Surge Arrester 2-Electrode-Arrester
A61-A350XF Ordering code: B88069X4470C102
DC spark-over voltage 1) 2) Impulse spark-over voltage at 100 V/µs - for 99 % of measured values - typical values of distribution at 1 kV/µs - for 99 % of measured values - typical values of distribution
350 ± 20 < 750 < 680 < 900 < 750 10 20 10 40 100 > 10 < 1.5 < 20 < 0.5 ~ 60 ~ 1.5 -40 ... +90 40/ 90/ 21 350 YY O
350 YY O - Nominal voltage - Year of production - Non radioactive
V % V V V V kA kA A A A GΩ pF V A V g °C
Nominal impulse discharge current (wave 8/20 µs) Single impulse discharge current (wave 8/20 µs) 3) Nominal alternating discharge current (50 Hz, 1 s) Alternating discharge current (50 Hz, 9 cycles) Service life 300 operations Insulation resistance at 100 Vdc Capacitance at 1 MHz Arc voltage at 1 A Glow to arc transition current Glow voltage Weight Storage temperature Climatic category (IEC 60068-1) Marking, red 10/1000 µs
1) 2)
At delivery AQL 0.65 level II, DIN ISO 2859 In ionized mode 3) After load: Insulation resistance >108 Ω, Impulse spark-over voltage < 1000 V Terms in accordance with ITU-T Rec. K.12 and DIN 57845/VDE0845
AB E / AB PM Page 1 of 2
Issue 02, 06.03.2003
Surge Arrester 2-Electrode-Arrester
A61-A350XF Ordering code: B88069X4470C102
Not to scale Dimensions in mm Non controlled document
EPCOS AG 2002. Reproduction, publication and dissemination of this data sheet, enclosures hereto and the information contained therein without EPCOS' prior express consent is prohibited. Purchase orders are subject to the General Conditions for the Supply of Products and Services of the Electrical and Electronics Industry recommended by the ZVEI (German Electrical and Electronic Manufacturers' Association), unless otherwise agreed. AB E / AB PM Page 2 of 2 Issue 02, 06.03.2003
很抱歉,暂时无法提供与“A61-A350XF”相匹配的价格&库存,您可以联系我们找货
免费人工找货