3-Line Filters for Converters and Power Electronics
Power line filters for three-phase systems Rated voltage 480/275 and 520/300 V~, 50/60 Hz Rated current 8 to 200 A Construction
s Three-line filter s Metal case s Book size
B84143-B*-R110 B84143-B*-R112
Features
s s s s s s s
Very high insertion loss Low leakage current Optimized footprint saves space Litz wires on the load side reduce mounting time Low weight Degree of protection: IP 201) Design based on EN 133 200, UL 1283, CSA 22.2 No.8 1986 s Optimized for long motor cables and operation under full load s UL and CSA approval pending Applications
s Frequency converters for motor drives, e.g.
– elevators – pumps – traction systems – conveyor systems – HVAC systems (heating, ventilation and air conditioning) s Wind farms s Power supplies Terminals
s Line: Safe-to-touch terminal blocks s Load: Litz wires
Marking Marking on component: Manufacturer’s logo, ordering code, rated voltage, rated current, rated temperature, date code Minimum marking on packaging: Manufacturer’s logo, ordering code
1) In accordance with IEC 60529:1989; EN 60529:1991; DIN VDE 0470-1
246 03/01
3-Line Filters for Converters and Power Electronics
Typical circuit diagrams B84143-B8 … B16-R110
LINE L1 L2 L3 LOAD L1’ L2’ L3’
B84143-B*-R110 B84143-B*-R112
SSB1526-A
B84143-B25 … B200-R11*
LINE L1 L2 L3 LOAD L1’ L2’ L3’
SSB1527-I
247 03/01
3-Line Filters for Converters and Power Electronics
Technical data Rated voltage V R Rated current I R Test voltage V P Overload capability Leakage current I leak Climatic category 480/275 V~, 50/60 Hz (type -R110) 520/300 V~, 50/60 Hz (type -R112)
B84143-B*-R110 B84143-B*-R112
Referred to 40 °C ambient temperature 1770 V–, 2 s (line/line) 2700 V–, 2 s (lines/case) 1,5 · IR for 3 min per hour or 2,5 · IR for 30 s per hour at 480 V~, 50 Hz 25/100/21 (– 25 °C/+ 100 °C/21 days damp heat test) in accordance with EN 60068-1
Characteristics and ordering codes IR Terminal cross section load side: line side: terminal blocks litz wires mm2 mm2 8 16 25 36 50 66 90 120 150 200 4 4 6 6 16 25 25 50 50 95 1,5 2,5 4 6 10 16 25 35 35 70 I leak typ1) mA R typ mΩ 26 13 10 6,5 4,3 2,7 2,0 1,4 0,9 0,5 Approx. weight kg 1,5 1,5 2,7 3,2 3,7 4,3 7,7 8,3 9,7 13,5 B84143-B8-R110 B84143-B16-R110 B84143-B25-R11* B84143-B36-R11* B84143-B50-R11* B84143-B66-R11* B84143-B90-R11* B84143-B120-R11* B84143-B150-R11* B84143-B200-R11* Ordering code
A
< 14 < 14 < 14 < 14 < 14 < 14 < 14 < 14 < 14 < 14
Compilation of ordering code Replace the asterisk * by the code number for the required version: 0 = 480 / 275 V 2 = 520 / 300 V
1) At rated operation
248 03/01
3-Line Filters for Converters and Power Electronics
Dimensional drawings B84143-B8-R110, B84143-B16-R110
50 200 300±10
Litz wire Litze
B84143-B*-R110 B84143-B*-R112
Terminal Anschlussblocks 4 mm klemmen4 mm2
31 15
L3’ L2’ L1’ PE
Wire end ferrule Aderendhülse Litz wire markings Litzenbezeichnung
80
40
0,5
PE M6 x 25
230 215±0,5
6,5
L1 L2 L3
1
Marking LINE LOAD
25±0,3 46
SSB1291-1
B84143-B25-R11*, B84143-B36-R11*
60 250 400±10
Terminal Anschlussblocks 6 6 mm 2 klemmen mm2
Litz wire Litze
L3’ L2’ L1’
150
75
60 30
0,5
PE
1
Wire end ferrule Aderendhülse Litz wire markings Litzenbezeichnung
PE M6 x 25
280 265±0,5
L1 L2 L3
6,5
Marking LINE LOAD
35±0,3
56
SSB1292-9
249 03/01
3-Line Filters for Converters and Power Electronics
B84143-B50-R11*
60
Terminal Anschlussblocks 16 mm 2 klemmen16 mm2
B84143-B*-R110 B84143-B*-R112
300
500±10 Litze Litz wire L3’ L2’
150
75
L1’
52
30
0,5
1
PE
Wire end ferrule Aderendhülse Litz wire markings Litzenbezeichnung
PE M6 x 25 330 315±0,5 L1 L2 L3
Marking LINE LOAD
35±0,3 56
6,5
SSB1293-H
B84143-B66-R11*
80
Terminal Anschlussblocks 25 mm22 klemmen 25 mm
300
500±10 Litze Litz wire L3’
150
L2’
75
L1’
52 35
0,5
PE
PE M10 x 35
L3
76
L2
Marking LINE LOAD
55±0,3
L1
6,5
330 315±0,5
1
Wire end ferrule Aderendhülse Litzenbezeichnung Litz wire markings
SSB1562-6
250 03/01
3-Line Filters for Converters and Power Electronics
B84143-B90-R11*
80 300
B84143-B*-R110 B84143-B*-R112
500±10
Terminal Anschlussblocks 25 mm22 klemmen 25 mm
Litz wire Litze
L3’
200
L2’ L1’
100
PE
30 0,5 1
Wire end ferrule Aderendhülse Litz wire markings Litzenbezeichnung
52
PE M10 x 35 330 315±0,5 L1 L2 L3 Marking LINE LOAD
6,5 55±0,3 76
SSB1546-P
B84143-B120-R11*, B84143-B150-R11*
90 AnschlussTerminal blocks klemmen 50 mm 22 50 mm
200
350
500±10
Litz wire Litze
L3’ L2’
100
78
L1’ PE
0,5 1
PE M10 x 35
40
380 365±0,5
6,5
Aderendhülse Wire end ferrule Litz wire markings Litzenbezeichnung
L2 L3
Marking LINE LOAD
65±0,3
L1
86
SSB1561-X
251 03/01
3-Line Filters for Converters and Power Electronics
B84143-B200-R11*
Terminal blocks 95 Anschlussklemmen 95 mm 2 mm2 LitzLitze wire
B84143-B*-R110 B84143-B*-R112
Wire end ferrule Aderendhülse
110
400
500±10
L1’
220
L2’
110
L3’
79
30
0,5
PE M10 x 35
1
PE
430 415±0,5
Litz wire markings Litzenbezeichnung
L1 L2 L3
6,5
Marking LINE LOAD
85±0,3
106
SSB1563-E
252 03/01
3-Line Filters for Converters and Power Electronics
Insertion loss (typical values at Z = 50 Ω) unsymmetrical, adjacent branches terminated common mode, all branches in parallel (asymmetrical) differential mode (symmetrical) B84143-B8-R110, B84143-B16-R110
120 dB
SSB1528-R
B84143-B*-R110 B84143-B*-R112
B84143-B25-R11*, B84143-B36-R11*
120 dB
SSB1529-Z
αe
100 90 80 70 60 50 40 30 20 10 04 10 10 5 10 6 10 7 f Hz 10 8
αe
100 90 80 70 60 50 40 30 20 10 04 10 10 5 10 6 10 7 f Hz 10 8
B84143-B50-R11*
120 dB
SSB1530-3
B84143-B66-R11*
120 dB
SSB1531-B
αe
100 90 80 70 60 50 40 30 20 10 04 10 10 5 10 6 10 7 f Hz 10 8
αe
100 90 80 70 60 50 40 30 20 10 04 10 10 5 10 6 10 7 f Hz 10 8
253 03/01
3-Line Filters for Converters and Power Electronics
Insertion loss (typical values at Z = 50 Ω) unsymmetrical, adjacent branches terminated common mode, all branches in parallel (asymmetrical) differential mode (symmetrical) B84143-B90-R11*, B84143-B120-R11*
120 dB
SSB1532-J
B84143-B*-R110 B84143-B*-R112
B84143-B150-R11*, B84143-B200-R11*
120 dB
SSB1533-S
αe
100 90 80 70 60 50 40 30 20 10 04 10 10 5 10 6 10 7 f Hz 10 8
αe
100 90 80 70 60 50 40 30 20 10 04 10 10 5 10 6 10 7 f Hz 10 8
254 03/01
Herausgegeben von EPCOS AG Marketing Kommunikation, Postfach 80 17 09, 81617 München, DEUTSCHLAND EPCOS AG 2000. Alle Rechte vorbehalten. Vervielfältigung, Veröffentlichung, Verbreitung und Verwertung dieser Broschüre und ihres Inhalts ohne ausdrückliche Genehmigung der EPCOS AG nicht gestattet. Mit den Angaben in dieser Broschüre werden die Bauelemente spezifiziert, keine Eigenschaften zugesichert. Bestellungen unterliegen den vom ZVEI empfohlenen Allgemeinen Lieferbedingungen für Erzeugnisse und Leistungen der Elektroindustrie, soweit nichts anderes vereinbart wird. Diese Broschüre ersetzt die vorige Ausgabe. Fragen über Technik, Preise und Liefermöglichkeiten richten Sie bitte an den Ihnen nächstgelegenen Vertrieb der EPCOS AG oder an unsere Vertriebsgesellschaften im Ausland. Bauelemente können aufgrund technischer Erfordernisse Gefahrstoffe enthalten. Auskünfte darüber bitten wir unter Angabe des betreffenden Typs ebenfalls über die zuständige Vertriebsgesellschaft einzuholen.
Published by EPCOS AG Marketing Communications, P.O. Box 80 17 09, 81617 Munich, GERMANY EPCOS AG 2000. All Rights Reserved. Reproduction, publication and dissemination of this brochure and the information contained therein without EPCOS’ prior express consent is prohibited. The information contained in this brochure describes the type of component and shall not be considered as guaranteed characteristics. Purchase orders are subject to the General Conditions for the Supply of Products and Services of the Electrical and Electronics Industry recommended by the ZVEI (German Electrical and Electronic Manufacturers’ Association), unless otherwise agreed. This brochure replaces the previous edition. For questions on technology, prices and delivery please contact the Sales Offices of EPCOS AG or the international Representatives. Due to technical requirements components may contain dangerous substances. For information on the type in question please also contact one of our Sales Offices.
1