Embedded Power for Business-Critical Continuity
LPS100-M Series
150 Watts
Total Power: Input Voltage: # of Outputs: 80 - 150 Watts 90 - 264 Vac Single
Rev. 4.30.09_29 LPS100-M Series 1 of 3
Special Features
• • • • • • • • • • • • • • Medical and ITE safeties Active power factor correction 2” x 4” footprint Less than 1U high EN61000-3-2 compliant Remote sense Power fail Adjustable main output Built-in Class B EMI filter Overvoltage protection Overload protection Thermal overload protection Isolated12 V Fan output LPX50 Enclosure kit available
Electrical Specifications
Input
Input range: Frequency: Inrush current: Efficiency: EMI/RFI: Safety ground leakage current: 90 - 264 Vac; 120 - 300 Vdc 47-63 Hz 50 A max., cold start @ 25 °C 88% typical at full load FCC Class B conducted; CISPR22 Class B conducted; EN55022 Class B conducted; VDE0878PT3 Class B conducted 2 75 µA @ 50/60 Hz, 264 Vac input
Output
100 W for convection (80 W for LPS102-M); 150 W with 30 CFM forced air (120 W for LPS102-M) Adjustment range: ± 10% minimum on the main outputs Fan output: 12 V @ 1 A isolated, ± 10% Hold-up time: 10 ms @ 150 W load, 120 Vac input Overload protection: Short circuit protection on all outputs. Case overload protected @ 110-160% above rating Overvoltage protection: 15-35% above nominal output Maximum power:
Logical Control
Power failure: Open collector logic signal goes high 100-500 msec after main output; it goes low at least 6 msec before loss of regulation C ompensates for 0.5 V lead drop min. Will operate without remote sense connected. Reverse connection protected.
Safety
• • • • • • TUV 60950, 60601-1 UL 60950, 60601-1 cULus 60950, 60601-1 TUV 60950, 60601-1 CB Certificate & report CE Mark (LVD)
Remote sense:
Embedded Power for Business-Critical Continuity
Environmental Specifications
Operating temperature: 0° to 50 °C ambient derate each output as 2.5% per degree from 50° to 70 °C. -20 °C start up -40 °C to +85 °C Designed to meet EN61000-4; -2, -3, -4, -5, -6, -8, -11 Level 3 Operating; non-condensing 10% to 95% RH IEC68-2-6 to the levels of IEC721-3-2 > 550,000 hours at full load and 25 °C ambient conditions Storage temperature: Electromagnetic susceptibility: Humidity: Vibration: MTBF demonstrated
Rev. 4.30.09_29 LPS100-M Series 2 of 3
Mechanical Drawing
M1
VR1 Output Voltage Adjust Pot M2
1 4 8
SK203 SK2
GND
SK1 1 3
2.00" (50.8)
1
3.73" (94.7) 4.00" (101.6)
0.197” (5.0) Minimum Standoff Height
0.16" (4.0) 1.29" (33.0)
1.72" (43.8) Mounting Hole Ø0.16"[4.0] 4 Places Max. Screw Head Diameter .22” (5.6)
1
4
SK5
Embedded Power for Business-Critical Continuity
Ordering Information
Model Number LPS102-M LPS103-M LPS104-M LPS105-M LPS108-M Output Voltage 5 V 12 V 15 V 24 V 48 V Minimum Load 0 A 0 A 0 A 0 A 0 A Maximum Load with Convection Cooling 16 A 8.3 A 6.7 A 4.2 A 2.1 A Maximum Load with 30CFM Peak Load Regulation2 Forced Air 24 A 12.5 A 10 A 6.3 A 3.1 A 30 A 14 A 11 A 7 A 3.5 A ± 2% ± 2% ± 2% ± 2% ± 2% Ripple P/P (PARD)3 50 mV 120 mV 150 mV 240 mV 480 mV
Americas
5810 Van Allen Way Carlsbad, CA 92008 USA Telephone: +1 760 930 4600 Facsimile: +1 760 930 0698
Rev. 4.30.09_29 LPS100-M Series 3 of 3
Europe (UK)
1. Peak current lasting < 30 seconds with a maximum 10% duty cycle. 2. At 25 °C including initial tolerance, line voltage, load currents and output voltages adjusted to factory settings. 3. Peak-to-peak with 20 mHz bandwidth and 10 µF (tantalum capacitor) in parallel with a 0.1 µF capacitor at rated line voltage and load ranges.
Waterfront Business Park Merry Hill, Dudley West Midlands, DY5 1LX United Kingdom Telephone: +44 (0) 1384 842 211 Facsimile: +44 (0) 1384 843 355
Asia (HK)
Pin Assignments
Connector LPS100-M SK1 Pin 1 Pin 3 SK2 Pin 1 Pin 2 Pin 3 Pin 4 Pin 5 Pin 6 Pin 7 Pin 8 SK203 Pin 1 Pin 2 Pin 3 Pin 4 SK5 Pin 1 Pin 2 Pin 3 Pin 4 Neutral Line Common Common Common Common +Vout +Vout +Vout +Vout Common Power Fail - Remote Sense + Remote Sense +12 V Fan +12 V Fan Fan Return (Isolated) Fan Return (Isolated)
Mating Connectors
AC Input (SK1): Molex P/N: 09-50-8031, Pins: 08-52-0113 or Landwin P/N: 3060S0302, Pins: 3360T011P AC Ground Molex: 01-90020001 DC Output Molex P/N: 09-50-8081, Pins: 08-52-0113 (SK2): or Landwin P/N: 3060S0802, Pins: 3360T011P Remote Sense Molex P/N: 35155-0400, Pins: 08-70-0057 (SK203): or Landwin P/N: 2640S04A0, Pins: 2543T011P Fan: (SK5): Molex P/N: 22-01-1042, Pins: 08-70-0049 or Landwin: P/N: 2510S04A0, Pins: 2543T011P Emerson Network Power Connector Kit #70-841-025, includes all of the above
14/F, Lu Plaza 2 Wing Yip Street Kwun Tong, Kowloon Hong Kong Telephone: +852 2176 3333 Facsimile: +852 2176 3888
For global contact, visit:
www.PowerConversion.com techsupport.embeddedpower @emerson.com
While every precaution has been taken to ensure accuracy and completeness in this literature, Emerson Network Power assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
Emerson Network Power. The global leader in enabling business-critical continuity. AC Power Connectivity DC Power Embedded Computing
Notes: 1. Specifications subject to change without notice. 2. All dimensions in inches (mm), tolerance is ±.02”. 3. mounting holes MH1, MH2 should be grounded for EMI purpose 4. Mounting MH1 is safety ground connection 5. Specifications are for convection rating at factory settings at 115 Vac input 25 °C unless otherwise stated. 6. This power supply requires mounting on metal standoffs 0.20” (5 m) in height. 7. Warranty: 2 year 8. Weight: 0.44 lb. / 0.20 kg
Embedded Power Monitoring Outside Plant Power Switching & Controls Precision Cooling Racks & Integrated Cabinets Services Surge Protection EmersonNetworkPower.com
Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2009 Emerson Electric Co.
很抱歉,暂时无法提供与“LPS103-M”相匹配的价格&库存,您可以联系我们找货
免费人工找货