DIN FUSES
BS88
SEMICONDUCTOR PROTECTION FUSES
PROTISTOR® FUSES 500-690V AC gRB/URB FROM 20 TO 400A SIZE: 000
Features / Benefits ➤ Extremely High Interrupting Rating Fuses: Protection of Power Semiconductors according to IEC 269. and EN 60269-.4 ➤ 500-690V Voltage Rating (Rating 20 to 400A) ➤ gR Class (gRB Ratings 20 to 125A) According to VDE 636-23. -Full range protection -Improving safety and protection -Allows selective coordination ➤ aR Class (URB Ratings 75 to 400A) According to VDE 636-23 and IEC 269.4 ➤ Two models according to BS 88-4 and EN 60 269.4 Standards: Z3 Drawing (74mm Between Axes) External open fuse with and without indicator
C
VOLTAGE RATING UN( V ) CLASS
US
CURRENT RATING IN( A ) 20 25 32 40 50 63 80 100 125 75 80 100 110 125 160 200 250 315 350 400 MELTING I2t @ 1 ms I2tp (A2s) 12 20 39 70 102 210 475 970 1900 350 390 690 950 1300 2700 5250 9900 15500 22400 33200
APPLICATIONS DATA
TOTAL CLEARING I2t @ UN I2tt (A2s) 80 150 270 460 730 1500 2900 6000 11800 2250 2500 4200 6800 8900 16000 31500 52000 82000 110000 160000 WATT LOSSES 0.8 IN 3.8 5.0 5.5 6.6 7.7 8.8 9.9 11 11.6 11.2 11.6 12.7 13.5 14.3 17.0 19.8 24.8 31.9 31.9 36.3 IN 7 9 10 12 14 16 18 20 21 20.5 21 23 24.5 26 31 36 45 58 58 66 TESTED INTERRUPTING RATING ESTIMATED INTERRUPTING RATING
690
gRB
200 k A @ 660 V
300 k A @ 660 V
690
URB
200 k A @ 660 V
300 k A @ 660 V
660 500
URB
120 k A @ 500 V
Minimum operating voltage for the external trip-indicator: 20V
D 56
AMP-TRAP®–Form 101
BS88
SEMICONDUCTOR PROTECTION FUSES
C British Standard without open fuse indicator
CURRENT RATING
US
REF #
T330044 V330045 W330046 X330047 Z330049 A330050 N330108 H330103 P330109 B330051 C330052 D330053 E330100 E330054 F330101 F330055 G330056 H330057 J330058 X330116 G330194
CATALOG NO.
6,9 gRB 000 BS88/020 6,9 gRB 000 BS88/025 6,9 gRB 000 BS88/032 6,9 gRB 000 BS88/040 6,9 gRB 000 BS88/050 6,9 gRB 000 BS88/063 6,9 gRB 000 BS88/080 6,9 gRB 000 BS88/100 6,9 gRB 000 BS88/125 6,9 URB 000 BS88/075 6,9 URB 000 BS88/080 6,9 URB 000 BS88/100 6,9 URB 000 BS88/110 6,9 URB 000 BS88/125 6,9 URB 000 BS88/150 6,9 URB 000 BS88/160 6,9 URB 000 BS88/200 6,9 URB 000 BS88/250 6,6 URB 000 BS88/315 5 URB 000 BS88/350 5 URB 000 BS88/400
50
1.5 21.5
8.7 36
12.7 4 70 ± 4 9
20 25 32 40 50 63 80 100 125 75 80 100 110 125 150 160 200 250 315 350 400
D
C British Standard with external open fuse trip-indicator
CURRENT RATING
US
REF #
Y330117 Z330118 A330119 B330120 C330121 D330122 E330123 F330124 G330125 H330126 J330127 K330128 L330129 M330130 N330131 P330132 Q330133 R330134 S330135 T330136 H330195
CATALOG NO.
6,9 gRB 000 BS88P/020 6,9 gRB 000 BS88P/025 6,9 gRB 000 BS88P/032 6,9 gRB 000 BS88P/040 6,9 gRB 000 BS88P/050 6,9 gRB 000 BS88P/063 6,9 gRB 000 BS88P/080 6,9 gRB 000 BS88P/100 6,9 gRB 000 BS88P/125 6,9 URB 000 BS88P/075 6,9 URB 000 BS88P/080 6,9 URB 000 BS88P/100 6,9 URB 000 BS88P/110 6,9 URB 000 BS88P/125 6,9 URB 000 BS88P/150 6,9 URB 000 BS88P/160 6,9 URB 000 BS88P/200 6,9 URB 000 BS88P/250 6,6 URB 000 BS88P/315 5 URB 000 BS88P/350 5 URB 000 BS88P/400
50
1.5 27
8.7 36
12.7 4 70 ± 94
The use of MC 6.3 GR 2-5N blown fuse remote sensing microswitch is possible. Ref. Number: Y 310015 mounted on separate trip-indicator. See Microswitch section page J10, J12.
20 25 32 40 50 63 80 100 125 75 80 100 110 125 150 160 200 250 315 350 400
D 57