PAPERLESS RECORDER
DATA SHEET
This is a paperless recorder that displays measured data on the LCD in real time and stores data in CompactFlash. The type of input such as thermocouple, resistance bulb, D.C. voltage (current), etc. can be arbitrarily set to 6 channels at the maximum. The data stored in CompactFlash can be regenerated on the screen, and the use of supplied support software allows the data to be regenerated on a PC screen. The data recorded in ASCII format can be directly read in a spreadsheet such as Excel, which facilitates the processing on a PC. (The data recorded in binary format cannot be read in.)
PHF
FEATURES
1. Large capacity storage by CompactFlash Measured data is periodically stored in CompactFlash. Large storage capacity of up to 512MB allows display files for approximately 4 years to be recorded continuously at the display refresh cycle of 30 seconds (in the case of ASCII data format, 6 channels). 2. Quick search and display of past data Data stored in CompactFlash can be displayed in succession by scrolling the screen. 3. Various display capability Depending on the object of measurement, the most suitable display format can be selected from a variety of formats including bar graph display, trend display, digital display, etc. 4. PC support software supplied as standard Loader software that enables easy display and change of set data and data viewer software that regenerates the data stored in CompactFlash are supplied as standard. 5. Compact size 160 (W) × 144 (H) × 185 (D) mm (Panel mounting), 1.5kg compact size 6. 6-point recording (Option) 12 types of thermocouples, 5 types of resistance bulbs and DC voltage/current input can be recorded up to 6 points. 7. Screen saver function If the non-operation exceeds the setting value of parameter, “LCD lights-out time” recorder turns off the , backlight. Setting range of this parameter is 0 to 60 minutes. If the setting value is "0", this function doesn’t work, so the backlight remains on during power on. Screen saver function makes the life of backlight expand and power consumption reduce. 8. Ethernet function (Option) FTP , Web server, e-mail and MODBUS-TCP are available using 10Base-T.
SPECIFICATIONS
Input system
Number of input points: 3 points or 6 points (Can be selected at the time of purchase) Input circuit: Input mutual isolation Resistance bulb measured current: about 1 mA Measuring cycles: 3 or 6 points….100ms cycles Recording cycle: 1 sec to 12 hours Input types: Thermocouple, resistance bulb, DC voltage, and DC current (Shunt resistors are fitted in input terminals). Note) Order a shunt resistor (t ype: PHZP0101) separately. Measuring range
Input types Reference range 400.0 to 1760.0°C Thermocouple B 0.0 to 1760.0°C R 0.0 to 1760.0°C S –200.0 to 1370.0°C K –200.0 to 800.0°C E –200.0 to 1100.0°C J –200.0 to 400.0°C T 0.0 to 1300.0°C N 0.0 to 1760.0°C W –200.0 to 900.0°C L –200.0 to 400.0°C U 0.0 to 1300.0°C PN –200.0 to 600.0°C Resistance bulb JPt100 –200.0 to 600.0°C Pt100 –60.0 to 180.0°C Ni100 –200.0 to 600.0°C Pt50 –50.0 to 200.0°C Cu50 0.00 to 50.00mV DC voltage 50mV 0.0 to 500.0mV 500mV 1.000 to 5.000V 1-5V 0.000 to 5.000V 0-5V Note) B, R, S, K, E, J, T : JIS C 1602, DIN IEC 584-1 N : NICOSIL -NISIL (IEC 584) W : 5%Re-26%Re · W (Hoskins Mfg. Co. USA) L : Fe-Cu · Ni (DIN 43710) U : Cu-Cu · Ni (DIN 43710) PN: Platinum JPt100 : JIS C 1604-1989 (Old JIS Pt 100) Pt100, Pt50 : JIS C 1604, DIN IEC 751
EDS10-77e
Date Dec. 5, 2011
PHF
Selection of input types: By key operation on the front panel. Note that the same input type (thermocouple, resistance bulb, voltage) should be selected for channel 4 and 5. Refer to ”Setting method of input types” for details. Burn-out function: Equipped in thermocouple and resistance bulb inputs as standard, and overswings the recording to 100% side. Thermocouple burn-out current: approx. 0.2 µA Input filter function: Settable for each channel (primary delay filter) Time constants are settable in the range from 0 to 900 sec. Scaling function: ossible by DC voltage (current) input P Scaling range: -32767 to 32767 Decimal position: settable at any point Unit symbol: settable up to 7 digits and 125+12 types Subtraction function: Subtraction between each channel is allowed. Square rooter function: Square rooter can be performed against the input value per each channel. Ethernet log display: E-mail sending, FTP server log in/off and MODBUS TCP/IP communication start/ stop can be displayed. Parameter display/set: Already-set Data Display and Set Change Display screen TAG indication: Number. of characters to be displayed: Up to 8 characters at 6 channels on one screen or up to 16 (= 8 × 2) characters at 4 channels on one screen. Characters to be displayed: Alphanumerical characters Tag, unit and channel number display: It depends on the screen. See below table.
Screen Trend Bar graph Number of channel on one screen 4 or less more than 5 4 or less more than 5 TAG1 + x + x Items TAG2 unit ch number + + + x x + + + x x all items are displaed
Digital x: only 1 item can be displayed. +: only 2 items can be displayed.
Indication system
5.7” STN color LCD (320 x 240 dots) with backlight Note) The LCD may have some pixels that do not stay on or off. Due to the characteristics of liquid crystal, the brightness may not be uniform, which is not a failure. Color of indication: 14 colors Applicable language: English, French, German, Italian (switchable) Life of backlight: 50,000 hours (20°C) (the complete indicator unit should be replaced when replacing backlight). Trend display: Direction: vertical and horizontal Number of channels: 6 channels or 4 channels or 3 channels for the screen (Input: 6 points at the maximum). Display refreshment cycles: select from 1 second to 12 hours No numerical value display. Scale display/ no-display can be selected. Bar graph display: Direction: vertical Number of channels: 6 channels or 4 channels or 3 channels for the screen (Input: 6 points at the maximum). Display refreshment cycles: 1 second. Digital display: Number of channels: 6 channels or 4 channels or for the screen (Input: 6 points at the maximum). Display refreshment cycles: 1 second. Event summary display: Alarm summary and message summary can be displayed. Indicator:
Historical trend display: The past data can be displayed from the Compact Flash or internal memory. The past data file can be read and displayed with scroll display function or jump the cursor to the position which you entered date and time. Scale display/no-display can be selected. Number of screen groups: 1 group (Up to 6 channels per 1 group can be registered.)
Keyboard
No. of Keys: Function: 8 Use to select various screens and set various parameters.
Recording function
External memory media: Compact Flash card (Format as FAT32, FAT16 or FAT, or recorder can’t read and write.) Recording capacity: 2GB maximum (compact flash). Limiting the recording file to 64MB is recommended (for 112 hours if display refresh cycle is 1 second. See Table 1 (p. 6).) (When the size of the recording file comes to be 256MB or more, a new file is created automatically and recording is maintained.) * Please change the compact flash every six month to prevent the data losing. Recording method: Turning ON the REC key allows measured data to be written at fixed cycles. Recorded as a new file whenever the recording starts
2
Data save cycles: Linked to the display refreshment cycles on the “Trend display” screen. However, they are automatically set to about 1 minute if the refreshment cycles are set to less than 1 minute. Trend data: Average, instance or min. and max. measured values out of measured data that are sampled at the measuring cycles are saved. Event data: Saves alarm data and power ON data when the power turns off and on during recording. Storage capacity : Approximately 4 years when the display refresh cycle is 30 seconds (in the case of 6-channel recording in ASCII data format, and 512MB Compact Flash is used). Refer to Table 1. Memory usage: Indicates the memory which has already used on the screen. When all the memory is used up, you can stop recording or delete the oldest recording file to save the newest data. Compact flash card form: PHZP2801 (CF card) (If a card other than the above is used, no operation assurance is ensured. Meanwhile, as for other CF cards for which operation check will have been completed, the results will be posted on our company's homepage sequentially. Please refer to this website.) Data format: Either of ASCII or binary format can be selected. (Switching cannot be made while the recording is in progress. In the case of ASCII format, the data can be directly read on Excel, etc.) Note: The data recorded in binary format cannot be read directly. Approximately 118 bytes per sample (for 6-channel input in ASCII format) or approximately 28 bytes (for 6-channel input in binary format)
Power supply
Rated power voltage: 100 to 240V AC Range of operating voltage: 90 to 264V AC Supply frequency: 50/60Hz (both employable) Power consumption
100V AC 240V AC About 32VA About 42VA
Structure
Mounting method: Panel-mounted (vertical panel) Thickness of panel: 2 to 26 mm Materials: PC-ABS for case and bezel Color: Black External dimensions: Panel-mounted: 160 (W) × 144 (H) × 185 (D) mm Mass: Approx. 1.5 kg (no option) External terminal board: Screw terminals (M3 thread) RJ45 : Ethernet terminal (option)
Normal operating condition
Power voltage: 90 to 264V AC Supply frequency: 50/60 Hz ±2% (both employable) Ambient temperature: Panel-mounted 0 to 50°C (without Ethernet option*1) 0 to 40°C (with Ethernet option*2) Note) In case of 30°C or more of ambient temperature, this display might be fogged little bit (This is not out of order). Ambient humidity: 20 to 80%RH Vibration: 10 to 60Hz 0.2m/s2 or less Shock: None Magnetic field: 400 A/m or less Signal source resistance: Thermocouple input …. 1kΩ or less Resistance bulb input… 10Ω/wire or less (resistance of each wire of 3-wire system should be balanced). Voltage input… 0.1% or less of input resistance Mounting posture: Forward tilt 0°, backward tilt within 30°, horizontal 0° Warm-up time: One hour or more after power ON Environmental protection: IEC IP50 (Front)/20 (Terminal) Installation category: II Pollution degree: 2 Operating altitude: 2000m max. *1: In case of the 12th digit of ordering code is ”Y” . *2: In case of the 12th digit of ordering code is “E” .
Alarm function
No. of settings: Up to 4 alarms for each channel are settable. Type of alarm: High/Low limits Indication: Status (alarm types) is displayed on digital display unit when an alarm occurs. History display on alarm summary (Alarm start/cancel time and alarm types) Hysteresis: Set within the recording range of 0 to 100% (it is effective only in case of high/low limit alarm) Relay output: Number of points; 10 Alarm latch function: Keeps alarm indication and alarm output turning on after alarm reset. ON/OFF operation is performed according to key setting.
3
PHF
Safety and EMC standard
Safety standard: Based on IEC61010-1 EMC standard: Based on EN61326 Withstand voltage: Power terminal – ground: 2000V AC, 1 min Input terminal – ground: 500V AC, 1 min Alarm terminal – ground: 2000V AC, 1 min Alarm terminal – alarm terminal: 750V AC, 1 min Communication terminal – ground: 500V AC, 1 min
Transportation/storage conditions
Temperature: Humidity: Vibration: Shock: –10 to +60°C 5 to 90%RH, no condensation 10 to 60Hz, 2.45m/s2 or lower 294m/s2 or lower (packed state)
Effect on operation
Effect of power supply fluctuation conditions: For the fluctuation in the range from 90 to 264V AC (frequency: 50/60Hz) Reading change (100V AC base): ±(0.2%+1 digit) or lower. For the fluctuation in the range from 47 to 63Hz (power voltage: 100V AC) Reading change (50Hz base): ±(0.2%+1 digit) or lower. Effect of input signal resistance: Thermocouple input: (0.5µV/ Ω )+1 digit or less DC voltage: Fluctuation for resistance value equivalent to 0.1% of the input resistance: ±(0.2%+1 digit) or lower. Resistance bulb (for wiring resistance of 10Ω for 1 line (the same for 3 lines)) Reading change: ±(0.2%+1 digit) or lower. Effect of ambient temperature: Reading change: ±(0.3%+1 digit)/10°C or lower. Effect of Mounting position: For the backward 30° slant Reading change: ±(0.2%+1 digit) or lower. Effect of vibration: When sine wave of 10 to 60Hz with the acceleration of 0.2m/s 2 is applied in each direction for 2 hours. Reading change: ±(0.2%+1 digit) or lower. Effect of external noise: Normal mode noise (50, 60Hz±0.1Hz) …20dB or more Common mode noise (50, 60Hz±0.1Hz) …120dB or more (Thermocouple input: minus terminalground) (Resistance bulb input: b Line-ground)
Reference standard
Accuracy/resolution: Measuring conditions (23±2°C, 65±10% RH, power voltage, frequency fluctuation within ±1%, no external noise, warm-up time of 1 hour or more, vertical mounting, standard values of signal source resistance and wiring resistance... within 1% )
Input types Thermocouple B R S K E J T N W L U PN Resistance bulb Digital indication accuracy Note 1 ± (0.15%+1 digit) ±(0.3%+1 digit) for the range shown below Thermocouple B : 400 to 600°C Thermocouples R and S : 0 to 300C Thermocouples K, E, J, T, L and U : -200 to -100°C Digital indication resolution
0.1°C
JPt100 Pt100 ± (0.15%+1 digit) Pt50 0.1°C Ni100 Cu50 ± (0.5%+1 digit) DC voltage 50mV 10µV 500mV 100µV ± (0.15%+1 digit) 1-5V 1mV 0-5V 1mV Note 1) Digital indication accuracy is a percentage (%) of the value in the measuring range on page 1. Note 2) No error of reference contact compensation of thermocouple is included.
Error of reference contact compensation: K, E, J, T, N, L, U, PN: 0.5°C ± R, S, B, W: ±1.0°C (when measured at 0°C or more) Max. input voltage: Thermocouple, resistance bulb, DC voltage: ±10V DC (continuous) Input resistance: Thermocouple, DC voltage: About 1MΩ
Additional function (option) Others
With calendar function (Christian era) Accuracy: ±100ppm or less (monthly error: about 4 minutes) However, time error at ambient temperature 23±2°C and power ON/OFF is not included. Memory backup: Parameters are saved to the internal nonvolatile flash memory. The clock and totalized data are backed up with built-in lithium battery. Insulation resistance: 100 M Ω or more (when measured between each terminal and ground by using a 500V DC megger) Clock: ■ Alarm relay output/DI (11th digit of code symbols: “1”) A card with 10-point relay output and 5-point DI input can be mounted. Terminal structure: M3 screw terminal Alarm relay output: Contact output (SPST:10 points), Individual channel or common output (OR output) allowed. DO1: Contact capacity; 150V/3A AC, 30V/3A DC (resistive load) DO2-10: Contact capacity; 240/3A AC, 30V/3A DC (resistive load)
4
DI input:
No-voltage contact input (5 points) The following control is allowed by contact input. (1) Recording start/stop (2) LCD turns on (3) E-mail sending On pulse width: 200msec or longer Off pulse width: 200msec or longer
Ethernet (Option)
The following can be performed through the Ethernet function. ■ HTTP server (Internet Explorer 6 is compatible) Note 1 Measurement display: Digitally displays the measurement of each channel of the recorder and alarm occurrence status. Event summary display: Displays event summary including alarm ON/OFF. Main unit information display: Displays memory use conditions and information on the main unit such as the battery end warning. Integrated value display: Digitally displays the integrated value of each channel of the recorder. ■ FTP server (Internet Explorer 6 is compatible.) Note 1 File download: Record files stored in compact flash (CF) can be downloaded from the browser. File delete: Record files stored in CF can be deleted from the browser. Access authentication: Authenticates access authority to FTP server. ■ SMTP (e-mail client) Transmits e-mails to specified address under the following conditions. (1) When an alarm turns on or off (2) When DI is set to ON or OFF (3) When an error occurs to the main unit (such as low battery or no memory space) (4) At specified intervals ■ MODBUS TC/IP Data read: Settings can be read through MODBUS TCP/IP communication. Data write: Settings can be written through MODBUS TCP/IP communication. Note1: Neither Netscape nor Mozilla Firefox is available.
Required memory: 64MB or larger Disk drive: Windows 2000/XP-capable CD-ROM drive Hard disk capacity: Free capacity of 30MB or larger required Printer: Windows 2000/XP-capable printer and printer driver Note) PC loader communication cable (type PHZP1801) is separately required. ■ Data viewer software Major function: Regenerates the past trend record on the PC from the data in the Compact Flash. Provided with historical trend display and event display functions. O/S: Windows 2000/XP Required memory: 64MB or larger Disk drive: Windows 2000/XP-complaint CD-ROM drive Hard disk drive: Free capacity of 30MB or larger required Printer: Windows 2000/XP-capable printer and printer driver
Standard functions
Function Record range voluntary setting Input type setting Description Recording range can be set by channel. Input can be set by channel. (Key operation on the front face) The same input type is selected for channel 4 and 5. See “SELECTING INPUT TYPE” on the last page. Skips arbitrary channel display/recording. Time display: Time is displayed at the top of the trend display screen. Alarm display: On occurrence of an alarm and the restoration, alarm is displayed in the alarm display field. The Compact Flash usage is displayed at the top of the bargraph. By channel, Maximum of 8 characters. Displays the screen name (maximum of 16 characters). Industrial units can be arbitrarily created, Maximum of 7 digits, 12 types. Arbitrary scaling is allowed in the case of DC voltage input. Decimal point position can also be arbitrarily set in the range from -32767 to 32767 . Shift the zero point and slant of the reading. Prevents sudden fluctuation of input for each channel (primary delay filter). Time constant: 0 to 900 seconds. Displays the break of thermocouple/resistance bulb input by scaling out to 100% side. Regenerates and displays the data stored in the compact flash by scrolling the screen or jump to time when you entered.
Skip function Trend display
TAG name display Screen name display Unit creation Scaling function
PV shift Input filter
Burnout function Historical trend display
Support software
The following software is provided as standard. • PC/AT-compatible machine • Operation on PC98-series machines by NEC is not guaranteed. • Operation on self-made or shop-brand PCs is not guaranteed. ■ Loader software for PC Major function: Performs various parameter setting/change of the main unit O/S: Windows 2000/XP
5
PHF
Table 1. Recording capacity
Input point: 6 Data format: ASCII The recording can be made for the period of time listed in CompactFlash size 64MB the tables shown below. When the number of input points Display refreshment is 3, the period is approximately 1.6 times of min 10 min 1 sec 10 sec 30 sec 1 those listed cycle in the table. Recordable capacity In binary format, the period is approximately 4 times as long 159 hours 66 days 199 days 398 days 10.9 years (about) as those listed in the table.
CompactFlash size Display refreshment cycle Recordable capacity(about) 1 sec 256MB 10 sec 30 sec 1 min
ORDERING CODE
PHF
4 5 6 7 8 9 10 11 12 13 1B1 1-E 1 V
Digit Specifications Note 4 5 3 6 6 11 Without With 12 Without any communication With Ethernet communication
0 1 Y E
26 days 265 days 2.1 years 4.3 years
When Compact Flash is not used, up to 600K bytes of the recording data and the event data can be stored in the main unit. (In case of 6-channel in Max./Min. recording, approximately 21,000 data can be stored. For 5 hour at the display refresh cycle of 1 second. The number of the save data varies depending on the number of the event data.
STANDARD ACCESSORY
Item Recorder (PHF) Panel mounting bracket CD-ROM PC support software instruction manual Noise filter for the power supply Quantity Panel mounting 1 2 1 1
OPTIONAL ITEMS
Item Shunt resistor for DC current input PC loader communication cable CD-ROM with Instruction manual and 2 support software PC card adapter Compact Flash Code PHZP0101 PHZP1801 PHZP2101 Specification 10Ω ±0.1% With USB-A and USB miniB * 3m
PHZP0501 PHZP2801-512 PHZP2801-01G
For Compact Flash 512MB 1GB
* Shape of this cable is shown below USB (A) Plug – USB (Mini-B ) Plug
6
OUTLINE DIAGRAMS (Unit : mm)
PANEL MOUNTING
In the case of 3, 6-point input
Panel 2 T 26 T Mtg.bracket Ethernet terminal (Option) Digital input & alarm output (Option) Source terminal Input terminal
N
136.5 161
143.6
REC
DISP
SEL
ENT
160 21.6
140 185 136.5
(Note) When placing the main unit on another instrument or on the floor, allow a space of 100mm or more between the unit and instrument or the floor.
In the case of 3,6-point input
PANEL CUTOUT
Mounting one unit +1.5 137 0 Mounting n unit (160 × n-22) +2 0 n : Number of units to be mounted
137+1.5 0
Do not use the water proof packing in case of mounting n unit
EXTERNAL CONNECTION DIAGRAMS (M3 screw)
In the case of 3, 6-point input
Alarm (relay) output / digital Input terminal
211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 DI1 DI2 DI3 DI4 DI5 DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8 DO9 DO10 Voltage Thermocouple
137+1.5 0
Input terminal
Resistance bulb 11 12 13 CH4 41 42 43 RCJ Resistance Thermocouple Voltage bulb CH1
R-MODULE Rcj Fuji Electric
Source terminal
AC100 to 240V 50/60Hz
231 232 233 234 235 236 237 238 239 240 241 242 243 244 245
21 22 23
CH2
CH5
CH6
51 52 53 31 61 32 62 33 63
CH3
(Note1) (Note2)
For current input, connect an optional shunt resistance to a voltage input terminal. Do not use any input terminal which is not needed.
100∼240VAC
L
7
PHF
SELECTING INPUT TYPE
The input types of channel 4 and 5 is the same. Channel 5 can only be allocated the input type that is the same as channel 4. The following input types are available.
Input category Thermocouple, 50mV Resistance bulb 500mV 5V
Details K, E, J, T, R, S, B, N, W, L, U, and PN thermocouples, 50mV Pt100, JPt100, Ni100, Pt50, Cu50 500mV 1 to 5V, 0 to 5V
Note) Arbitrary input type can be selected for any channels other than channel 4 and 5 irrespective of the type allocated to other channels.
Example of channel input type selection
Input type Channel 1 Channel 2 Channel 3 Channel 4 Channel 5 Channel 6 K thermocouple 1-5V 500mV K thermocouple 50mV Pt100
Input category Thermocouple, 50mV 5V 500mV Thermocouple, 50mV Resistance bulb
Description
The input type of the thermocouple and 50mV is the same.
Note 1) Windows 2000/XP , Excel and Internet Explorer are the registered trademarks of Microsoft Corporation in the U.S.A. Note 2) Compact Flash is the registered trademark of Sandisk Corporation. Note 3) Modbus® is the trade mark or registered trade mark of AEG Schneider Automation International. Note 4) PC98 series are the trade mark or registered trade mark of NEC Corp. Note 5) Netscape is the trade mark or registered trade mark of Netscape Communication Corp. Note 6) Mozilla Firefox is the registered trade mark of Mozilla Foundation.
Caution on Safety *Before using this product, be sure to read its instruction manual in advance.
International Sales Div Sales Group Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome, Shinagawa-ku, Tokyo 141-0032, Japan http://www.fujielectric.com Phone: 81-3-5435-7280, 7281 Fax: 81-3-5435-7425 http://www.fjielectric.com/products/instruments/ Information in this catalog is subject to change without notice.