Embedded Power for Business-Critical Continuity
TLP150 Medical Series
Single output
Total Power: 150 W Input Voltage: 85 - 264 VAC # of Outputs: Single
Rev.7.8.09_140 TLP150 Medical Series 1 of 4
RoHS
Special Features
• • • • • • • • • • 150 W on main channel with only 200 LFM Low profile fits 1U applications Active PFC and EN61000-3-2 compliant Integrated control and monitoring features Overcurrent, overvoltage and overtemperature protection Compliance to EN55022-B conducted noise standard 12 V fan output 5 V standby output (optional) RoHS compliant 2 year warranty
Electrical Specifications
Input
Input voltage range: Input frequency range: Input surge current: Safety ground leakage current: Input current: Input fuse: 264 Vac (cold start) 264 Vac, 50 Hz 120 Vac @ 150 W 230 Vac @ 150 W UL/IEC127 Universal Input 85 - 264 Vac 47-63 Hz 40 A max. 150 µA 1.8 A rms 0.8 A rms T 3.15 A, 250 Vac ± 10% ± 3% ± 5% ± 10% 2.0 s max. 5% max. dev., 1 ms max. recovery to 1% ± 0.02%/°C Main outputs Current limited Singles See Note 9 25%, ± 5% Continuous 0 A 12 V @ 0.5 A
Output
Adjustment Range: Total regulation (line and load): Main output Auxiliary outputs Fan output Turn-on delay: @120 Vac Input Transient response: Main output 25% to 75% step at 0.5 A/µs
Safety
• VDE EN60601-1/IEC60601-1 • UL2601-1/CSA22.2 • No. 601-1
Temperature coefficient: Overvoltage protection: Short circuit protection: Minimum output current: Fan voltage output:
Embedded Power for Business-Critical Continuity
EMC Characteristics (5)
Conducted emissions: Harmonic current correction: ESD air: ESD contact: Radiated immunity: Fast transients: Surge: Conducted immunity: EN55022, FCC part 15 EN61000-3-2 EN61000-4-2 EN61000-4-2 EN61000-4-3 EN61000-4-4 EN61000-4-5 EN61000-4-6 850 Vac @ 60 Hz 115 Vac @ 150 W 230 Vac @ 150 W Input/output Input/chassis 260g (9.2 oz) Telcordia SR-332 MIL-HDBK-217F 900,000 hours min. 350,000 hours min. Level B Compliant Level 3 Level 3 Level 3 Level 4 Level 4 Level 3 20 ms @ 150 W 81% typ. 84% typ. 4000 Vac 1500 Vac
Rev.7.8.09_140 TLP150 Medical Series of 4
General Specifications
Hold-up time: Efficiency: Isolation voltage: Weight: MTBF (@ 25 ºC):
Environmental Specifications
Thermal performance: Operating ambient, (See derating curve) Non-operating 0 °C to 50 °C ambient, 200 LFM forced air 0 °C to 50 °C ambient, convection cooled 50 °C to 70 °C ambient, convection cooled Non-condensing Operating Non-operating Vibration (See Note 7): Shock: 5 - 500 Hz per MIL-STD-810E 0° C to +70 °C -40 °C to +85 °C 150 W 100 W Derate linearly to 50% load 5 - 95% RH 10,000 feet max. 30,000 feet max. 2.4 G rms peak 516.4 Part IV
Relative humidity: Altitude:
Embedded Power for Business-Critical Continuity
Ordering Information
Output Voltage 12 V 24 V Output Current Min 0 A 0 A Max (free air)(1,4) 8.4 A 4.2A Max (forced air)(2,4) 12.5A 6.3 A Ripple 120 mV 240 mV Total Regulation ± 3.0% ± 3.0% Model Numbers TLP150N-99S12J TLP150N-99S24J
Rev.7.8.09_140 TLP150 Medical Series of 4
Notes
1 Free air convection. Maximum continuous output power not to exceed 100 W. Refer to Figure 1 for the derating curve. 2 200 LFM forced air cooling from the ac input side. Maximum continuous output power not to exceed 150 W. 3 Figure is peak-to-peak for room temperature rating. Output noise measurements are made across a 20 MHz bandwidth using a 6 inch twisted pair, terminated with a 10 µF tantalum capacitor and a 0.1 µF ceramic capacitor. 4 CAUTION: Allow a minimum of 1 second after disconnecting line power when making thermal measurements. For optimum reliability no part of the heatsink should exceed 115 °C and no semi-conductor case temperature should exceed 120 °C. 5 No external filtering required during conducted emissions testing but some applications may require additional filtering to achieve system compliance. Compliance with radiated EMI specifications may require mounting in a suitable enclosure. 6 This product is only for inclusion by professional installers within other equipment and must not be operated as a stand alone product. 7 Three orthogonal axes, random vibration 10 minutes for each axes, 2.4 G. 8 Replace the ‘J’ at the end of the model number with ‘FJ’ when the optional standby output and/or remote ON/OFF control is required e.g. TLP150N-99S12FJ. 9 12 V (fan) present when main output is present. An optional 5 Vsb (standby) output is available whenever ac input is present, regardless of remote ON/OFF signal status. 10 The ‘J’ suffix indicates that these parts are Pb-free (RoHS 6/6) compliant. TSE RoHS 5/6 (non Pb-free) compliant versions may be available on special request, please contact your local sales representative for details. 11 NOTICE: Some models do not support all options. Please contact your local Emerson representative or use the on-line model number search tool at http://www.PowerConversion.com to find a suitable alternative..
DERATING CURVE Output Power (Watts) 150 W 200 LFM (1.0 m/s) FORCED AIR COOLING 100 W 75 W NATURAL CONVECTION COOLING
50 W
0W 0C 10 C 20 C 30 C 40 C 50 C 60 C 70 C
Figure 1: Derating Curve
Outline Dimensions
5.000 (127.00) 4.550 (115.57)
J3
3.000 (76.20)
2.550 (64.77)
J1 1
Neutral Live J2
FAN
1 J4 1
0.225 (5.72)
1
R88 Ground/Earth 0.225 (5.72)
Trimmer Adjust Output Voltage
1
J301
Total Height 1.250 (31.75)
ø0.156 (4 Places)
Dimensions in Inches (mm)
Figure 2: Mechanical Drawing
Embedded Power for Business-Critical Continuity
Connector and Mating Connector Types
Connector J1 J3 Type Molex 09-65-2038 (5273 series) void pin 2 or equivalent Molex 09-65-2068 (5273 series) or equivalent Leoco 2421P04H000 (2421 series) or equivalent Mating Connector Type Molex 09-52-4034 (5239 series) or equivalent with Molex 08-52-0072 (2478 series) or equivalent crimp terminals Molex 09-52-4064 (5239 series) or equivalent with Molex 08-52-0072 (2478 series) or equivalent crimp terminals Leoco 2420S04000 (2420 series) or equivalent with Leoco 2453TPH00V1 (2453T series) or equivalent crimp terminals or JST EHR-4 (EH series) or equivalent with JST SEH-001T-P0.6 (EH series) or equivalent crimp terminals Molex 22-01-3027 (2695 series) or equivalent with Molex 08-50-0113 (2759 series) or equivalent crimp terminals
Americas
Rev.7.8.09_140 TLP150 Medical Series 4 of 4
5810 Van Allen Way Carlsbad, CA 92008 USA Telephone: +1 760 930 4600 Facsimile: +1 760 930 0698
J301 (Optional)
Europe (UK)
Fan
Molex 22-23-2021(6373 series) or equivalent
Waterfront Business Park Merry Hill, Dudley West Midlands, DY5 1LX United Kingdom Telephone: +44 (0) 1384 842 211 Facsimile: +44 (0) 1384 843 355
Asia (HK)
J1 Pin Connections
Pin 1 Pin 3 Neutral Live
J3 Pin Connections
Pin 1 Pin 2 Pin 3 Pin 4 Pin 5 Pin 6 RTN RTN RTN Vo Vo Vo Main Return Main Return Main Return +Main Output +Main Output +Main Output
14/F, Lu Plaza 2 Wing Yip Street Kwun Tong, Kowloon Hong Kong Telephone: +852 2176 3333 Facsimile: +852 2176 3888
For global contact, visit:
J2 Tab Connections
Tan Ground/Earth
www.PowerConversion.com techsupport.embeddedpower@ emerson.com
While every precaution has been taken to ensure accuracy and completeness in this literature, Emerson Network Power assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
J4 Pin Connections
Pin 1 Pin 2 Pin 3 Pin 4 Pin 5 Pin 6 -S DC OK PW OK LS +S SGND -Vo Remote Sense DC Power Good Signal Power Good Load Share Signal +Vo Remote Sense Signal Common
Emerson Network Power. The global leader in enabling business-critical continuity. AC Power Connectivity DC Power Embedded Computing Embedded Power
J301 Pin Connections (Optional)
Pin 1 Pin 2 Pin 3 Pin 4 5 Vsb SGND Reserved PS OFF Standby Voltage Signal Common Do Not Connect Remote ON/OFF Signal
Monitoring Outside Plant Power Switching & Controls Precision Cooling Racks & Integrated Cabinets Services Surge Protection EmersonNetworkPower.com
Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2009 Emerson Electric Co.
Fan Pin Connections
Pin 1 Pin 2 +12 V +SGND Fan Voltage Return