Embedded Power for Business-Critical Continuity
LPT100-M Series
130 Watts
Total Power: Input Voltage: # of Outputs: 80 - 130 Watts 90 - 264 Vac Triple
Rev. 10.9.09_141 LPT100-M Series 1 of 3
Special Features
• • • • • • • • • • • • • Medical and ITE safeties Active power factor correction 2” x 4” footprint Less than 1U high EN61000-3-2 compliant Remote sense Power fail Adjustable main output Built-in Class B EMI filter Overvoltage protection Overload protection Thermal overload protection LPX50 enclosure kit available
Electrical Specifications
Input
Input range: Frequency: Inrush current: Efficiency: EMI/RFI: Safety ground leakage current: 90 - 264 Vac; 127 - 300 Vdc 47 - 63 Hz 50 A max., cold start @ 25 °C 82% typical at full load FCC Class B conducted; CISPR22 Class B conducted; EN55022 Class B conducted; VDE0878PT3 Class B conducted 2 75 µA @ 50/60 Hz, 264 Vac input
Output
Maximum power: 80 W for convection; 130 W with 200 LFM forced air Adjustment range: All outputs adjustable - 40%, +10%, except for +24V output on LPT104-M which will be -10%, +20% and 3.3 V output on the LPT101-M +10%, -15% Hold-up time: 10 ms @ 130 W load, 120 Vac input Overload protection: Short circuit protection on all outputs. Case overload protected @ 110 - 160% above rating for V1 & V2, 110-190% for V3 Overvoltage protection: 15 - 35% above nominal output
Logical Control
Power failure: Active LowTTL logic signal goes high 100 - 500 msec after main output; it goes low at least 6 msec before loss of regulation C ompensates for 0.5 V lead drop min. Will operate without remote sense connected. Reverse connection protected.
Safety
• • • • • • • TUV 60950, 60601-1 UL 60950, 60601-1 CSA 60950, 60601-1 NEMKO 60950, 60601-1 AUSTEL 60950, 60601-1 CB Certificate & report CE Mark (LVD)
Remote sense:
Embedded Power for Business-Critical Continuity
Environmental Specifications
Operating temperature: Storage temperature: Electromagnetic susceptibility: Humidity: Vibration: MTBF calculated: 0° to 50 °C ambient derate each output as 2.5% per degree from 50° to 70 °C. -20 °C start up -40 °C to +85 °C designed to meet EN61000-4; -2, -3, -4, -5, -6, -8, -11 Level 3 Operating; non-condensing 10% to 90% RH, non-operating, non-condensing 10% - 95% IEC68-2-6 to the levels of IEC721-3-2 583,000 hours at full load and 25 °C ambient conditions. 230 Vac input, Bellcore
Rev. 10.9.09_141 LPT100-M Series of 3
Mechanical Drawing
GND Output Voltage Adjust Pots
SK3
2.00” (50.8)
PIN 1 (LIVE) PIN 3 (NEUTRAL)
SK1
3.73” (94.6) 4.00” (101.6)
SK2 Mounting Hole ø0.16” [4.0] 4 Places Max. Screw Head Diameter .22” (5.6)
Output Voltage Adjust Pots
0.10” (2.5)
0.197” (5.0) Minimum Standoff height
1.28” (32.7)
1.72” (43.8)
Embedded Power for Business-Critical Continuity
Ordering Information
Model Number Maximum Load Maximum Load Output Minimum with Convection with 30CFM Voltage Load Cooling Forced Air +3.3 V LPT101-M +5 V +12 V +5 V LPT102-M +12 V -12 V +5 V LPT103-M +15 V -15 V +5 V LPT104-M +24 V +12 V 0 A 0 A 0 A 0 A 0 A 0 A 0 A 0 A 0 A 0 A 0 A 0 A 13 A 5 A 1 A 13 A 5 A 1 A 13 A 4 A 1 A 13 A 1.5 A 1 A 18 A 9 A 2.3 A 18 A 9 A 2 A 18 A 7.2 A 1.5 A 18 A 3 A 2.3 A Peak Load 20 A 10 A 2.3 A 20 A 10 A 2 A 20 A 8 A 2 A 2 A 3.5 A 2.3 A Regulation2 ±2% ±5% ±5% ±2% ±5% ±5% ±2% ±5% ±5% ±2% ±7% ±5% Ripple P/P (PARD)3 50 mV 50 mV 120 mV 50 mV 120 mV 120 mV 50 mV 150 mV 150 mV 50 mV 240 mV 120 mV
Americas
5810 Van Allen Way Carlsbad, CA 92008 USA Telephone: +1 760 930 4600 Facsimile: +1 760 930 0698
Rev. 10.9.09_141 LPT100-M Series 3 of 3
Europe (UK)
Waterfront Business Park Merry Hill, Dudley West Midlands, DY5 1LX United Kingdom Telephone: +44 (0) 1384 842 211 Facsimile: +44 (0) 1384 843 355
Asia (HK)
1. Peak current lasting < 15 seconds with a maximum 10% duty cycle. 2. At 25 °C including initial tolerance, line voltage, load currents and output voltages adjusted to factory settings. 3. Peak-to-peak with 20 mHz bandwidth and 10 µF (tantalum capacitor) in parallel with a 0.1 µF capacitor at rated line voltage and load ranges.
14/F, Lu Plaza 2 Wing Yip Street Kwun Tong, Kowloon Hong Kong Telephone: +852 2176 3333 Facsimile: +852 2176 3888
For global contact, visit:
www.PowerConversion.com techsupport.embeddedpower @emerson.com
While every precaution has been taken to ensure accuracy and completeness in this literature, Emerson Network Power assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
Pin Assignments
Connector SK1 PIN 1 PIN 3 SK2 PIN 1 PIN 2 PIN 3 PIN 4 PIN 5 PIN 6 PIN 7 PIN 8 SK3 PIN 1 PIN 2 PIN 3 PIN 4 LPT100-M Neutral Line V1out V1out GND GND GND GND V2out V3out Power Fail GND + Remote Sense - Remote Sense
Mating Connectors
AC Input (SK1): Molex P/N 09-50-8031 PINS: 08-52-0113 AC Ground: Molex P/N 01-9002001 DC Output (SK2): JST P/N VHR-8N PINS: SVH-21T-P1.1 Remote Sense (SK3): Molex P/N 87639-0400 PINS: 50212-8100 Emerson Network Power Connector Kit #70-841-026, includes all of the above
Emerson Network Power. The global leader in enabling business-critical continuity. AC Power Connectivity DC Power Embedded Computing Embedded Power Monitoring Outside Plant Power Switching & Controls Precision Cooling Racks & Integrated Cabinets Services Surge Protection EmersonNetworkPower.com
Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2009 Emerson Electric Co.
Notes: 1. Specifications subject to change without notice. 2. All dimensions in inches (mm), tolerance is ±.02”. 3. mounting holes MH1, MH2, MH3 should be grounded for EMI purpose 4. Mounting MH1 is safety ground connection 5. Specifications are for convection rating at factory settings at 115 Vac input 25 °C unless otherwise stated. 6. This power supply requires mounting on metal standoffs 0.20” (5 m) in height. 7. Warranty: 2 year 8. Weight: 0.44 lb. / 0.20 kg