Embedded Power for Business-Critical Continuity
LPS50-M Series
60 Watts
Total Power: Input Voltage: # of Outputs: 55 - 60 Watts 90 - 264 VAC 127 - 300 VDC Single
Rev. 1.08.09_149 LPS50-M Series 1 of 3
Special Features
• Medical Safety Approvals • Universal input • Less than 1U high • 2” x 4” footprint • Remote sense • Overload and short circuit protection • Adjustable output voltage • High efficiency • High MTBF • Built in EMI filter (CISPR 22 Class B) • LED power good indicator • Input power < 74 watts • Complies with EN61000 -3-2 • UL Class I approved • LPX50 enclosure kit available • Dual AC fuses
Electrical Specifications
Input
Input range: Frequency: Inrush current: Input power: Efficiency: EMI/RFI: Safety ground leakage current: 90 - 264 VAC (wide range) 127-300 Vdc 47-440 Hz < 60 A peak @ 230 VAC, cold start @ 25°C < 74 Watts 80% - 85% typical at full load FCC Class B conducted; CISPR 22 Class B conducted; EN55022 Class B conducted, VDE0878PT3 Class B conducted 275uA @ 50/60 Hz; 264 VAC input
Output
Maximum power: Adjustment range: Hold-up time: Overload protection: 60W for convection (LPS52, 55 W) ±20% minimum 10/ 20 ms 115/230 VAC input line Short circuit protection on all outputs. Case overload protected @ 110-160% of normal rating
Overvoltage protection: 30-50% above nominal output
Safety
• UL: • CSA: • VDE: • CE: UL 60601-1 CSA-C22.2 No. 601.1-M90 EN60601-1 LVD & EMC
Remote sense:
Compensatesd for 0.5 V lead drop max. Will operate without remote sense connected. Reverse connection protected.
Embedded Power for Business-Critical Continuity
Environmental Specifications
Operating temperature:
Rev. 1.08.09_149 LPS50-M Series of 3
0° to 50 °C ambient derate each output as 2.5% per degree from 50° to 70 °C. -20 °C start up
Storage temperature: -40 °C to +85 °C Electromagnetic susceptibility: Designed to meet EN61000-4; -2, -3, -4, -5, -6, -8, -11 Level 3 Humidity: Vibration: MTBF demonstrated: Operating; non-condensing 10% to 95% RH IEC68-2-6 to the levels of IEC721-3-2 > 550,000 hours at full load and 25 °C ambient conditions
Mechanical Drawing
M1
GRN/ YEL
3 C
+
VR1 Output Voltage M2 Adjust pot
C4 TP2
~
~
DB1
R3
A
R3
Q5
24
VR1
L2
J4
C32
C
TP1
C27
GND
2.00" [50.8]
L3
T1
D
4
R1
SK2
C30
T3.15A 2.5A 250VAC
F1
L1 C5 A
C22
1
T3.15A 2.5A 250VAC
SK1
F2
C1
J1
J2
R26
1 3
B T2 E F H
C18 C9
R 22
Q6
I
J3
G J
D2
HTSK_SEC D
6
TH 1
DIP 2005
C17
LED1
3.75" [95.3] 4.00" [101.6]
Mounting Hole Ø0.16"[4.0] 4 Places Max. Screw Head Diameter .22” (5.6)
0.16" [4.0]
0.197” (5.0) Minimum Standoff Height
1.30" [33.0]
1.75" [44.5]
CN1
1
C2
Embedded Power for Business-Critical Continuity
Ordering Information
Model Number LPS52-M LPS53-M LPS54-M LPS55-M LPS58-M Output Voltage 5 V 12 V 15 V 24 V 48 V Minimum Maximum Load with Load Convection Cooling 0 A 0 A 0 A 0 A 0 A 11 A 5 A 4 A 2.5 A 1.25 A Peak Load1 12 A 5.4 A 4.4 A 2.75 A 1.35 A Regulation2 ±2% ±2% ±2% ±2% ±2% Ripple P/P (PARD)3 50 mV 120 mV 150 mV 240 mV 480 mV
Americas
5810 Van Allen Way Carlsbad, CA 92008 USA Telephone: +1 760 930 4600 Facsimile: +1 760 930 0698
Rev. 1.08.09_149 LPS50-M Series 3 of 3
Europe (UK)
1. Peak current lasting < 15 seconds with a maximum 10% duty cycle. 2. At 25 °C including initial tolerance, line voltage, load currents and output voltages adjusted to factory settings. 3. Peak-to-peak with 20 MHz bandwidth and 10 µF (tantalum capacitor) in parallel with a 0.1 µF capacitor at rated line voltage and load ranges.
Waterfront Business Park Merry Hill, Dudley West Midlands, DY5 1LX United Kingdom Telephone: +44 (0) 1384 842 211 Facsimile: +44 (0) 1384 843 355
Asia (HK)
Pin Assignments
Connector SK1-1 SK1-3 SK2-1 SK2-2 SK2-3 SK2-4 SK2-5 SK2-6 LPS52-M Line Neutral +5 V +5 V Common Common -Sense +Sense LPS53-M Line Neutral +12 V +12 V Common Common -Sense +Sense LPS54-M Line Neutral +15 V +15 V Common Common -Sense +Sense LPS55-M Line Neutral +24 V +24 V Common Common -Sense +Sense LPS58-M Line Neutral +48 V +48 V Common Common -Sense +Sense
14/F, Lu Plaza 2 Wing Yip Street Kwun Tong, Kowloon Hong Kong Telephone: +852 2176 3333 Facsimile: +852 2176 3888
For global contact, visit:
www.PowerConversion.com techsupport.embeddedpower @emerson.com
While every precaution has been taken to ensure accuracy and completeness in this literature, Emerson Network Power assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
Emerson Network Power. The global leader in enabling business-critical continuity.
Mating Connectors
AC Input: Molex 09-50-8031 (USA) 09-91-0300 (UK) PINS: 08-52-0113 DC Outputs: Molex 09-50-8061 (USA) 09-91-0600 (UK) PINS: 08-52-0113 Emerson Network Power Connector Kit #70-841-006, includes all of the above Notes: 1. Specifications subject to change without notice. 2 . All dimensions in inches (mm), tolerance is ±0.02” (±0.5mm) 3. Mounting holes M1 and M2 should be grounded for EMI purposes. 4. Mounting hole M1 is safety ground connection. 5. Specifications are for convection rating at factory settings at 115 VAC input, 25 °C unless otherwise stated. 6. Warranty: 2 year 7. Weight: 0.41lbs/0.18kg
AC Power Connectivity DC Power Embedded Computing Embedded Power Monitoring Outside Plant Power Switching & Controls Precision Cooling Racks & Integrated Cabinets Services Surge Protection EmersonNetworkPower.com
Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2008 Emerson Electric Co.