PhaseCap™ B25667-A5966-A175
MKK525-I-8,3-01 4RB5 083-5 AA 52
Characteristics CN UN fN QN IN tan δ 0 1x 96 AC 525 50 8,33 1x 16 µF ±5 % V Hz kvar A
Marking
60 Hz 10 kvar 19 A
0,2 W/kvar (dielectric)
Maximum ratings Umax
The information in our data book / sheet describes the type of component and shall not be considered as assured characteristics.
I r(40) Is (du/dt) max (du/dt) s
AC 580 AC 680 1x 35 4800 20 50
V, 8 h daily V, 1 min A (ΘA = 40°C, U N ) A V/µs V/µs
Toothed washer DIN 6797-J13 Hex nut DIN 439-BM12
Test data UTT UTC AC 1150 V, 10 s AC 3000 V, 10 s
Rivet (Impregnating hole)
tan δ (50 Hz) ≤ 0,5 W/kvar (total)
C61014-A0505-A401 Dimensions in mm
Climatic category -40/D Θ min Θ max Humidity Θ stg –40 °C +55 °C Max. relative Humidity ≤ 95 % –55 bis +70 °C
Design data Dimensions Ø x l Approx. weight Impregnation Fixing Mounting hole Max. torque Terminals Max. torque Terminal cross section Creepage distance Clearance 121,6 x 164 mm (4,79 x 6,46 in) 1,2 kg (2,6 lb) Gas Threaded bolt M12 14 mm (0,55 in) 10 Nm Isolated terminal, IP20 1,2 Nm 16 mm² (5 AWG) 12,7 mm (0,50 in) 9,6 mm (0,38 in)
Life expectancy t LD 100 000 h
Overpressure disconnector Any mounting position possible
Remarks Natural cooling
IEC 60831-1/2, EN 60831-1/2, VDE 560-46/47
KO L E / Pe 01.12.1999