back pressure
Pa
0
Min. ambient temperature
°C
-25
Max. ambient temperature
°C
40
Starting current
A
1.3
ml = Max. load · me = Max. efficiency · fa = Running at free air · cs = Customer specs · cu = Customer unit
Subject to alterations
Item no. 11002-5-9980 · Revision 79566 · Release 2013-06-06 · Page 1 / 5
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
AC centrifugal fan
R2E250-AS47-05
backward curved, single inlet
Technical features
Mass
3 kg
Size
250 mm
Surface of rotor
Coated in black
Material of impeller
PA plastic, fibreglass-reinforced
Number of blades
11
Direction of rotation
Clockwise, seen on rotor
Type of protection
IP 44; Depending on installation and position as per EN 60034-5
Insulation class
"B"
Humidity class
F1-2
Max. permissible ambient motor
temp. (transp./ storage)
+ 80 °C
Min. permissible ambient motor
temp. (transp./storage)
- 40 °C
Mounting position
Shaft horizontal or rotor on bottom; rotor on top on request
Condensate discharge holes
Rotor-side
Operation mode
S1
Motor bearing
Ball bearing
Touch current acc. IEC 60990
(measuring network Fig. 4, TN
system)
< 0.75 mA
Motor protection
Thermal overload protector (TOP) wired internally
Cable exit
Variable
Protection class
I (if protective earth is connected by customer)
Approval
CCC; GOST
Item no. 11002-5-9980 · Revision 79566 · Release 2013-06-06 · Page 2 / 5
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
AC centrifugal fan
R2E250-AS47-05
backward curved, single inlet
Product drawing
1
Connection line PVC 4Gx0.5mm². 4x brass lead tips crimped
2
Accessory part: Inlet nozzle 96359-2-4013, not included in the standard scope of delivery
3
Depth of screw max. 5 mm
Connection screen
U1
blue
PE
green/yellow
Z
brown
U2
black
Item no. 11002-5-9980 · Revision 79566 · Release 2013-06-06 · Page 3 / 5
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
AC centrifugal fan
R2E250-AS47-05
backward curved, single inlet
Charts: Air flow 50 Hz
Druck p f s[Pa]für Rho=1,2kg/m^3
100
200
300
qv[cfm]
500
400
600
700
800
900
580
2,3
560
2,2
540
520
2,1
500
2
480
1,8
440
1,7
420
4
400
1,6
380
1,5
360
1,4
340
1,3
320
3
300
1,2
280
1,1
260
Air performance measured as per ISO 5801
Installation category A. For detailed
information on the measuring set-up, please
contact ebm-papst. Suction-side noise
levels: LwA measured as per ISO 13347 /
LpA measured with 1m distance to fan axis.
The values given are valid under the
measuring conditions mentioned above and
may vary according to the actual installation
situation. With any deviation from the
standard set-up, the specific values have to
be checked and reviewed with the unit
installed.
1
240
220
0,9
200
0,8
180
0,7
2
160
0,6
140
120
0,5
100
0,4
80
0,3
60
0,2
40
]
[Pa
pf s
20
0
Measurement: LU-30851
1,9
460
pf s[Pa]
1.000
2,4
p fs_E[IN H2O]
600
0
0,1
1
0
100
200
300
400
500
600
700
800 900
qv[m^3/h]
0
1.000 1.100 1.200 1.300 1.400 1.500 1.600 1.700
Measured values
U
f
n
Pe
I
qv
pfs
V
Hz
min-1
W
A
m3/h
Pa
1
230
50
2600
155
0.70
1365
0
2
230
50
2460
172
0.75
1090
150
3
230
50
2370
189
0.82
730
300
4
230
50
2430
177
0.77
435
400
U = Supply voltage · f = Frequency · n = Speed · Pe = Power input · I = Current draw · qv = Air flow · pfs = Pressure increase
Item no. 11002-5-9980 · Revision 79566 · Release 2013-06-06 · Page 4 / 5
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
AC centrifugal fan
R2E250-AS47-05
backward curved, single inlet
Charts: Air flow 60 Hz
Druck p f s[Pa]für Rho=1,2kg/m^3
0
100
200
300
qv[cfm]
500
400
600
700
800
900
1.000
3,1
750
3
2,9
700
2,8
Measurement: LU-30852
2,7
650
2,6
2,5
600
2,4
2,3
550
2,2
2,1
500
2
1,8
1,7
400
1,6
1,5
350
1,4
1,3
3
300
p fs_E[IN H2O]
450
pf s[Pa]
1,9
4
Air performance measured as per ISO 5801
Installation category A. For detailed
information on the measuring set-up, please
contact ebm-papst. Suction-side noise
levels: LwA measured as per ISO 13347 /
LpA measured with 1m distance to fan axis.
The values given are valid under the
measuring conditions mentioned above and
may vary according to the actual installation
situation. With any deviation from the
standard set-up, the specific values have to
be checked and reviewed with the unit
installed.
1,2
1,1
250
1
0,9
200
0,8
0,7
2
150
0,6
0,5
100
0,4
0,3
50
0,1
a]
s[P
pf
0
0,2
1
0
200
400
600
800
1.000
qv[m^3/h]
1.200
1.400
1.600
0
1.800
Measured values
U
f
n
Pe
I
qv
pfs
V
Hz
min-1
W
A
m3/h
Pa
1
230
60
2795
215
0.95
1490
0
2
230
60
2610
228
0.99
1185
150
3
230
60
2415
240
1.04
765
300
4
230
60
2560
231
1.00
415
450
U = Supply voltage · f = Frequency · n = Speed · Pe = Power input · I = Current draw · qv = Air flow · pfs = Pressure increase
Item no. 11002-5-9980 · Revision 79566 · Release 2013-06-06 · Page 5 / 5