0
登录后你可以
  • 下载海量资料
  • 学习在线课程
  • 观看技术视频
  • 写文章/发帖/加入社区
会员中心
创作中心
发布
  • 发文章

  • 发资料

  • 发帖

  • 提问

  • 发视频

创作活动
B84299D6050B003

B84299D6050B003

  • 厂商:

    TDK(东电化)

  • 封装:

    -

  • 描述:

    FILTER POWER LINE 250VAC 5A

  • 数据手册
  • 价格&库存
B84299D6050B003 数据手册
Datasheet Power line filter for shielded rooms & secure area 250/277/480 V, 50/60 Hz, 1--100 A, 40 °C Ordering code: B84299D6***A(B)00* Date: 2011--07--22 Version: 06  EPCOS AG 2011. Reproduction, publication and dissemination of this publication, enclosures hereto and the information contained therein without EPCOS’ prior express consent is prohibited. Page 1 of 10 Power line filter B84299D6***A(B)00* for shielded rooms & secure area Technical data and measuring conditions Rated frequency fR 50/60 Hz Rated temperature TR 40 °C Overload capability (thermal) for 3 min per hour or for 30 s per hour 1.5 x IR 2.5 x IR Climatic category (IEC 60068--1) 25/85/21 Rated frequency fR 50/60 Hz B84299D60*0B003 -- Rated voltage Ur 250 V AC Test voltage line to line for 2 s Utest 1768 V DC Test voltage line to case for 2 s Utest 2121 V DC B84299D6300B000 -- Rated voltage Ur 250 V AC Test voltage line to line for 2 s Utest 1768 V DC Test voltage line to case for 2 s Utest 2121 V DC B84299D6*00B003 -- Rated voltage Ur 480 V AC Test voltage line to line for 2 s Utest 2158 V DC Test voltage line to case for 2 s Utest 2200 V DC B84299D6101A003 -- Rated voltage Ur 277 V AC Test voltage line to line for 2 s Utest 2158 V DC Test voltage line to case for 2 s Utest 2200 V DC Characteristics and ordering codes IR LINE terminals: threaded studs LOAD terminals: cabels A Ileak 2) Rtyp Approx. weight mA mΩ kg Ordering code Approvals for USA, Canada: UL (listed) cUL (listed) 1 #6--32 UNC 2A AWG 18 1.6 107 1.9 B84299D6010B003 x 5 #6--32 UNC 2A AWG 18 1.6 107 1.9 B84299D6050B003 x 30 M6 AWG 12 157 3.2 1.5 B84299D6300B000 x 30 M6 AWG 10 1706 7.7 10.8 B84299D6300B003 x 60 M8 AWG 6 1714 6 22 B84299D6600B003 x 100 M10 AWG 2 3751 3 11.5 B84299D6101A003 x 2) Calculation according draft proposal IEC 60939--1 Ed. 3 (2008--10--29), annex A, ”Calculation of leakage current” at 50Hz. 3) X = approval granted P = pending D = design complies with - = none Please read Cautions and warnings and Important notes at the end of this document. Page 2 of 10 B84299-- D6*-- A(B)*-- 06-- 7659 Power line filter B84299D6***A(B)00* for shielded rooms & secure area Circuit diagram for B84299D6010B003 and B84299D6050B003 LINE L L’ N N’ LOAD Circuit diagram for B84299D6300B000 LOAD LINE L L’ N N’ Circuit diagram for B84299D6300B003 LOAD LINE L1 L1’ L2 L2’ Please read Cautions and warnings and Important notes at the end of this document. Page 3 of 10 B84299-- D6*-- A(B)*-- 06-- 7659 Power line filter B84299D6***A(B)00* for shielded rooms & secure area Circuit Diagram for B84299D6600B003 LINE LOAD L1 L1’ L2 L2’ Circuit Diagram for B84299D6101A003 LOAD LINE L’ L Please read Cautions and warnings and Important notes at the end of this document. Page 4 of 10 B84299-- D6*-- A(B)*-- 06-- 7659 Power line filter B84299D6***A(B)00* for shielded rooms & secure area 60 #0.1 Dimensions for B84299D6010B003, B84299D6050B003 20 89 230 Beschriftung 3x Litze/ Litz wire AWG18 24 20.6 30 20 #5 39.8 30+10 +10 450 M4 63 25 10 15 79 M25x1,5 All dimensions are in mm. Please read Cautions and warnings and Important notes at the end of this document. Page 5 of 10 B84299-- D6*-- A(B)*-- 06-- 7659 Power line filter B84299D6***A(B)00* for shielded rooms & secure area Dimensions for B84299D6300B000 All dimensions are in mm. Please read Cautions and warnings and Important notes at the end of this document. Page 6 of 10 B84299-- D6*-- A(B)*-- 06-- 7659 Power line filter B84299D6***A(B)00* for shielded rooms & secure area Dimensions for B84299D6300B003 All dimensions are in mm. Please read Cautions and warnings and Important notes at the end of this document. Page 7 of 10 B84299-- D6*-- A(B)*-- 06-- 7659 Power line filter B84299D6***A(B)00* for shielded rooms & secure area Dimensions for B84299D6600B003 All dimensions are in mm. Please read Cautions and warnings and Important notes at the end of this document. Page 8 of 10 B84299-- D6*-- A(B)*-- 06-- 7659 Power line filter B84299D6***A(B)00* for shielded rooms & secure area Dimensions for B84299D6101A003 All dimensions are in mm. Please read Cautions and warnings and Important notes at the end of this document. Page 9 of 10 B84299-- D6*-- A(B)*-- 06-- 7659 Power line filter B84299D6***A(B)00* for shielded rooms & secure area Cautions and warnings S S S S S S S Please note the advices in our data book “EMC Filters” (latest edition); attention should be paid to the chapter “General safety notes”. It shall be ensured that only qualified persons (electricity specialists) are engaged on work such as planning, assembly, installation, operation, repair and maintenance. They must be provided with the corresponding documentation. Danger of electric shock. EMC filters contain components that store an electric charge. Dangerous voltages can continue to exist at the filter terminals for longer than five minutes even after the power has been switched off. The protective earth connections shall be the first to be made when the EMC filter is installed and the last to be disconnected. Depending on the magnitude of the leakage currents, the particular specifications for making the protective--earth connection must be observed. Impermissible overloading of the EMC filter, such as with circuits able to cause resonances, impermissible voltages at higher frequencies etc. can lead to bodily injury and death as well as cause substantial material damages (e.g. destruction of the filter housing). EMC filters must be protected in the application against impermissible exceeding of the rated currents by overcurrent protective. In case of leakage currents > 3.5 mA you shall mount the PE conductor stationary with the required cross section before beginning of operation and save it against disconnecting. For leakage currents IL 4) < 10 mA the PE conductor must have a KU value 3) of 4.5; for leakage currents IL  10 mA the PE conductor must have a KU value of 6. 3) The KU value (symbol KU) is a classification parameter of safety--referred failure types designed to ensure protection against hazardous body currents and excessive heating. A value of KU = 4.5 with respect to interruptions is attained: -- with a permanently connected protective earth circuit ≥ 1.5 mm2 -- with a protective earth circuit ≥ 2.5 mm2 connected via shroud connectors (IEC 60309--2). KU = 6 with respect to interruptions is achieved for fixed--connection lines ≥ 10 mm2 where the type of connection and line layout correspond to the requirements for PEN conductors as specified in relevant standards. 4) IL = leakage current let--go Important notes The following applies to all products named in this publication: 1. Some parts of this publication contain statements about the suitability of our products for certain areas of application. These statements are based on our knowledge of typical requirements that are often placed on our products in the areas of application concerned. We nevertheless expressly point out that such statements cannot be regarded as binding statements about the suitability of our products for a particular customer application. As a rule, EPCOS is either unfamiliar with individual customer applications or less familiar with them than the customers themselves. For these reasons, it is always ultimately incumbent on the customer to check and decide whether an EPCOS product with the properties described in the product specification is suitable for use in a particular customer application. 2. We also point out that in individual cases, a malfunction of electronic components or failure before the end of their usual service life cannot be completely ruled out in the current state of the art, even if they are operated as specified. In customer applications requiring a very high level of operational safety and especially in customer applications in which the malfunction or failure of an electronic component could endanger human life or health (e.g. in accident prevention or life--saving systems), it must therefore be ensured by means of suitable design of the customer application or other action taken by the customer (e.g. installation of protective circuitry or redundancy) that no injury or damage is sustained by third parties in the event of malfunction or failure of an electronic component. 3. The warnings, cautions and product-- specific notes must be observed. 4. In order to satisfy certain technical requirements, some of the products described in this publication may contain substances subject to restrictions in certain jurisdictions (e.g. because they are classed as hazardous). Useful information on this will be found in our Material Data Sheets on the Internet (www.epcos.com/material). Should you have any more detailed questions, please contact our sales offices. 5. We constantly strive to improve our products. Consequently, the products described in this publication may change from time to time. The same is true of the corresponding product specifications. Please check therefore to what extent product descriptions and specifications contained in this publication are still applicable before or when you place an order. We also reserve the right to discontinue production and delivery of products. Consequently, we cannot guarantee that all products named in this publication will always be available. The aforementioned does not apply in the case of individual agreements deviating from the foregoing for customer--specific products. 6. Unless otherwise agreed in individual contracts, all orders subject to the current version of the “General Terms of Delivery for Products and Services in the Electrical Industry” published by the the German Electrical and Electronics Industry Association (ZVEI). 7. The trade names EPCOS, BAOKE, Alu--X, CeraDiode, CSMP, CSSP, CTVS, DeltaCap, DigiSiMic, DSSP, FormFit, MiniBlue, MiniCell, MKD, MKK, MLSC, MotorCAP, PCC, PhaseCap, PhaseCube, PhaseMod, PhiCap, SIFERRIT, SIFI, SIKOREL, SilverCap, SIMDAD, SiMic, SIMID, SineFormer, SIOV, SIP5D, SIP5K, ThermoFuse, WindCap are trademarks registered or pending in Europe and in other countries. Further information will be found on the Internet at www.epcos.com/trademarks. 1 Please read Cautions and warnings and Important notes at the end of this document. Page 10 of 10 B84299-- D6*-- A(B)*-- 06-- 7659
B84299D6050B003 价格&库存

很抱歉,暂时无法提供与“B84299D6050B003”相匹配的价格&库存,您可以联系我们找货

免费人工找货