PAPERLESS RECORDER
DATA SHEET
PHU
OVERVIEW
This is a paperless recorder that displays measured data on the LCD in real time and stores data in CompactFlash. The type of input such as thermocouple, resistance bulb, D.C. voltage (current), etc. can be arbitrarily set to 36 channels at the maximum. The data stored in CompactFlash can be regenerated on the screen, and the use of supplied support software allows the data to be regenerated on a PC screen. The data recorded in ASCII format can be directly read in a spreadsheet such as Excel, which facilitates the processing on a PC. (The data recorded in binary format cannot be read in.)
FEATURES
1. Large capacity storage by CompactFlash Measured data is periodically stored in CompactFlash. In case of 512 MB, for example, display files for about 2 year and a half (display refresh cycle 30 sec) can be taken up (in case of ASCII data format, 9 channels, maximum/ minimum recording). 2. Quick search and display of past data Data stored in CompactFlash can be displayed in succession by scrolling the screen. 3. Various display capability Depending on the object of measurement, the most suitable display format can be selected from a variety of formats including bar graph display, trend display, digital display, etc. 4. PC support software supplied as standard Loader software that enables easy display and change of set data and data viewer software that regenerates the data stored in CompactFlash are supplied as standard. 5. 36-point recording 12 types of thermocouples, 2 types of resistance bulbs and DC voltage/current input can be recorded up to 36 points. 6. LCD extinguishing function Automatically extinguishes the LCD if nothing is operated for certain time. You can set the time after a lapse of which the LCD is extinguished via parameter "LCD extinguishing time". The settable range is 0 to 60 minutes. Setting at 0 minute overrides the function, whereby the LCD will never extinguish. This function prevents the backlight life from shortening uselessly. During the extinguishment, the power consumption can be reduced. 7. Ethernet function (Option) FTP Web server, e-mail and MODBUS-TCP are available , using 10Base-T.
SPECIFICATIONS
Input system
Number of input points: 9, 18, 27 or 36 points (Can be selected at the time of purchase) Input circuit: Input mutual isolation (See ”Others” on page 4 for the withstand voltage) Resistance bulb measured current: about. 1 mA Measuring cycles: 9 or 18 points….100ms cycles 27 or 36 points….200ms cycles Recording cycle: 1 second to 12 hours Input types: Thermocouple, resistance bulb, DC voltage, and DC current (Shunt resistors are fitted in input terminals). Note) Provide a shunt resistor (type: PHZP0101) separately. Measuring range
Input types B R S K E J T N W L U PN Resistance bulb JPt100 Pt100 Ni100 Pt50 Cu50 DC voltage Thermocouple Reference range 400.0 0.0 0.0 –200.0 –200.0 –200.0 –200.0 0.0 0.0 –200.0 –200.0 0.0 –200.0 –200.0 –60.0 –200.0 –50.0 to 1760.0°C to 1760.0°C to 1760.0°C to 1370.0°C to 800.0°C to 1100.0°C to 400.0°C to 1300.0°C to 1760.0°C to 900.0°C to 400.0°C to 1300.0°C to 600.0°C to 600.0°C to 180.0°C to 600.0°C to 200.0°C to 50.00mV to 500.0mV to 5.000V to 5.000V U : Cu-Cu · Ni (DIN 43710) PN: Platinel JPt100 : JIS C 1604-1989 (Old JIS Pt 100) Pt100, Pt50 : JIS 1604, DIN IEC 751
0.00 50mV 0.0 500mV 1.000 1-5V 0.000 0-5V Note) B, R, S, K, E, J, T, N : JIS C 1602, DIN IEC 584-1 W : 5%Re-26%Re · W (Hoskins Mfg. Co. USA) L : Fe-Cu · Ni (DIN 43710)
EDS10-79c
Date Dec. 5, 2011
PHU
Selection of input types: By key operation on the front panel. Note that the same input type (thermocouple, resistance bulb, voltage) should be set every 2 channels. Refer to "Setting method of input types" for details. Burn-out function: Provided as standard for thermocouple and resistance bulb inputs. If the input has been open-circuited, the recording level swings over 100%. Thermocouple burn-out current: approx. 0.2 µA Input filter function: Settable for each channel (primary delay filter) Time constants are settable in the range from 0 to 900 sec. Scaling function: ossible by DC voltage (current) input P Scaling range: -32767 to 32767 Decimal position: settable at any point Unit symbol: Selectable out of 125 different units or 12 user units of up to 7 characters. Subtraction function: S ubtraction between each channel is allowed. Totalizing function: The measured value of each channel can be totalized. Applicable to daily, monthly, annual or external input totalizing. F value calculation function: F value (extinction value of bacteria by sterilization by heating) can be calculated from the measured temperature by each channel. Square rooter function: Square rooter can be performed against the input value per each channel. Computation function: The following calculation is available with the computation function. (1) Computation function: Addition, subtraction, multiplication, division, absolute value, exponential, square-root extraction, LOG, LN, EXP , humidity, maximum, minimum, average, and integration. (2) Computation input enable: Analog input (Ch1 to 72), integration input (Ch1 to 72), DI (DI1 to 16), communication input (No.1 to 36), and constant number (No.1 to 60). Color of indication: 14 colors Applicable language: English, French (switchable) Life of backlight: 50,000 hours in terms of total lighting time. (Replace the backlight as a set of display unit. If the LCD extinguishing function is resorted to, the LCD can be used longer as much.) Trend display: Direction: vertical and horizontal Number of channels: 10, 6 or 4 channels per screen group. (Input: 72 points at the maximum). Display refreshment cycles: select from 1 second to 12 hours Scale display or no-display can be selected. Bar graph display: Number of channels: 10, 6 or 4 channels per screen group. (Input: 72 points at the maximum). Display refreshment cycles: 1 second Analog meter display: Number of channels: 10, 6 or 4 channels per screen group. Display in bar graphs or in analog meters can be selected. Display refresh cycle: 1 second Digital display: Number of channels: 10, 6 or 4 channels per screen group. (Input: 72 points at the maximum). Display refreshment cycles: 1 second Totalizing data display: Number of channels: 10, 6 or 4 channels per screen group. (Input: 72 points at the maximum). Display refresh cycle: 1 second Event summary display: Alarm summary and message summary can be displayed. The message occurrence information and message display can be switched. Ethernet log display: E-mail sending, FTP server log in/off and MODBUS TCP/IP communication start/ stop can be displayed. Parameter display/set: Already-set Data Display and Set Change Display screen TAG indication: Number of characters to be displayed: Up to 8 characters Up to 8 characters (Note 1) at 10 or 6 channel display. Up to 16 characters at 4 channel display. Note 1: Up to 7 characters only can be displayed on certain screens. Characters to be displayed: Alphanumerics Tag , unit and channel No. display: Which can be displayed depends on the particular screen. Refer to the table below. (Keywords only are extracted.)
Indication system
Indicator: 12” TFT color LCD (800 x 600 dots) with backlight, no contrast adjustment. On the LCD, certain picture elements remain lit or extinguished. On account of the nature inherent to LCD, the brightness may be non-uniform. But, such are not troubles.
2
Screen Trend Bar graph
Channnels per screen 4 or less 5, 6 7 or more 6 or less 7 or more
Tag 1
Analog meter Instantaneous value : Displayed : 1 item only can be displayed – : Nothing can be displayed
Item Tag 2 Unit All – – All – All
ch Np.
Historical trend display: Displays past recording data read from compact flash, currently recording data or just recorded data. The recording chart can be scrolled or, via time designation, the control can jump to an arbitrary recording chart. Number of screen groups: 8 groups (Up to 10 channels per 1 group can be registered.)
Keyboard
No. of Keys: Function: 8 Use to select various screens and set various parameters.
Recording function
External memory media: Compact Flash card Format according to FAT16 or FAT. Otherwise, reading and saving are impossible. Recording capacity: 1 GB maximum (compact flash). Limiting the recording file to 64 MB is recommended (for 112 hours if display refresh cycle is 1 second. See Table 1 (p. 6).) If impossible, up to 256 MB is tolerated. A file recorded beyond could not be opened. * Please change the compact flash every six month to prevent the data losing. Recording method: Turning ON the REC key allows measured data to be written at fixed cycles. Recorded as a new file whenever the recording starts. Data save cycles: Linked to the display refreshment cycles on the ”Real Time Trend” screen. However, they are automatically set to about 1 minute if the refreshment cycles are set to less than 1 minute. Trend data: Measurement data sampled at measurement cycle is saved in terms of mean value, instantaneous value or maximum/minimum value. Event data: Saves alarm data and message data. Further saves power ON and OFF, if any, after starting recording.
Totalizing value data: Tot alizing value dat a at designat ed timing is recorded per channel. Totalized value data at designated totalized value recording cycle or the sum total is recorded in the totalizing file. You can choose which type you want to record. For each cahnnel. it can be select as totalizing action from Analog input totalization, Digital input count or period of Digital input ON, and it can be select as totalizing period type from Dairy, Weekly, Monthly, Annual, Periodic, Dairy (time set) or External input signal. Even if a power failure occues during totalization and then the power is restored,the totalization restarts from the value before power failure. Configuration data: Configuration data can be saved. And this data can also download to recorder. Storage capacity : Approximately 3 years when the display refresh cycle is 30 seconds (in case of 9-channel recording in ASCII data format, and 512 MB compact flash used). Refer to Table 1. Residual capacity of memory: Indicates how much of the memory card has been used on the screen. If the residual capacity is none, the recording stops. Compact flash card form: PHZP2801 (CF card) (If a card other than the above is used, no operation assurance is ensured. Meanwhile, as for other CF cards for which operation check will have been completed, the results will be posted on our company's homepage sequentially. Please refer to this website.) Data format: Either of ASCII or binary format can be selected. (Switching cannot be made while the recording is in progress. In the case of ASCII format, the data can be directly read on Excel, etc. The data recorded in binary format cannot be read directly.) Approximately 166 bytes per sampling for maximum/minimum recording of 9-channel input in ASCII format, or approximately 40 bytes for maximum/ minimum recording of 9-channel input in binary format.
Alarm function
No. of settings: Up to 4 alarms for each channel are settable. Type of alarm: High/Low limits Indication: Status (alarm types) is displayed on digital display unit when an alarm occurs. Historical display on alarm summary (Alarm start/cancel time and alarm types)
3
PHU
Set within the recording range of 0 to 100% Acts on high or low limit alarm, and does not affect the battery alarm nor memory full alarm. Relay output: Number of points; 20 (option: Up to 2 cards with relay output can be mounted.) Transistor output (open collector output): 16 points (option) Alarm latch function: Holds alarm indication and alarm output even after measurement value has left the alarm range. ON/OFF operation is performed according to key setting. Hysteresis: Signal source resistance: Thermocouple input .… 1kΩ or less Resistance bulb input .… 10Ω/wire or less (resistance of each wire of 3-wire system should be balanced). Voltage input .… 0.1% or less of input resistance Mounting posture: Forward tilt 0, backward tilt within 30, horizontal 0 Warm-up time: One hour or more after power ON *1: In case of the 12th digit of ordering code is ”Y” . *2: In case of the 12th digit of ordering code is ”E” .
Reference standard
Accuracy/resolution: Measuring conditions (23±2˚C, 65±10% RH, power voltage, frequency fluctuation within ±1%, no external noise, warm-up time of 1 hour or more, vertical mounting, standard values of signal source resistance and wiring resistance... within 1% )
Input types Thermocouple B R S K E J T N W L U PN Resistance JPt100 bulb Pt100 Pt50 Digital indication accuracy Note 1 ±(0.15%+1 digit) ±(0.3%+1 digit) for the range shown below Thermocouple B : 400 to 600°C Thermocouples R and S : 0 to 300°C Thermocouples K, E, J, T, L and U : -200 to -100°C Digital indication resolution
Power supply
Rated power voltage: 100 to 240V AC Range of operating voltage: 90 to 264V AC Supply frequency: 50/60Hz ±2% (both employable) Power consumption
Power voltage Consumption About 65VA About 80VA
100V AC 240V AC
Structure
Mounting method: Panel-mounted (vertical panel) Thickness of panel: 2 to 26 mm Materials: Stainless steel for case, PC-ABS for bezel Color: Silver for case, Munsell N2.0 (black) for bezel External dimensions: 300 (W) × 300 (H) × 220.5 (D) mm Mass: About 4.7 kg (9-point input, without option) About 6.4 kg (full option) External terminal board: Input terminal: M3 screw terminal Power terminal: M4 screw terminal
0.1°C
±(0.15%+1 digit) 0.1°C
DC voltage
Ni100 ±(0.5%+1 digit) Cu50 50mV 500mV ±(0.15%+1 digit) 5V
10V 100V 1mV
Note 1) Digital indication accuracy is a percentage (%) with respect to input range of 1 page. Note 2) No error of reference contact compensation of thermocouple is included.
Operating condition
Power supply voltage: 90 to 264V AC Power supply frequency: 50/60Hz ±2% (sharing) Ambient temperature: W ithout Ethernet function: 0 to 50°C*1 W ith Ethernet function: 0 to 40°C*2 Ambient humidity: 20 to 80%RH Vibration: 10 to 60Hz 0.2m/s2 or less Shock: None Magnetic field: 400 A/m or less
Error of reference contact compensation: K, E, J, T, N, L, U, PN: ±0.5˚C R, S, B, W: ±1.0˚C (when measured at 0˚C or more) Max. input voltage: Thermocouple, resistance bulb, DC voltage: ±10V DC (continuous) Input impedance: Thermocouple, DC voltage: About 1MΩ
Others
Clock: With calendar function (Christian era) Accuracy: ±50 ppm or less (monthly error: about 2 minutes) However, time error at power ON/OFF is not included.
4
Memory backup: Parameters are saved to the internal non-volatile flash memory. The clock is backed up with built-in lithium battery. Trend data is not backed up. Insulation resistance: 100 MΩ (when measured between each terminal and ground by using a 500V DC megger) Withstand voltage: Input terminal – input terminal: 500 V AC, 1 min Power terminal – ground: 2000V AC, 1 min Input terminal – ground:500V AC, 1 min Alarm terminal (cont act output) – ground: 2000 V AC, 1 min Alarm terminal (contact output) – alarm terminal (contact output): 750 V AC, 1 min Communication terminal – ground: 500 V AC, 1 min Alarm terminal (open co ll e c t o r ) – ground: 500 V AC, 1 min Power terminal – input terminal: 500 V AC, 1 min
Vibration: Shock:
10 to 60Hz, 2.45 m/s2 or lower 294m/s2 or lower (packed state)
Additional function (option)
■ Alarm relay output (11th digit of code symbols: ”1” , ”2” , ”4” or ”5”) Up to 2 cards with 10-point relay output can be mounted. (Maximum 20 points) Terminal structure: M3 screw terminal Alarm relay output: 1a contact output (10 points/card), Individual channel or common output (OR output) allowed. Rating: Contact capacity 240V AC/3A, 30V DC/3A (Resistive load). ■ Alarm open collector output (11 digit of code symbols is ”3” , ”4” or ”5”) Card having 16 alarm points (open collector output) can be mounted. Terminal structure: M3 screw terminal Alarm output: Open-collector transistor output (16 points) Rating: 30V DC/0.1A (resistance load) ■ DI input (7 digits of code symbol is ”1”) Card having 16 DI input can be mounted. Terminal structure: M3 screw terminal DI input: No-voltage contact input (16 points). Contact input allows following controls. (1) Recording start/stop (2) Message set (3) F value calculation reset (4) Totalizing start/stop (5) Totalized value reset (6) LCD (backlight) lighting (7) E-mail sending Input pulse width: ON pulse width: 400msec or more OFF pulse width: 400msec or more
Effect on operation
Effect of power supply fluctuation conditions: For the fluctuation in the range from 90 to 264V AC (frequeucy: 50/60Hz) Reading change: ±(0.2%+1 digit) or lower. For the fluctuation in the range from 47 to 63Hz (power voltage: 100V AC) Reading change: ±(0.2%+1 digit) or lower. Effect of input signal resistance: Thermocouple input: 50 µ V ± 1 digit per 100Ω D C voltage: Fluctuation for resistance value equivalent to 0.1% of the input resistance: ±(0.2%+1 digit) or lower. Reistance bulb (for wiring resistance of 10Ω for 1 line (the same for 3 lines)) Reading change: ±(0.2%+1 digit) or lower. Effect of ambient temperature: Reading change: ±(0.3%+1 digit)/10˚C or lower. Effect of Mounting position: For the backward 30˚ slant Reading change: ±(0.2%+1 digit) or lower. Effect of vibration: When sine wave of 10 to 60Hz with the acceleration of 0.2m/s 2 is applied in each direction for 2 hours. Reading change: ±(0.2%+1 digit) or lower.
Ethernet (Option)
The following can be performed through the Ethernet function. ■ HTTP server (Internet Explorer 6 is available) Note 1 Measurement display: Digitally displays the measurement of each channel of the recorder and alarm occurrence status. Event summary display: Displays event summary including alarm ON/OFF and issuance of messages. Main unit information display: Displays memory use conditions and information on the main unit such as the battery end warning. Integrated value display: Digitally displays the integrated value of each channel of the recorder. ■ FTP server (Internet Explorer 6 available.) Note 1 File download: Record files stored in compact flash (CF) can be downloaded from the browser.
Safety and EMC standard
Safety standard: Based on IEC61010-1 EMC standard: Based on EN61326
Transportation/storage conditions
Temperature: Humidity: -10 to +60˚C 5 to 90%RH
5
PHU
Record files stored in CF can be deleted from the browser. Access authentication: Authenticates access authority to FTP server. ■ SMTP (e-mail client) Transmits e-mails to specified address under the following conditions. (1) When an alarm turns on or off (2) When DI is set to ON or OFF (3) When an error occurs to the main unit (such as low battery or no memory space) (4) At specified intervals ■ MODBUS TC/IP Data read: Settings can be read through MODBUS TCP/IP communication. Data write: Settings can be written through MODBUS TCP/IP communication. Note1: Neither Netscape nor Mozilla Firefox are available. File delete:
Standard functions
Function Record range voluntary setting Input type setting Description Recording range can be set by channel. Input type can be set by channel. (Key operation on the front face) Set the same input type for every 2 channels. Skips arbitrary channel display/recording. Time display: Time is displayed at the top of the trend display screen. Alarm display: On occurrence of an alarm and the restoration, alarm is displayed in the alarm display field. The compact flash usage is displayed with a bargraph at the top. By channel, Maximum of 8 characters. Displays the screen name (maximum of 16 characters). Industrial units can be arbitrarily created, Maximum of 7 digits, 12 types. Arbitrary scaling is allowed in the case of DC voltage input. Decimal point position can also be arbitrarily set in the range from -32767 to 32767 . Shift the zero point and slant of the reading. Prevents sudden fluctuation of input for each channel (primary delay filter). Time constant: 0 to 900 seconds. Displays the break of thermocouple/resistance bulb input by scaling out to 100% side. Regenerates and displays the data stored in the compact flash by scrolling the screen. Displays data of a designated time.
Skip function Trend display
TAG name display Screen name display Unit creation Scaling function
PV shift Input filter
Support software
The following software is provided as standard. • Applicable PC: PC/AT-compatible machine • Operation on PC98-series machines by NEC is not guaranteed. • Operation on self-made or shop-brand PCs is not guaranteed. ■ Loader software for PC Major function: Performs various parameter setting/ change of the main unit O/S: Windows 2000/XP (Windows Vista is not supported.) Required memory: 64MB or larger Disk drive: Windows 2000/XP-capable CD-ROM Hard disk capacity: Free capacity of 30MB or larger required Printer: Windows 2000/XP-capable printer and printer driver Note) PC loader communication cable (type PHZP1801) is separately required. ■ Data viewer software Major function: Regenerates the past trend record on the PC from the data in the compact flash. Provided with historical trend display and event display functions. Data can be changed to CSV file. O/S: Windows 2000/XP (Windows Vista is not supported.) Required memory: 64MB or larger Disk drive: Windows 2000/XP-capable CD-ROM drive Hard disk drive: Free capacity of 30MB or larger required Printer: Windows 2000/XP-capable printer and printer driver
Burnout function Historical trend display
Table 1. Recording capacity
The recording can be made for the period of time listed in the tables shown below under the following conditions. CompactFlash size 64MB • 9 input points Display upgrade cycle 1 sec 10 sec 30 sec 1 min 10 min • Recording data format: ASCII Recordable capacity Maximum/minimum recording • Recording type: 112 hours 46 days 140 days 280 days 7.7 years (about) • No alarm, nor message, nor other events.
CompactFlash size Display upgrade cycle Recordable capacity(about) 1 sec 256MB 10 sec 30 sec 1 min
18 days 187 days 1.5 years 3 years
• When the number of input points goes on increasing, the period becomes as follows. 18 input points; The period is approximately one half of those listed in the table. 27 input points; The period is approximately one-third of those listed in the table. 36 input points; The period is approximately one-fourth of those listed in the table. • In binary format, the period is approximately 4 times as long as those listed in the table. • For recording type of mean or instantaneous value, the number of days is approximately 2 times as long. When compact flash is not used, up to 6M bytes of the recording data and the event data can be stored in the main unit. (In case of 32-channel in Max./Min. recording, approximately 400,000 data can be stored. For 11 hours at the display refresh cycle of 1 second. The number of the save data varies depending on the number of the event data.
6
CODE SYMBOLS
PHU
4 5 6 7 8 9 10 11 12 13 00 11 Y
Digit Specifications Note 4 1 9 points 2 18 points 3 27 points 4 36 points 7 Without With (16 points) 8 9 English 11 Without 10 relay points 20 relay points Transistor (open collector) 16 points 10 relay points + transistor (open collector) 16 points 20 relay points + transistor (open collector) 16 points 12 Without With
0 1 1 E 0 1 2 3 4 5 Y E
SCOPE OF DELIVIRY
Item Recorder Panel mounting bracket CD-ROM PC support software instruction manual Noise filter for the power supply Quantity 1 2 1 1
OPTIONAL ITEMS
Item Shunt resistor for DC current input PC loader communication cable Code PHZP0101 PHZP1801 Specification 10Ω ± 0.1% Length 3m with connector USB-A/USB miniB terminal *
CD-ROM with instruction PHZP2501 manual and support software PC card adapter Compact flash PHZP0501 PHZP2801-512 PHZP2801-01G For compact flash 512MB 1GB
* Shape of this cable is shown below USB (A) male – USB (Mini-B ) male
B
7
PHU
OUTLINE DIAGRAMS (Unit : mm)
PANEL MOUNTING TYPE In the case of 9-point input
Panel
220.5 300 26 175
Alarm output transistor terminal Alarm output relay terminal
Ethernet terminal (option) DI input terminal Power terminal
100-240VAC?`
L
DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8 DO9 DO10 DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8 DO9 DO10
N
DO1-10 ?iRY?j
DO11 DO12 DO13 DO14 DO15 DO16 DO17 DO18 DO19 DO20 DO11 DO12 DO13 DO14 DO15 DO16 DO17 DO18 DO19 DO20
DO11-20 ?iRY?j
VPD
DO21 DO22 DO23 DO24 DO25 DO26 DO27 DO28 PCD DO29 DO30 DO31 DO32 DO33 DO34 DO35 DO36 PCD
DI 0V DI 0V
DI1 DI9
DI2
DI3
DI4
DI5
DI6
DI7
DI8
DI 0V DI 0V
300
VPD
DI10
DI11
DI12
DI13
DI14
DI15
DI16
280
DO21-36 ?iTr?j
DI1-16
CH1-CH9
LAN Communicator
+ TC?^V + TC?^V LOWER ‰º’i 16 17
1 2
CH1
3
+ TC?^V
4
CH2
5 6
+ TC?^V 7 8
CH3 RCJ
9
+ TC?^V 10
CH4
12
+ TC?^V 13
CH6
18
+ TC?^V 19 20
CH7
21
+ TC?^V 22 23
11
CH8
24
+ TC?^V 25
14
CH5 UPPER 15 ã’i CH9
27
26
PUSH
t 2 ≤ t ≤ 26 Mounting bracket
Input terminal (1 to 9 points)
In the case of 18-point input
Panel
220.5 300 26 175
Alarm output transistor terminal Alarm output relay terminal
DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8 DO9 DO10 DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8 DO9 DO10
DO1-10 ?iRY?j
DO11 DO12 DO13 DO14 DO15 DO16 DO17 DO18 DO19 DO20 DO11 DO12 DO13 DO14 DO15 DO16 DO17 DO18 DO19 DO20
DO11-20 ?iRY?j
VPD
DO21 DO22 DO23 DO24 DO25 DO26 DO27 DO28 PCD DO29 DO30 DO31 DO32 DO33 DO34 DO35 DO36 PCD
300
VPD
280
DO21-36 ?iTr?j
CH1-CH9
+ TC?^V + TC?^V LOWER ‰º’i 16 17
1 2
CH1
3
+ TC?^V
4
CH2
5 6
+ TC?^V 7 8
CH6
18
+ TC?^V 19 20
CH7
21
PUSH
t 2 ≤ t ≤ 26 Mounting bracket Input terminal (1 to 9 points)
280 318
Input terminal (10 to 18 points)
8
R-MODULE Rcj
R-MODULE Rcj
280 318
Ethernet terminal (option) DI input terminal Power terminal
100-240VAC?`
L N
DI 0V DI 0V
DI1 DI9
DI2
DI3
DI4
DI5
DI6
DI7
DI8
DI 0V DI 0V
DI10
DI11
DI12
DI13
DI14
DI15
DI16
DI1-16
LAN Communicator
CH10-CH18
CH3 RCJ
9
+ TC?^V 10
CH4
12
+ TC?^V 13
+ TC?^V 22 23
11
CH8
24
+ TC?^V 25
14
CH5 UPPER 15 ã’i CH9
27
+ TC?^V + TC?^V LOWER ‰º’i 43 44
28 29
CH10 + TC?^V 30
CH11
33
+ TC?^V 34 35
CH12 + TC?^V RCJ
36 37
CH13 + TC?^V 39
CH15 + TC?^V 45 46 47
31
32
CH16
48
+ TC?^V 49 50
38
CH17 + TC?^V 51 52
40
41
CH14 UPPER 42 ã’i CH18
54
26
53
R-MODULE Rcj
In the case of 27-point input
Panel Alarm output transistor terminal
220.5 300 26 175
Ethernet terminal (option) DI input terminal Power terminal
100-240VAC?`
Alarm output relay terminal
L
DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8 DO9 DO10 DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8 DO9 DO10
N
DO1-10 ?iRY?j
DO11 DO12 DO13 DO14 DO15 DO16 DO17 DO18 DO19 DO20 DO11 DO12 DO13 DO14 DO15 DO16 DO17 DO18 DO19 DO20
DO11-20 ?iRY?j
VPD
DO21 DO22 DO23 DO24 DO25 DO26 DO27 DO28 PCD DO29 DO30 DO31 DO32 DO33 DO34 DO35 DO36 PCD
DI 0V DI 0V
DI1 DI9
DI2
DI3
DI4
DI5
DI6
DI7
DI8
DI 0V DI 0V
300
VPD
DI10
DI11
DI12
DI13
DI14
DI15
DI16
280
DO21-36 ?iTr?j
DI1-16
CH1-CH9
LAN Communicator
CH10-CH18
+ TC?^V + TC?^V LOWER ‰º’i 16 17
1 2
CH1
3
+ TC?^V
4
CH2
5 6
+ TC?^V 7 8
CH3 RCJ
9
+ TC?^V 10
CH4
12
+ TC?^V 13
CH6
18
+ TC?^V 19 20
CH7
21
+ TC?^V 22 23
11
CH8
24
+ TC?^V 25
14
CH5 UPPER 15 ã’i CH9
27
+ TC?^V + TC?^V LOWER ‰º’i 43 44
28 29
CH10 + TC?^V 30
CH11
33
+ TC?^V 34 35
CH12 + TC?^V RCJ
36 37
CH13 + TC?^V 39
CH15 + TC?^V 45 46 47
31
32
CH16
48
+ TC?^V 49 50
38
CH17 + TC?^V 51 52
40
41
CH14 UPPER 42 ã’i CH18
54
26
53
CH19-CH27
+ TC?^V + TC?^V LOWER ‰º’i 43 44
28 29
CH10 + TC?^V 30
CH11
33
+ TC?^V 34 35
CH12 + TC?^V RCJ
36 37
CH13 + TC?^V 39
PUSH
CH15 + TC?^V 45 46 47
31
32
CH16
48
+ TC?^V 49 50
38
CH17 + TC?^V 51 52
40
41
CH14 UPPER 42 ã’i CH18
54
53
t 2 ≤ t ≤ 26
Mounting bracket Input terminal (1 to 9 points)
280 318
Input terminal (10 to 18 points) Input terminal (19 to 27 points)
In the case of 36-point input
Panel Alarm output transistor terminal
220.5 300 26 175
Ethernet terminal (option) DI input terminal Power terminal
100-240VAC?`
Alarm output relay terminal
DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8 DO9 DO10 DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8 DO9 DO10
DO1-10 ?iRY?j
DO11 DO12 DO13 DO14 DO15 DO16 DO17 DO18 DO19 DO20 DO11 DO12 DO13 DO14 DO15 DO16 DO17 DO18 DO19 DO20
DO11-20 ?iRY?j
VPD
DO21 DO22 DO23 DO24 DO25 DO26 DO27 DO28 PCD DO29 DO30 DO31 DO32 DO33 DO34 DO35 DO36 PCD
DI 0V DI 0V
DI1 DI9
DI2
DI3
DI4
300
VPD
DI10
DI11
DI12
280
DO21-36 ?iTr?j
CH1-CH9
LAN Communicator
CH10-CH18
+ TC?^V + TC?^V LOWER ‰º’i 16 17
1 2
CH1
3
+ TC?^V
4
CH2
5 6
+ TC?^V 7 8
CH3 RCJ
9
+ TC?^V 10
CH4
12
+ TC?^V 13
CH6
18
+ TC?^V 19 20
CH7
21
+ TC?^V 22 23
11
CH8
24
+ TC?^V 25
14
CH5 UPPER 15 ã’i CH9
27
+ TC?^V + TC?^V LOWER ‰º’i 43 44
28 29
CH10 + TC?^V 30
CH11
33
+ TC?^V 34 35
CH15 + TC?^V 45 46 47
31
32
CH16
48
26
CH19-CH27
CH28-CH36
+ TC?^V + TC?^V LOWER ‰º’i 43 44
28 29
CH10 + TC?^V 30
CH11
33
+ TC?^V 34 35
CH12 + TC?^V RCJ
36 37
CH13 + TC?^V 39
PUSH
CH15 + TC?^V 45 46 47
31
32
CH16
48
+ TC?^V 49 50
38
CH17 + TC?^V 51 52
40
41
CH14 UPPER 42 ã’i CH18
54
+ TC?^V + TC?^V LOWER ‰º’i 97 98
82 83
CH28 + TC?^V 84
CH29 + TC?^V 87
CH33 + TC?^V 99 100 101
85
86
CH34
102
88
53
t 2 ≤ t ≤ 26
Mounting bracket Input terminal (1 to 9 points)
280 318
Input terminal (10 to 18 points) Input terminal (28 to 36 points) Input terminal (19 to 27 points)
PANEL CUTOUT SIzE
360 MIN
+2 281 0
320 MIN
281
+2 0
R-MODULE Rcj
R-MODULE Rcj
R-MODULE Rcj
R-MODULE Rcj R-MODULE Rcj R-MODULE Rcj R-MODULE Rcj
L N
DI5
DI6
DI7
DI8
DI 0V DI 0V
DI13
DI14
DI15
DI16
DI1-16
CH12 + TC?^V RCJ
36 37
CH13 + TC?^V 39
+ TC?^V 49 50
38
CH17 + TC?^V 51 52
40
41
CH14 UPPER 42 ã’i CH18
54
53
CH30 + TC?^V RCJ
90 91
CH31 + TC?^V 93
89
+ TC?^V 103 104
92
CH35 + TC?^V 105 106
94
95
CH32 UPPER 96 ã’i CH36
108
107
9
PHU
EXTERNAL CONNECTION DIAGRAMS
Alarm output relay terminal M3 screw
DO1 1 DO2 2 11 DO3 3 12 DO4 4 13 DO5 5 14 DO6 6 15 DO7 7 16 DO8 8 17 DO9 9 18 DO10 10 19 20
Power terminal M4 screw
100 to 240V AC 50/60Hz
Alarm output relay terminal M3 screw
DO11 21 DO12 DO13 DO14 DO15 DO16 DO17 DO18 DO19 DO20 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
Alarm output transistor terminal M3 screw
VPD 41 DO21 DO22 DO23 DO24 DO25 DO26 DO27 DO28 PCD 45 46 47 48 49 50 43 44 42 24V DC+ DO29 DO30 DO31 DO32 DO33 DO34 DO35 DO36 0V 51 52 53 54 55 56 57 58 59 60 DI 0V 61 DI1 62 DI9 71 72 DI2 63
DI input terminal M3 screw
DI6 DI7 DI8 DI 0V DI3 DI4 DI5 70 64 65 66 67 68 69 DI10 DI11 DI12 DI13 DI14 DI15 DI16 73 74 75 76 77 78 79 80
Input terminal Number of input points = 1 to 9 points
CH1 CH2 CH3 CH4 CH5
M3 screw
Number of input points = 10 to 18 points
CH10 CH11 CH12 CH13 CH14
Voltage + Thermocouple + Resistance bulb
1
-
+ +
-
+ +
-
+ +
-
+ +
-
Voltage + Thermocouple + Resistance bulb
-
+ +
-
+ +
-
+ +
-
+ +
-
2
3
4
5
6
7
8
9 10 11 12 13 14 15 22 23 24 25 26 27
28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54
16 17 18 19 20 21
Resistance bulb Thermocouple + Voltage + CH6
RCJ
Resistance bulb + + CH8
RCJ
+ +
CH7
+ +
CH9
Thermocouple + Voltage +
-
+ +
-
+ +
CH17
+ +
CH18
CH15
CH16
Number of input points = 19 to 27 points
CH19 CH20 CH21 CH22 CH23
Number of input points = 28 to 36 points
CH28 CH29 CH30 CH31 CH32
Voltage
+
-
+ +
-
+ +
-
+ +
-
+ +
-
Voltage
+
-
+ +
-
+ +
-
+ +
-
+ +
-
Thermocouple + Resistance bulb
Thermocouple + Resistance bulb
55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81
82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100101 102 103104105106107108
Resistance bulb Thermocouple + Voltage + + + -
RCJ
Resistance bulb + + + + Thermocouple + Voltage + + + -
RCJ
+ +
CH35
+ +
CH36
CH24
CH25
CH26
CH27
CH33
CH34
Note) For current input, connect an optional shunt resistance to a voltage input terminal.
10
SELECTING INPUT TYPE
The input type is the same every 2 channels. The input type of channel 2, 4, 6, 8, 11, 13, 15, 17, 20, 22, 24, 26, 29, 31, 33 and 35 can only be set in the same category of previous channel. Note, however, that input type can be arbitrarily selected only for channels 9, 18, 27 and 36 irrespective of the type allocated to other channels. The following input types are available.
Input type Thermocouple, 50mV
Details K, E, J, T, R, S, B, N, W, L, U, and PN thermocouples, 50mV Pt100, JPt100, Ni100, Pt50 and Cu50 500mV 1 to 5V, 0 to 5V
Resistance bulb 500mV 5V
Example of channel input type selection (for 18 points input)
Input type Channel 1 Channel 2 Channel 3 Channel 4 Channel 5 Channel 6 Channel 7 Channel 8
Input type Thermocouple, 50mV 5V Resistance bulb 500mV Thermocouple, 50mV Thermocouple, 50mV 5V Resistance bulb 500mV Thermocouple, 50mV
Description The type of thermocouple can be arbitrarily selected for each channel.
K thermocouple T thermocouple 1-5V 0-5V Pt100 JPt100 500mV 500mV J thermocouple K thermocouple 50mV Skip 1-5V Pt100 Skip Other channels 500mV 50mV
The type of resistance bulb can be arbitrarily selected for each channel.
Channel 9 Channel 10 Channel 11 Channel 12 Channel 13 Channel 14 Channel 15 Channel 16 Channel 17 Channel 18
Input type can be arbitrarily selected for channel 9. The input type of the thermocouple and 50mV is the same. Skip and other channel can arbitrarily be selected irrespective of the input type.
Input type can be arbitrarily selected for channel 18.
Note 1) Windows2000/XP Excel, and Internet Explorer are the trademarks or registered trademarks of Microsoft Corpora, tion in the U.S. Note 2) CompactFlash is the trademark or registered trademark of Sandisk Corporation. Note 3) Modbus is the trademark or registered trademark of AEG Schneider Automation International. Note 4) The PC98 Series are the trademark or registered trademark of NEC Corporation. Note 5) Netscape is the trademark or registered trademark of Netscape Communications Corp. Note 6) Firefox is the trade mark of Mozilla Corporation.
11
PHU
Caution on Safety *Before using this product, be sure to read its instruction manual in advance.
International Sales Div Sales Group Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome, Shinagawa-ku, Tokyo 141-0032, Japan http://www.fujielectric.com Phone: 81-3-5435-7280, 7281 Fax: 81-3-5435-7425 http://www.fjielectric.com/products/instruments/ Information in this catalog is subject to change without notice.