EMC filters
3-line filters
for converters and power electronics
Rated current 150 to 2500 A
Series/Type: Date: B84143B*S020 … S024 January 2006
EPCOS AG 2006. Reproduction, publication and dissemination of this data sheet and the information contained therein without EPCOS’ prior express consent is prohibited.
3-line filters for converters and power electronics
Power line filters for 3-phase systems Rated voltages 530/310, 690/400, 760/440 V AC Rated current 150 to 2500 A Alternative version
■ Series B84143B*S080 and B84143B*S081
B84143B*S020 … S024
offers a low-cost solution. Construction
■ 3-line filter ■ Metal case
Features
■ ■ ■ ■ ■ ■
Optimized leakage current
Easy to install
Very compact design
Optimized for operation under full load
Low weight
UL, cUL approval
Applications
■ ■ ■ ■
B84143B*S024 for IT mains supply
Frequency converters for motor drives
Wind farms
Power supplies
Terminals
■ Busbars
Marking Marking on component: Manufacturer’s logo, ordering code, rated voltage, rated current, rated temperature, climatic category, date code Minimum marking on packaging: Manufacturer’s logo, ordering code
Please read Cautions and warnings and
Important notes at the end of this document.
2
01/06
3-line filters for converters and power electronics
Typical circuit diagram
LINE L1
L2 L3
B84143B*S020 … S024
LOAD
L1’ L2’ L3’
SSB2130-I
Technical data and measuring conditions Rated voltage VR Type S020: 530/310 V AC, 50/60 Hz Type S021: 760/440 V AC, 50/60 Hz Type S024: 690/400 V AC, 50/60 Hz (Filters for IT mains supply. See also Chapter “General”, Section 7.4) Referred to 40 °C ambient temperature Type S020: 2280 V DC, 2 s (line/line) 2690 V DC, 2 s (lines/case) Type S024: 2980 V DC, 2 s (line/line) 2890 V DC, 2 s (lines/case) Type S021: 3270 V DC, 2 s (line/line) 2890 V DC, 2 s (lines/case) Overload capability (thermal) Leakage current Ileak Climatic category (IEC 60068-1) Approvals 1.5 · IR for 3 min per hour or 2.5 · IR for 30 s per hour At VR, 50 Hz 25/100/21 (– 25 °C/+100 °C/21 days damp heat test) UL 1283; CSA C22.2 No.8 (Type S020: 500/290 V; Type S021 and S024: 600/350 V)
Rated current IR Test voltage Vtest
Please read Cautions and warnings and
Important notes at the end of this document.
3
01/06
3-line filters for converters and power electronics
Characteristics and ordering codes
VR AC V
B84143B*S020 … S024
IR A
Ileak mA < 20 < 20 < 20 < 20 < 20 < 20 < 20 < 20 < 20 < 28 < 28 < 28 < 28 < 28 < 28 < 28 < 28 < 28 < 905 < 905 < 905 < 905 < 905 < 905 < 905 < 905 < 905
Rtyp µΩ 140 140 63 67 67 52 33 22 15 140 140 63 67 67 52 33 22 15 140 140 63 67 67 52 33 22 15
Approx. weight kg 13 13 15 21 21 22 28 34 105 13 13 15 21 21 22 28 34 105 13 13 15 21 21 22 28 34 105
Ordering code
Approvals
Type S020 530/310 150 180 250 320 400 600 1000 1600 2500 Type S021 760/440 150 180 250 320 400 600 1000 1600 2500 690/400 150 180 250 320 400 600 1000 1600 2500 × = approval granted
1) Filters for IT mains supply. (See also Chapter “General”, Section 7.4)
500/290 V B84143B0150S020 B84143B0180S020 B84143B0250S020 B84143B0320S020 B84143B0400S020 B84143B0600S020 B84143B1000S020 B84143B1600S020 B84143B2500S020 B84143B0150S021 B84143B0180S021 B84143B0250S021 B84143B0320S021 B84143B0400S021 B84143B0600S021 B84143B1000S021 B84143B1600S021 B84143B2500S021 B84143B0150S024 B84143B0180S024 B84143B0250S024 B84143B0320S024 B84143B0400S024 B84143B0600S024 B84143B1000S024 B84143B1600S024 B84143B2500S024 × × × × × × × × × × × × × × × × × × × × × × × × × × × × × × × × × × × × × × × × × × × × × × × × × × × × × ×
600/350 V
Type S024 (Filters for IT mains supply1))
600/350 V
Please read Cautions and warnings and
Important notes at the end of this document.
4
01/06
3-line filters for converters and power electronics
Dimensional drawings
B84143B0150S02*, B84143B0180S02* (150 A, 180 A)
2 x M5 x 5
PE M10 x 30
ø9 120±0.3
30
B84143B*S020 ... S024
91
36
10
310±2 260 115±0.2
10
80 140
32±1
32±1
L3’ L2’ L1’
L3 L2 L1
3
Marking LINE LOAD
6.6
155±0.2 170
SSB2142-7
B84143B0250S02* (250 A)
110±0.3 30
2 x M6 x 6
ø11 PE M10 x 30
25 90
2
81
36
15
360±7 300 240±1
15
80 140
60
60
LINE ø12
LOAD
40±1
40±1
165±1 190
Marking
L3’ L2’ L1’
L3 L2 L1
5
SSB2143-F
Please read Cautions and warnings and
Important notes at the end of this document.
5
01/06
1
115
141
20
3-line filters for converters and power electronics
B84143B0320S02*, B84143B0400S02* (320 A, 400 A)
4 x M6 x 6 ø11 PE M10 x 30 30
B84143B*S020 … S024
36
15
360±2 300 240±1
15
120 180±0.5 210
60
60
ø12 42±2 42±2
SSB2144-N
B84143B0600S02* (600 A)
PE M10 x 30
30
L3’
L3
LINE
LOAD
235±1 260
L2’
Marking
5
L2
L1’
L1
4 x M6 x 6
30
85±0.5 116
ø11
91
36
15
410±2.5 350 290±1
15
120 180±0.5 210
60
60
ø12 42±3 42±3
SSB2145-W
Please read Cautions and warnings and
Important notes at the end of this document.
L3’
L3
LINE
LOAD
235±1 260
L2’
Marking
L2
5
L1’
L1
6
01/06
2 16
2 16
85±0.5 116
25
91
3-line filters for converters and power electronics
B84143B1000S02* (1000 A)
PE M12 x 30
4 x M6 x 6 40
B84143B*S020 … S024
ø14
61
20
65
420±2.5 350 290±1 65
20
160 220±0.8 250
8
LINE
LOAD
52±3
ø12
L3’
L3
52±3
275±1 300
L2’
Marking
L2
L1’
L1
SSB2146-5
B84143B1600S02* (1600 A)
400 340±1 141
105 61 4 x M6 x 6
105
L1
10
LINE
LOAD
L3
L3
92±3 20 ø14
ø12 550±3
92±3 20
2.5
16
135±0.8 166
40
40 PE M12 x 30
SSB1210-5
Please read Cautions and warnings and
Important notes at the end of this document.
7
01/06
50
40 220±0.8 250
275±1 300
Marking
L1
160
L2
L2
2.5 16
135±0.8 166
40
141
3-line filters for converters and power electronics
B84143B2500S02* (2500 A)
650 560±1.5
B84143B*S020 … S024
125
125
191.5 91.5 4 x M6 x 6
L1
15
355±1 385
LINE
L3
LOAD
L3
93±3
ø14 810±3.5
93±3
3.5 16.5
20 40
20 40
40
190±1 221.5
ø14
PE M16 x 50
80
SSB1211-D
Please read Cautions and warnings and
Important notes at the end of this document.
8
01/06
60 286±1 320
200
Marking
L2 L2
L1
3-line filters for converters and power electronics
Insertion loss (typical values at Z = 50 Ω)
B84143B*S020 … S024
unsymmetrical, adjacent branches terminated common mode, all branches in parallel (asymmetrical) differential mode (symmetrical) Filters for 150 … 250 A (Type S020) Filters for 320 … 1000 A (Type S020)
100 dB B84143B0150 ... B0250S020 α 80
SSB2131-R
100 dB B84143B0320 ... B1000S020 α
80
SSB2132-Z
60
60
40
40
20
20
04 10
10 5
10 6
10 7
Hz 10 8 f
04 10
10 5
10 6
10 7
Hz 10 8 f
Filters for 1600 and 2500 A (Type S020)
100
dB α 80
SSB1800-Z
B84143B1600S020 B84143B2500S020
60
40
20
0 10 4
10 5
10 6
10 7 f
Hz 10 8
Please read Cautions and warnings and
Important notes at the end of this document.
9
01/06
3-line filters for converters and power electronics
Insertion loss (typical values at Z = 50 Ω)
B84143B*S020 … S024
unsymmetrical, adjacent branches terminated common mode, all branches in parallel (asymmetrical) differential mode (symmetrical) Filters for 150 … 250 A (Type S021) Filters for 320 … 1000 A (Type S021)
100 dB α 80
SSB2133-8
100 dB B84143B0320 ... B1000S021 α 80
SSB2134-G
60
60
40
40
20
20
B84143B0150 ... B0250S021
04 10
10 5
10 6
10 7
Hz 10 8 f
04 10
10 5
10 6
10 7
Hz 10 8 f
Filters for 1600 and 2500 A (Type S021)
100 α dB 80
SSB1204-V
B84143B1600S021 B84143B2500S021
60
40
20
0
10 4
10 5
10 6
10 7
Hz 10 8 f
Please read Cautions and warnings and
Important notes at the end of this document.
10
01/06
3-line filters for converters and power electronics
Insertion loss (typical values at Z = 50 Ω)
B84143B*S020 … S024
unsymmetrical, adjacent branches terminated common mode, all branches in parallel (asymmetrical) differential mode (symmetrical) Filters for 150 … 250 A (Type S024) Filters for 320 … 1000 A (Type S024)
100 dB B84143B0150 ... B0250S024 α 80
SSB2135-P
100 dB α
80
SSB2136-X
60
60
40
40
20
20
04 10
10 5
10 6
10 7
Hz 10 8 f
B84143B0320 ... B1000S024 04 10 5 10 6 10 7 10
Hz 10 8 f
Filters for 1600 and 2500 A (Type S024)
100
dB α 80
SSB1801-8
B84143B1600S024 B84143B2500S024
60
40
20
0 10 4
10 5
10 6
10 7 f
Hz 10 8
Please read Cautions and warnings and
Important notes at the end of this document.
11
01/06
EMC filters Cautions and warnings
Important information Please read all safety and warning notes carefully before installing the EMC filter and putting it into operation (see ). The same applies to the warning signs on the filter. Please ensure that the signs are not removed nor their legibility impaired by external influences. Death, serious bodily injury and substantial material damage to equipment may occur if the appro priate safety measures are not carried out or the warnings in the text are not observed. Using according to the terms The EMC filters may be used only for their intended application within the specified values in low voltage networks in compliance with the instructions given in the data sheets and the data book. The conditions at the place of application must comply with all specifications for the filter used. Warnings
■ It shall be ensured that only qualified persons (electricity specialists) are engaged on work such
■
■
■ ■
as planning, assembly, installation, operation, repair and maintenance. They must be provided with the corresponding documentation. Danger of electric shock. EMC filters contain components that store an electric charge. Danger ous voltages can continue to exist at the filter terminals for longer than five minutes even after the power has been switched off. The protective earth connections shall be the first to be made when the EMC filter is installed and the last to be disconnected. Depending on the magnitude of the leakage currents, the particular specifications for making the protective-earth connection must be observed. Impermissible overloading of the EMC filter, such as impermissible voltages at higher frequen cies that may cause resonances etc. can lead to destruction of the filter housing. EMC filters must be protected in the application against impermissible exceeding of the rated currents by suitable overcurrent protective.
12
01/06
EMC filters Important notes
The following applies to all products named in this publication: 1. Some parts of this publication contain statements about the suitability of our products for certain areas of application. These statements are based on our knowledge of typical requirements that are often placed on our products in the areas of application concerned. We nevertheless expressly point out that such statements cannot be regarded as binding statements about the suitability of our products for a particular customer application. As a rule, EPCOS is either unfamiliar with individual customer applications or less familiar with them than the customers themselves. For these reasons, it is always ultimately incumbent on the customer to check and decide whether an EPCOS product with the properties described in the product specification is suitable for use in a particular customer application. 2. We also point out that in individual cases, a malfunction of passive electronic components or failure before the end of their usual service life cannot be completely ruled out in the current state of the art, even if they are operated as specified. In customer applications requiring a very high level of operational safety and especially in customer applications in which the malfunction or failure of a passive electronic component could endanger human life or health (e.g. in accident prevention or life-saving systems), it must therefore be ensured by means of suitable design of the customer application or other action taken by the customer (e.g. installation of protective circuitry or redundancy) that no injury or damage is sustained by third parties in the event of malfunction or failure of a passive electronic component. 3. The warnings, cautions and product-specific notes must be observed. 4. In order to satisfy certain technical requirements, some of the products described in this publication may contain substances subject to restrictions in certain jurisdictions (e.g. because they are classed as “hazardous”). Useful information on this will be found in our Material Data Sheets on the Internet (www.epcos.com/material). Should you have any more detailed questions, please contact our sales offices. 5. We constantly strive to improve our products. Consequently, the products described in this publication may change from time to time. The same is true of the corresponding product specifications. Please check therefore to what extent product descriptions and specifications contained in this publication are still applicable before or when you place an order. We also reserve the right to discontinue production and delivery of products. Consequently, we cannot guarantee that all products named in this publication will always be available. 6. Unless otherwise agreed in individual contracts, all orders are subject to the current version of the “General Terms of Delivery for Products and Services in the Electrical Industry” published by the German Electrical and Electronics Industry Association (ZVEI). 7. The trade names EPCOS, EPCOS-Jones, Baoke, CeraDiode, CSSP, MLSC, PhaseCap, PhaseMod, SIFI, SIKOREL, SilverCap, SIMID, SIOV, SIP5D, SIP5K, UltraCap, WindCap are trademarks registered or pending in Europe and in other countries. Further information will be found on the Internet at www.epcos.com/trademarks.
13
01/06