Energy Management Compact Transducer for AC Measurements Type CVT-DIN AV1/AV4/AV5
• For AC current/voltage measurement • Field adjustment capability • For DIN-rail mounting • Degree of protection: IP 50
Product Description
Compact transducer for AC current/voltage measurements with field adjustment capability. The housing is for DIN-rail mounting and ensures a degree of protection of IP 50.
Ordering Key
Model Range code Measurement Power supply Setpoints Rated output Calibration
CVT-DIN AV5AD01X
Type Selection
Range code AV1: AV4: AV5: 100 VAC - 1 AAC (max. 120 VAC - 1.2 A) 100 VAC - 5 AAC (max. 120 VAC - 6 A) 500 VAC - 5 AAC (max.600VAC- 6 A) Power supply A: B: C: D: 24 VAC, -15% +10%, 50/60 Hz 1) 48 VAC, -15% +10%, 50/60 Hz 1) 115 VAC, -15% +10%, 50/60 Hz 1) 230 VAC, -15% +10%, 50/60 Hz (standard) Rated output 1: 2: 3: 4: Analogue output 0 to 20 mA (standard) Analogue output 4 to 20 mADC 1) Analogue output 0 to 10 VDC 1) Analogue output 0 to ±1 VDC 1) Calibration X: Y: Standard calibration Special calibration, use ”Y” followed by requested value
1)
On request
Input Specifications
Accuracy (@ 25°C ± 5°C, R.H. ≤ 60%) Additional errors: Humidity Input frequency Magnetic field Ripple Rated input AV1: AV4: AV5: ± 0.5% f.s., (0.1 ln/Un to 1 In/Un) The given accuracy already includes: frequency, power supply, output load influences < 0.3%, 60% to 90% R.H. < 0.4%, 62 to 400 Hz < 0.5%, @ 400 A/m ≤ 1% according to IEC 60688-1 and EN 60688-1 1 A (1 V internal shunt/1 Ω imp)/ 100 VAC (200 kΩ impedance) 5 A (250 mV internal shunt/ 0,05 Ω impedance) / 100 VAC (200 kΩ imp.) 5 A (250 mV internal shunt/ 0,05 Ω impedance) / 500 VAC (1 MΩ imp.) AC frequency range Overload protection Cont.: Current: Voltage: For 1 s: Current: Voltage: 48 to 62 Hz 1.2 x rated input 1.2 x rated input 20 x rated input 2 x rated input
Specifications are subject to change without notice
1
CVT-DIN AV1/AV4/AV5
General Specifications
Warm-up time Operating temperature Storage temperature Insulation reference voltage Insulation 15 minutes 0 to 50°C (32 to 122°F) (R.H. < 90% non-condensing) -10 to 60°C (14 to 140°F) (R.H. < 90% non-condensing) 300 Vrms to ground 2000 Vrms between output and measuring input, output and supply input. 4000 Vrms between input/output and ground 4000 Vrms for 1 minute ≥ 80 dB, 48 to 62 Hz EN 50081-1, EN 50082-1 Safety standards Safety requirements Product requirements Connector Housing Dimensions Material Degree of protection Weight Approval IEC 601010-1, EN 61010-1 IEC 60688-1, EN 60688-1 Screw-type, max. 2.5 mm2 wires 4-DIN modules, 58.5 x 89 x 71.5 mm ABS, self-extinguishing: UL 94 V-0 IP 50 300 g approx. (packing included) CE
Dielectric strength Noise rejection CMRR EMC
Output Specifications
Range/load 0 to 20 mA 4 to 20 mA 0 to 10 V 0 to ±1 V Adjustment Load: ≤ 500 Ω Load: ≤ 500 Ω Load: ≥ 10 kΩ Load: ≥ 10 kΩ Easy field adjustment from 50 to 130% of the I/U inputs which can be modified without any calibrator being requested 300 ms typical 200 ppm/ºC
Supply Specifications
AC supply 230 VAC, -15% +10%, 50/60 Hz (standard) 24 VAC, 48 VAC, 115 VAC, -15% +10%, 50/60 Hz (on request) ≤ 5 VA
Power consumption
Response time Temperature drift
Dimensions
Connections
230VAC 115VAC 48VAC 24VAC
~
~
1
3
CVT-DIN A-V AC/DC
4 56 8 10 11 12
Note Measurement inputs Current measurement: between current input and common (1) terminals; Voltage measurement: between voltage input and common (1) terminals.
2
Specifications are subject to change without notice
+ OUTPUT: 10V/±1V..... –
ADJUSTMENT INPUT: current (1) COM.
INPUT: voltage
OUTPUT: 20mA
+ .. –
} }