EMC filters
3-line filters
for converters and power electronics
Series/Type:
B84243A*000
Date:
August
©TDKElectronicsAG202.Reproduction,publicationanddisseminationofthispublication,enclosureshereto
andtheinformationcontainedthereinwithoutTDKElectronics'priorexpressconsentisprohibited.
3-line filters
B84243A*000
for converters and power electronics
Power line filters for 3-phase systems
Rated voltage VR: 305/530 V AC
Rated current IR: 3 A to 280 A
Construction
3-line filters
Metal case
Features
Typical performance according to
EN 61800-3 + A1(2011): C1 up to 25 m respectively
C2 up to 50 m motor cable length
Discharge time up to 44 A types: < 60 V within 1 s
Short Circuit Current Rating SCCR 100 kA
Degree of protection: IP 201)
ENEC, UL and cUL approval
Typical applications
Frequency converters for motor drives, e.g.
elevators
pumps
conveyor systems
HVAC systems (heating, ventilation and air conditioning)
Power supplies
Textile machines, packaging machines, machine-tools
Up to 44 A: Plug connected devices
Terminals
Finger-safe terminals
Marking
Marking on component:
Manufacturer's logo, ordering code, rated voltage, rated
current, rated temperature, climatic category, date code,
SCCR value
Minimum data on packaging:
Manufacturer's logo, ordering code, quantity, date code
1) According to IEC 60529
Please read Cautions and warnings and
Important notes at the end of this document.
Page 2 of 16
Schematic pictures
3-line filters
B84243A*000
for converters and power electronics
Typical circuit diagram
Technical data and measuring conditions
Rated voltage VR
Rated voltage for IT mains
supply
305/530 V AC (50/60 Hz)
265/460 V AC (50/60 Hz)
See also chapter "Technical information", section 8 "Energy
supply networks".
Rated current IR
Referred to 50 °C / 40 °C rated temperature
Test voltage Vtest
2240 V DC, 2 s (line/line)
2720 V DC, 2 s (lines/case)
Overload capability (thermal)
1.5 IR for 3 min per hour or
2.5 IR for 30 s per hour
Leakage current lLK
At VR and 50 Hz
Climatic category (IEC 60068-1) 25/100/21 (25 °C/+100 °C/21 days damp heat test)
Approvals
Please read Cautions and warnings and
Important notes at the end of this document.
IEC 60939, UL 1283, CSA C22.2 No.8
Page 3 of 16
3-line filters
B84243A*000
for converters and power electronics
Characteristics and ordering codes
IR
50 °C
A
IR
Terminal
ILK
40 °C cross section
mm2
A
mA
Approvals
mΩ
Approx. Ordering code
weight
kg
40
14
10
7
4
3
2
1.5
1.2
1.2
1.2
0.9
0.8
0.8
0.7
0.5
0.4
0.4
0.5
0.6
0.7
1.2
1.4
2.3
2.6
2.8
6
6
8
8
11
11
14
15
17
17
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
Rtyp
VR = 305/530 V AC
3
8
12
17
25
33
44
60
83
90
103
120
140
150
180
220
275
280
3.5
4
9
4
13
4
19
10
27
10
36
10
48
25
66
35
91
50
98
50
113
50
131
50
153
50
164
50
197
95
230
95
301
150
306
240
2.6
4.8
4.8
4.8
4.8
4.8
6.8
12
14
14
14
14
14
14
16
17
17
17
B84243A8003U000
B84243A8008W000
B84243A8012W000
B84243A8017W000
B84243A8025W000
B84243A8033W000
B84243A8044X000
B84243A8060W000
B84243A6083Z000
B84243A6090Z000
B84243A6103Z000
B84243A6120Z000
B84243A6140Z000
B84243A6150Z000
B84243A6180Z000
B84243A6220B000
B84243A6275A000
B84243A6280A000
× = Approval granted
Please read Cautions and warnings and
Important notes at the end of this document.
Page 4 of 16
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
3-line filters
B84243A*000
for converters and power electronics
Dimensional drawings
B84243A8003* ... B84243A8060* (3 A ... 60 A)
General tolerances according to ISO 2768cL
Dimensions in mm
IR
A
3
8
12
17
25
33
44
60
Dimensions (mm)
A
190
190
190
250
270
270
310
250
B
40
40
40
45
50
50
50
85
C
95
95
95
85
100
100
95
120
D
180
180
180
235
255
255
295
235
Tightening torque in Nm
E
20
20
20
25
30
30
30
60
Please read Cautions and warnings and
Important notes at the end of this document.
F
5.5
5.5
5.5
5.5
5.5
5.5
5.5
6.5
G
160
160
160
210
230
230
280
210
H
M5
M5
M5
M5
M5
M5
M6
M6
K
20
20
20
22.5
25
25
25
42.5
L
15
15
15
15
15
15
15
15
Page 5 of 16
Terminal
0.9 ±0.1
0.9 ±0.1
0.9 ±0.1
2.0 ±0.1
2.0 ±0.1
2.0 ±0.1
2.0 ±0.1
2.0 ±0.1
PE
3.0 ±0.1
3.0 ±0.1
3.0 ±0.1
3.0 ±0.1
3.0 ±0.1
3.0 ±0.1
5.0 ±0.1
5.0 ±0.1
3-line filters
B84243A*000
for converters and power electronics
B84243A6083* ... B84243A6220* (83 A ... 220 A)
General tolerances according to ISO 2768cL
Dimensions in mm
IR
A
83
90
103
120
140
150
180
220
Dimensions (mm)
A
270
270
270
270
275
275
380
380
B
80
80
105
105
100
100
120
120
C
185
185
190
190
270
270
210
210
D
255
255
255
255
260
260
365
365
Tightening torque in Nm
E
60
60
65
65
65
65
102
102
Please read Cautions and warnings and
Important notes at the end of this document.
F
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
G
270
270
270
270
275
275
379
379
H
M8
M8
M10
M10
M10
M10
M10
M10
K
40
40
52.5
52.5
50
50
60
60
L
Page 6 of 16
80
80
100
100
100
100
30
30
Terminal
7.0 ±1
7.0 ±1
7.0 ±1
7.0 ±1
7.0 ±1
7.0 ±1
17.5 ±2.5
17.5 ±2.5
PE
6.0 ±0.3
6.0 ±0.3
10 ±1
10 ±1
10 ±1
10 ±1
10 ±1
10 ±1
3-line filters
B84243A*000
for converters and power electronics
B84243A6275A000 (275 A)
General tolerances according to ISO 2768cL
Dimensions in mm
Tightening torque in Nm
Terminal
27.5 ±2.5
Please read Cautions and warnings and
Important notes at the end of this document.
Page 7 of 16
PE
10 ±1
3-line filters
B84243A*000
for converters and power electronics
B84243A6280A000 (280 A)
General tolerances according to ISO 2768cL
Dimensions in mm
Tightening torque in Nm
Terminal
27.5 ±2.5
Please read Cautions and warnings and
Important notes at the end of this document.
Page 8 of 16
PE
10 ±1
3-line filters
B84243A*000
for converters and power electronics
Insertion loss (typical values at Z = 50 Ω)
Filters for 3 A to 12 A
Filters for 17 A and 25 A
Filters for 33 A and 44 A
Filter for 60 A
Please read Cautions and warnings and
Important notes at the end of this document.
Page 9 of 16
3-line filters
B84243A*000
for converters and power electronics
Insertion loss (typical values at Z = 50 Ω)
Filters for 83 A and 90 A
Filters for 103 A and 120 A
Filters for 140 A and 150 A
Filters for 180 A to 280 A
Please read Cautions and warnings and
Important notes at the end of this document.
Page 10 of 16
3-line filters
B84243A*000
for converters and power electronics
Cautions and warnings
Please read all warning and safety notes carefully before installing the filter and putting it into operation (see ). The same applies to the warning signs on the filter. Please ensure that the signs
are not removed nor their legibility impaired by external influences.
Death, serious bodily injury and substantial material damage to equipment may occur if the appropriate safety measures are not carried out or the warnings in the text are not observed.
Using according to the terms
The filters may be used only for their intended application within the specified values in lowvoltage networks in compliance with the instructions given in the data sheets and the data book.
The conditions at the place of application must comply with all specifications for the filter used.
Warning
It shall be ensured that only qualified persons (electricity specialists) are engaged on work such
as planning, assembly, installation, operation, repair and maintenance. They must be provided
with the corresponding documentation.
Danger of electric shock. Filters contain components that store an electric charge. Dangerous
voltages can continue to exist at the filter terminals for longer than five minutes even after the
power has been switched off.
The protective earth connections shall be the first to be made when the filter is installed and the
last to be disconnected. Depending on the magnitude of the leakage currents, the particular
specifications for making the protective earth connection must be observed.
Impermissible overloading of the filter or filter, such as with circuits able to cause resonances,
impermissible voltages at higher frequencies etc. can lead to bodily injury and death as well as
cause substantial material damages (e.g. destruction of the filter housing).
Filters must be protected in the application against impermissible exceeding of the rated currents by overcurrent protective devices.
In case of leakage currents >3.5 mA you shall mount the PE conductor stationary with the required cross section before beginning of operation and save it against disconnecting. For leakage currents IL1) ≤10 mA the PE conductor must have a KU value2) of 4.53); for leakage currents
IL >10 mA the PE conductor must have a KU value of 64).
Output chokes and output filters must be protected in the application against impermissible exceeding of the component temperature.
The converter output frequency must be within the specified range to avoid resonances and uncontrolled warming of the output chokes and output filters.
Because the product can become very hot during operation, there is the risk of burns if
touched. The product can remain hot for some time after the power is switched off!
1) IL = leakage current let-go
2) The KU value (symbol KU) is a classification parameter of safety-referred failure types designed to ensure protection against hazardous
body currents and excessive heating.
3) A value of KU = 4.5 with respect to interruptions is attained with: a) permanently connected protective earth connection ≥1.5 mm2 and
b) a protective earth connection ≥2.5 mm2 via connectors for industrial equipment (IEC 603092)
4) KU = 6 with respect to interruptions is achieved for fixed-connection lines ≥10 mm2 where the type of connection and installation correspond to the requirements for PEN conductors as specified in relevant standards.
Please read Cautions and warnings and
Important notes at the end of this document.
Page 11 of 16
3-line filters
B84243A*000
for converters and power electronics
The table below summarizes the safety instructions that must be observed without fail. A detailed
description can be found in the relevant chapters of the databook.
Topic
Instructions
Selecting a filter
When selecting a filter, it is mandatory to observe the
rated data of the equipment (such as its rated input
current, rated voltage, harmonic content etc.) as well
as the derating instructions in Chapters 9 and 10.
Rated voltage
When power distribution systems deviating from the
symmetric TN-S system is to check the suitability of
the filters and the allowed voltages including the fault
cases.
Protection from
Active parts must be discharged within 5 s to a
residual voltages
voltage of less than 60 V (or 50 μ C). If this limit
Discharge resistors cannot be observed due to the operating mode, the
hazardous point must be permanently marked in a
clearly visible way.
Filters which are not permanently connected (e.g.
when the test voltage is applied to the filter at the
incoming goods inspection) must be discharged after
the voltage has been switched off.
Installing and
removing of filters
Installation
Reference chapter
(data book),
paragraph
Selection guide for
converter filters
Power distribution
systems,
7
Safety regulations,
6.1
Safety regulations,
6.2
When installing and removing our filters, a Safety regulations,
voltage-free state must be set up and secured with 6.4
observance of the five safety rules described in
EN 50110-1.
Use in IT systems
The special features of the IT system ("first fault case" Power distribution
and other fault cases) shall be observed.
system (network
types), 7.6
Safety notes on
leakage currents
The filter leakage currents specified in the data book
are intended for user information only.The maximum
leakage current of the entire electrical equipment or
appliance has to be limited for safety reasons. Please
obtain the applicable limits for your application from
the relevant regulations, provisions and standards.
Leakage current,
8.4
Leakage current,
8.6
Voltage derating
If the permissible limits for the higher-frequency Voltage derating,
Hazards caused by voltages at the filter are exeeded, the filter may be 9.8
damaged or destroyed.
overloading the
filters
Current derating at
elevated ambient
temperatures
Non-observance of the current derating may lead to Current derating,
overheating and consequently represents a fire 10.1
hazard.
Please read Cautions and warnings and
Important notes at the end of this document.
Page 12 of 16
3-line filters
B84243A*000
for converters and power electronics
Topic
Protective earth
connection at
operating currents
>250 A
Reference chapter
(data book),
paragraph
For operating currents greater than 250 A, we Mounting
recommend the PE connection to be set up between instructions,
the feed (filter: line) and output (filter: load) not via the point 2
PE terminal bolt in the filter housing.
Instructions
Mounting position
Note the mounting position of the filters! It must Mounting
always be ensured that natural convection is not instructions,
impaired.
point 13
Long motor cables
Long motor cables cause parasitic currents in the
installation. The cable lengths indicated for the output
chokes and output filters serve for orientation. The
user must check the technical parameters and
especially the choke temperatures for the respective
application.
Mounting
instructions,
point 15
Display of ordering codes for TDK Electronics products
The ordering code for one and the same product can be represented differently in data sheets,
data books, other publications, on the company website, or in order-related documents such as
shipping notes, order confirmations and product labels. The varying representations of the ordering codes are due to different processes employed and do not affect the specifications
of the respective products.
Detailed information can be found on the Internet under
www.tdk-electronics.tdk.com/orderingcodes.
Please read Cautions and warnings and
Important notes at the end of this document.
Page 13 of 16
3-line filters
B84243A*000
for converters and power electronics
Symbols and terms
Symbol English
α
Insertion loss
CR
Rated capacitance
CX
Capacitance X capacitor
CY
Capacitance Y capacitor
ΔV
Voltage drop (input to output)
dv/dt
Rate of voltage rise
f
Frequency
fM
Converter output frequency
fP
Pulse frequency
fR
Rated frequency
fres
Resonant frequency
IC
Current through capacitor
ILK
Filter leakage current
Imax
Maximum current
IN
Nominal current
Iop
Operating current (design current)
Ipk
Rated peak withstand current
Iq
Capacitive reactive current
IR
Rated current
IS
Interference current
L
Inductance
LR
Rated inductance
Lstray
Stray inductance
PL
Power loss
R
Resistance
Ris
Insulation resistance
Rtyp
DC resistance, typical value
TA
Ambient temperature
Tmax
Upper category temperature
Tmin
Lower category temperature
TR
Rated temperature
Referred voltage drop in %
uk
RMS voltage
Veff
VK
Voltage drop
VLE
Voltage line to earth; voltage line to ground
VN
Nominal voltage
VR
Rated voltage
Vpeak
Peak voltage
Vtest
Test voltage
VX
Voltage over X capacitor
VY
Voltage over Y capacitor
Inductive reactance
XL
Impedance
Z
|Z|
Impedance, absolute value
Please read Cautions and warnings and
Important notes at the end of this document.
German
Einfügungsdämpfung
Bemessungskapazität
Kapazität X-Kondensator
Kapazität Y-Kondensator
Spannungsabfall (Eingang zu Ausgang)
Spannungsanstiegsgeschwindigkeit
Frequenz
Motorfrequenz
Pulsfrequenz
Bemessungsfrequenz
Resonanzfrequenz
Strom durch Kondensator
Filter-Ableitstrom
Maximalstrom
Nennstrom
Betriebsstrom
Bemessungs-Stoßstromfestigkeit
Kapazitiver Blindstrom
Bemessungsstrom
Störstrom
Induktivität
Bemessungsinduktivität
Streuinduktivität
Verlustleistung
Widerstand
Isolationswiderstand
Gleichstromwiderstand typisch
Umgebungstemperatur
Obere Kategorietemperatur
Untere Kategorietemperatur
Bemessungstemperatur
Bezogener Spannungsabfall in %
Effektivspannung
Spannungsabfall
Spannung Phase zu Erdpotential
Nennspannung
Bemessungsspannung
Spitzenspannung
Prüfspannung
Spannung über X-Kondensator
Spannung über Y-Kondensator
Induktiver Blindwiderstand
Scheinwiderstand
Scheinwiderstand (Betragswert)
Page 14 of 16
Important notes
The following applies to all products named in this publication:
1. Some parts of this publication contain statements about the suitability of our products for
certain areas of application. These statements are based on our knowledge of typical requirements that are often placed on our products in the areas of application concerned. We
nevertheless expressly point out that such statements cannot be regarded as binding
statements about the suitability of our products for a particular customer application.
As a rule, we are either unfamiliar with individual customer applications or less familiar with
them than the customers themselves. For these reasons, it is always ultimately incumbent on
the customer to check and decide whether a product with the properties described in the
product specification is suitable for use in a particular customer application.
2. We also point out that in individual cases, a malfunction of electronic components or
failure before the end of their usual service life cannot be completely ruled out in the
current state of the art, even if they are operated as specified. In customer applications
requiring a very high level of operational safety and especially in customer applications in
which the malfunction or failure of an electronic component could endanger human life or
health (e.g. in accident prevention or lifesaving systems), it must therefore be ensured by
means of suitable design of the customer application or other action taken by the customer
(e.g. installation of protective circuitry or redundancy) that no injury or damage is sustained by
third parties in the event of malfunction or failure of an electronic component.
3. The warnings, cautions and product-specific notes must be observed.
4. In order to satisfy certain technical requirements, some of the products described in this
publication may contain substances subject to restrictions in certain jurisdictions (e.g.
because they are classed as hazardous). Useful information on this will be found in our Material Data Sheets on the Internet (www.tdk-electronics.tdk.com/material). Should you have
any more detailed questions, please contact our sales offices.
5. We constantly strive to improve our products. Consequently, the products described in this
publication may change from time to time. The same is true of the corresponding product
specifications. Please check therefore to what extent product descriptions and specifications
contained in this publication are still applicable before or when you place an order. We also
reserve the right to discontinue production and delivery of products. Consequently, we
cannot guarantee that all products named in this publication will always be available. The
aforementioned does not apply in the case of individual agreements deviating from the foregoing for customer-specific products.
6. Unless otherwise agreed in individual contracts, all orders are subject to our General
Terms and Conditions of Supply.
Page 15 of 16
Important notes
7. Our manufacturing sites serving the automotive business apply the IATF 16949 standard. The IATF certifications confirm our compliance with requirements regarding the quality
management system in the automotive industry. Referring to customer requirements and customer specific requirements (“CSR”) TDK always has and will continue to have the policy of
respecting individual agreements. Even if IATF 16949 may appear to support the acceptance
of unilateral requirements, we hereby like to emphasize that only requirements mutually
agreed upon can and will be implemented in our Quality Management System. For clarification purposes we like to point out that obligations from IATF 16949 shall only become
legally binding if individually agreed upon.
8. The trade names EPCOS, CarXield, CeraCharge, CeraDiode, CeraLink, CeraPad, CeraPlas,
CSMP, CTVS, DeltaCap, DigiSiMic, ExoCore, FilterCap, FormFit, LeaXield, MiniBlue,
MiniCell, MKD, MKK, ModCap, MotorCap, PCC, PhaseCap, PhaseCube, PhaseMod, PhiCap,
PowerHap, PQSine, PQvar, SIFERRIT, SIFI, SIKOREL, SilverCap, SIMDAD, SiMic, SIMID,
SineFormer, SIOV, ThermoFuse, WindCap, XieldCap are trademarks registered or pending in Europe and in other countries. Further information will be found on the Internet at
www.tdk-electronics.tdk.com/trademarks.
Release 2020-06
Page 16 of 16