    F880 - 8-segment redundant fieldbus power system for use with Yokogawa CENTUM 3000 R3 Control System...

  • 详情介绍
  • 数据手册
  • 价格&库存
F880 数据手册
8-segment redundant fieldbus power system for use with Yokogawa CENTUM 3000 R3 Control System F880 ♦ Integrated redundant fieldbus power for ALF111 FOUNDATION fieldbus™ cards ♦ ♦ ♦ ♦ Low power dissipation Passive module carrier On-line diagnostics option Redundant power & conditioning ♦ ♦ High-density, compact design Fully isolated The F880 fieldbus power system is designed to provide redundant power for eight FOUNDATION fieldbusTM H1 segments when used with Yokogawa ALF111 fieldbus cards. The F880 module carrier has system connectors for direct connection to two redundant pairs of fieldbus cards using Yokogawa AKB336 cables. Power for the fieldbus segments is provided by two F801 power modules operating in a redundant configuration. Failure alarms, galvanic isolation, power conditioning and segment termination are incorporated into each F801 module. In simplex applications, a single F801 module may be used. Termination of the fieldbus segments is automatically maintained when single or redundant F801 modules are fitted. For extreme reliability, the module carrier has no components and only provides interconnections between the power modules and external connections. It is supported in a rigid metal frame that protects the circuit board from mechanical damage. Secure DIN-rail mounting is provided by integrated fixings. Each F801 module monitors the output of the eight fieldbus segments and indicates an alarm by means of a built-in, normally closed relay if any of the segments is shorted or below the minimum output voltage threshold. Failure of either of the bulk power input supplies is also annunciated. The alarm contacts are volt-free and galvanically isolated from other circuitry. Connections to the alarm relays are made via terminals on the F880-CA carrier. A separate alarm module is not required for this function. LED indicators also show the status of each F801 module and the eight individual segments. In normal operation, each segment LED is lit, showing that the segment is powered. If a segment is shorted, this LED is extinguished, and the module Alarm LED is lit. A separate physical layer diagnostics module may be installed on the carrier to automatically collect and distribute additional diagnostic information for each of the eight fieldbus segments. The F801 module provides galvanic isolation between the 24V DC input power and the fieldbus segments, as recommended by the IEC61158-2 fieldbus standard and the FIELDBUS Foundation™ FF-831 validation test for power conditioners.There is also galvanic isolation between the fieldbus segments, thereby preventing multiple segment failures due to ground faults on more than one segment. Each segment has its own fieldbus power conditioner and current limitation. Redundant 24V DC (nom.) input power is connected to the F880 carrier using two-part pluggable connectors. Field wiring connections are available with either pluggable screw terminals (F880PS) or pluggable spring clamp terminals (F880-PC). FOUNDATION fieldbus™ is a trademark of Fieldbus Foundation™ , Austin, Texas. EUROPE (EMEA) Tel: +44 (0)1582 723633 Fax: +44 (0)1582 422283 AMERICAS Tel: +1 603 926 0090 Fax: +1 603 926 1899 ASIA PACIFIC Tel: +65 487 7887 Fax: +65 487 7997 E-mail: enquiry@mtl-inst.com Web site: www.mtl-inst.com Dec 2005 SPECIFICATION Location of equipment See Approvals OUTPUT Number of channels Eight Voltage 21.5V DC minimum 24.0V DC maximum Design current 0 to 350mA per segment Current limit > 370mA Minimum load No load Isolation Fieldbus to power supply: 250V AC rms withstand Fieldbus to fieldbus: 250V AC rms withstand INPUT Input voltage 19.2 - 30.0V DC, reverse polarity protected Current consumption (8 segments each with 350mA output load, redundant operation) 3.5A @ 24V DC input, max. Power dissipation (8 segments each with 350mA output load, redundant operation) 2.75W / segment, typ. ALARMS Alarm contact rating 1 A max. @ 30V DC max. Alarm contact status Normally closed Alarm threshold Segment output: 19V DC MECHANICAL Mounting method Integrated fixings for 'Top hat' DIN rail, 35mm x 7.5mm or 35mm x 15mm to EN50022 ELECTRICAL CONNECTIONS Host connectors Host 1A, Host 1B, Host 2A, Host 2B via AKB336 cables to ALF111 modules Field, Power & Alarm terminals Pluggable rising cage-clamp screw terminals (- PS) Conductor size: 0.14 to 2.5 mm2 Pluggable spring-clamp screw terminals (- PC) Conductor size: 0.2 to 2.5 mm2 - flexible or rigid Chassis ground Fixed rising cage-clamp screw terminals Conductor size: 0.14 to 2.5 mm2 Terminators A single termination is provided automatically by using either 1 or 2 power modules F880 - Block diagram Power A 1A F801 Power Module Power conditioning Alarm Segment 1 2 Diagnostic module 3 4 5 6 7 Segment 8 Chassis Ground Field Connections Feb 2006 Host Connections 1B 2A Isolation F801 Power Module Power conditioning 2B Power B ENVIRONMENTAL Ambient temperature Operating —40°C to +65°C Storage —40°C to +85°C Isolation (See note) Note: This temperature range applies only when the carrier DIN rail is mounted vertically on a vertical surface. Ingress protection IP20 to BS EN60529 (Additional protection by means of enclosure) ELECTRICAL EMC Compliance To EN61326:1998 Electrical equiment for measurement, control and laboratory use - EMC requirements PHYSICAL NETWORKS IEC61158-2 ISA-S50.02 Part 2-1992 FOUNDATION fieldbusTM H1 Profibus PA ORDERING INFORMATION COMPONENTS AND ACCESSORIES Part No F880-CA F801 F880-PS Description F880 module carrier, unpopulated 8-segment power module F880 system, pluggable screw terminal connectors, comprising F880 carrier and two F801 modules F880 system, pluggable spring clamp connectors, comprising F880 carrier and two F801 modules F880-PC EUROPE (EMEA) Tel: +44 (0)1582 723633 Fax: +44 (0)1582 422283 AMERICAS Tel: +1 603 926 0090 Fax: +1 603 926 1899 ASIA PACIFIC Tel: +65 487 7887 Fax: +65 487 7997 E-mail: enquiry@mtl-inst.com Web site: www.mtl-inst.com F801 module top panel showing indicators Dimensions 5.76” 146mm Segment 4 Segment 3 Segment 2 Segment 1 Linking alarm circuits ALARM DI F8xx-CA #1 ALARM 6.1” 154mm Ground Segment 8 Segment 7 Segment 6 Segment 5 Power A Host 1A Host 1B Host 2A Host 2B x8 x8 Alarm F801 Segment Pwr www.relcominc.com 503-357-5607 Alarm F880-CA 1 2 3 4 5 6 7 8 Relcom, Inc. F809 T Alarm 11.5” 292mm 1 2 34 5 F801 Segment www.relcominc.com 503-357-5607 6 78 1 2 3 4 5 6 7 www.relcominc.com Relcom Inc. 8 503-357-5607 Relcom, Inc. T Power B 6.35” 161mm F8xx-CA #2 2.38” 60.5mm 3.38” 86mm EUROPE (EMEA) Tel: +44 (0)1582 723633 Fax: +44 (0)1582 422283 AMERICAS Tel: +1 603 926 0090 Fax: +1 603 926 1899 ASIA PACIFIC Tel: +65 487 7887 Fax: +65 487 7997 E-mail: enquiry@mtl-inst.com Web site: www.mtl-inst.com Dec 2005 APPROVALS - for the latest certification information visit www.mtl-inst.com/certs_1.nsf Country – Authority FIELDBUS foundationTM Standard FF-831 Certificate PS001700 Approved for H1 Profile-132 Ratings – EUROPE (EMEA) Tel: +44 (0)1582 723633 Fax: +44 (0)1582 422283 AMERICAS Tel: +1 603 926 0090 Fax: +1 603 926 1899 ASIA PACIFIC Tel: +65 487 7887 Fax: +65 487 7997 E-mail: enquiry@mtl-inst.com Web site: www.mtl-inst.com Dec 2005
F880
1. 物料型号: - F880:模块载体,未安装任何模块。 - F801:8-segment power module,即8段电源模块。

2. 器件简介: - F880模块载体设计用于与Yokogawa ALF111现场总线卡一起使用,为FOUNDATION fieldbus™ H1段提供冗余电源。 - F801模块提供两个F801电源模块在冗余配置下为现场总线段供电。

3. 引脚分配: - F880模块载体通过Yokogawa AKB336电缆直接连接到两个冗余对的现场总线卡。 - F880-PS系统包含F880载体和两个F801模块,使用可插拔的螺丝端子。 - F880-PC系统包含F880载体和两个F801模块,使用可插拔的弹簧夹端子。

4. 参数特性: - 输出电压:最小21.5V DC,最大24.0V DC。 - 设计电流:每段0到350mA。 - 电流限制:大于370mA。 - 输入电压:19.2 - 30.0V DC,防反接保护。 - 电流消耗:在8段每段350mA输出负载下,最大3.5A @ 24V DC输入。

5. 功能详解: - F880系统提供冗余电源和调理,故障报警,每段的隔离和终止。 - F801模块提供24V DC输入电源和现场总线段之间的隔离,符合IEC61158-2现场总线标准。 - 模块载体没有组件,只提供电源模块和外部连接之间的互连,以提高可靠性。

6. 应用信息: - 适用于需要冗余电源和高密度、紧凑设计的FOUNDATION fieldbus™ H1段的应用。

7. 封装信息: - F880模块载体支持在刚性金属框架中安装,以保护电路板免受机械损伤。 - 提供DIN-rail安装固定。

很抱歉,暂时无法提供与“F880”相匹配的价格&库存,您可以联系我们找货