FC SERIES RATIO SETTER
DATA SHEET
The FC series ratio setter is used to set ratio for ratio control, and its set point signal is transmitted to a controller. This instrument uses a solid state indicator and a pushbutton operation system to provide reliable monitoring and operating functions. It also accepts a thermocouple, a resistance bulb and a 4 to 20mA DC input optionally.
PNG1
FEATURES
1. High reliability This instrument is designed with few mechanical parts. It is mainly composed of electronic parts such as a solid state indicator which was formerly consisted of mechanical parts. 2. International standards This instrument is compact in size, conforming to international standards IEC. It operates on 24V DC power to deliver 1 to 5V DC signals as recommended by IEC standards. 100 and 200V AC power are also available for convenience of operation. 3. Front panel operation Process values and set points can be read accurately with digital indications on panel front. Various parameter settings and setting operations are also possible from the front panel of the instrument.
FUNCTIONAL DIAGRAM
PV Square-root extraction SV SO Local mode output (LS) Remote reques (R-REQ) Compensated process value signal (KPV) Limiter
R B1 B2 B3
Linearize Process value input (PV)
Filter
SO = R X (SV+B3) X (PV–B1) + B2
H
L
Set point output (SO) SO2 Squared set point output (SO2) Ratio output signal (SV) High alarm output (H) Low alarm output (L)
External set point input (CAS or PI) (1 to 5V DC, pulse width, or pulse number) Remote acknowledge signal (R-ACK)
Limiter H R L L SV
KPV
ALM
EDS11-106e
Date Jul. 1, 1994
PNG1
SPECIFICATIONS
1. Ratio computing function
Computing formula
Fault output FLT H L LS R-REQ Open-collector output (photocoupler insulation) Output rating, 30V x 0.1A DC max.
(2) Digital output signal: 5 points
SO=R(SV+B3)(PV–B1)+B2
Computation output Ratio factor Ratio set point Bias 3 Process value Bias 1 Bias 2
High alarm output Low alarm output Local mode output Remote request
4. Indication, setting, operating functions
(1) Bargraph indication
PV indicator Indication method No. of segments Range Resolution Scale length Indicating mode LED (red) 101 + 2 0 to 100%, linear 1 %/FS 100mm 2%/FS 50mm SV indicator LED (green) SO indicator LED (red) 51 + 2
Ratio factor and ratio bias: Setting range; –327.6 to 327.67% Computation cycle: 0.1 sec.
0 to 100% bargraph indication, 0 to 100% reverse bargraph indication, dot indication, –50 to +50% deviation indication
2. Input signal
(1) Process value input signal: One input selectable from the following
Voltage input signal Current input signal 1 to 5V DC 4 to 20mA DC Input resistance, 1MΩ o r more Allow. error ± 0.2%/FS*
I+ Thermocou- I 0 Type I – J: 0 to 600°C ple input K: 0 to 1200 °C E: 0 to 800°C R: 0 to 1600 °C Resistance bulb input JPt100/Pt100 –50 to 500°C
24V ± 2V DC can be Allow. error supplied to transmitter ± 0.2%/FS* in case of AC power supply approx. 35mA Allow. error 10mV DC span or more ± 0.5%/FS* cold junction compensation comprised 50 °C span or more Allow. error ± 0.5%/FS*
Note: *FS: Full scale
(2) Analog input signal: 1 point
External set point CAS 1 to 5V DC Input resistance, 1MΩ or more Allow. error ± 0.2%/FS
(2) Operation mode indication Indicating method: LED (green) Green: L, R (3) Numerical value indication, setting Indication method: LED (red), name in 3 digits + numerical value in 5 digits (negative sign included) Contents of indication: Process value (industrial value), set point (industrial value), high/low alarm, etc. Indication contents are selectable by F/S , , keys on front panel. Setting method: By using F/S , , , , ST keys on front panel (4) Setting functions Fixed value setting method: By using of , pushbuttons on front panel. Setting speed, approx. 40 sec/FS Remote setting method: By use of external set point signal (voltage or pulse input) Tracking speed setting range; 0 to 900 sec/FS (5) Operation mode changeover By using of R/L pushbutton on front panel.
R R L changeover L changeover Voltage signal* Pulse width signal Balanceless bumpless Balance bumpless Balanceless bumpless
(3) Digital input signal: 1 point
Remote acknowledge signal R-ACK Contact input (photo-coupler insulation) ON 0V, OFF 24V ( input current, approx. 11mA/24V DC)
(4) Pulse width or pulse number input signal: 1 set (eithre one)
Pulse width input signal Pulse number input signal Pl+ Pl– Contact input (photo-coupler insulation) ON 0V, OFF 24V ( input current, approx. 11mA/24V DC) ON 0V, OFF 24V ( approx. 11mA/24V DC), max. input frequency 500Hz
Note: * Balanceless bumpless by setting tracking speed
3. Output signal
(1) Analog output signal: 4 points
Compensated process value signal Ratio output signal Set point output Squared set point output KPV SV SO SO2 1 to 5V DC Output resistance, 1Ω or less Allow. error ± 0.2%/FS
5. Power failure processing function Power failure detection: Setting output held at power failure detection. During power failure: Operating parameters backed up by capacitor up to 5 minutes. Initial value of set point is stored in non-volatile memory (lasts 10 years expected at ambient temperature of 50° C or less).
2
Power failure recovery: Initial or continuous start mode can be set within 5 minutes of power failure. Recovery from power failure lasting longer than 5 minutes is done by initial.
Note: ** Control mode at initialzation can be registered L: Local mode or R: Remote mode
6. Self-diagnosis functions
Computing circuit abnormality: FLT lamp lights, FLT contact output "ON". Manual operation output possible Input/output signal abnormality: FLT lamp lights, FLT contact output "ON", computation stops, operating output held Fault contents indication: Cause of fault is indicated numerically on numerical indicator on front panel
Dielectric strength: 1500V AC, 1 min. Insulation resistance: 500V DC, 100MΩ or more Ambient temperature: 0 to 50°C Ambient humidity: 90% RH or less Enclosure: Steel case Rating plate (Name plate): 100 (H) x 70 (W) mm, white acryl Dimensions: 144 (H) x 72 (W) x 391 (D) mm, IEC (DIN) standard Mass {weight}: Approx. 2.9kg Mounting method: Flush with indoor mounting; vertical mounting. Mountable on tilted surface, angle "α"
7. Transmission functions
(1) Transmission items Supervisory items: PNG host Process value, set point, control output, operation mode, alarm information, fault information, various limiter values, constants, etc. Setting operation items: Host PNG Set point, control output, operation mode, various limiter values, constants, etc. (2) Transmission setting inhibit: Parameter setting enable/inhibit can be designated by transmission from the host. Designation is done by keys on the front panel. (3) Communication interface (a) T-link: Private interface Transmission speed: 500Kbps No. of units connectable: 32 max. Transmission distance: 1km max. Transmission form: Multi-drop Control method: I/O transmission and message (b) RS-422A/485: Universal interface Transmission speed: 2400, 4800, 9600 or 19200bps configurable No. of units connectable: 31 max. Transmission distance: 1km max. Transmission form: Multi-drop Control method: Polling/selecting (c) CC data line: Private interface Transmission speed: 19.2Kbps (fixed) No. of units connectable: 15 max. Transmission distance: 500m max. Transmission form: Multi-drop Control method: Polling/selecting
α=0° to 90°
Finish color:
Munsell N 1.5 for both front panel and case Scope of delivery: Setter and mounting bracket Item to be ordered separately: Communication cable (type PNZ)
CODE SYMBOLS
12345678 9 10
PNG1 A B C D E F G W
5-0
Description Process value input signal 1 to 5V DC 4 to 20mA DC J thermocouple 10mV DC span or K thermocouple more, with cold E thermocouple junction compenR thermocouple sation Resistance bulb, JPt 100, 3-wire, 50 °C span or more Resitance bulb, Pt100, 3-wire, 50 °C span or more
A B 1 2 3 Y T R S C
Setting method L type R-L type Power supply 24V DC (20 to 30V DC) 100V AC (85 to 132V/47 to 63Hz AC) 200V AC (187 to 264V/47 to 63Hz AC) Transmission function None T-link RS-422A RS-485 CC data line
8. Other functions
Data protective function by pass code
Note: Symbols for resistance bulb are as follows. JPt100.....JIS C 1604-1981 Pt100.....IEC Pub 751-1983 (Selection of JPt100/Pt100 possible by front key operation)
9. Operating conditions
Power supply: Select from 3 types 24V DC (20 to 30V DC) 100V AC (85 to 132/47 to 63Hz AC) 200V AC (187 to 264V/47 to 63Hz AC) Power consumption: Approx. 11W (DC) Approx. 20VA (AC)
3
PNG1
OUTLINE DIAGRAM
Terminal Terminal cover
(Unit:mm)
Panel thickness 8mm or less
16
140
36
Support bracket
200min. 355
Mounting bracket
144
72
Panel cutout
When mounting 1 unit When mounting "n" units
+1 0
250min.
200min.
+1 0
68
+0.7 0
(72.2n – 4) +1 0
4
138
No. of units n2
138
CONNECTION DIAGRAM
Block terminals (M4 screw)
AO (Compensated process value signal) AO (Set ratio output signal) AO (Set point output) AO (Squared set point output) AI, AO Common bus AI (External set point)
KPV SV SO SO2 SC
51 52 53 54 55 56 57
71 72 73 74 75 76 77 78 79 80 81 82
CAS
Process value input
I+ (PV) I– (SC)
11 12 13 31 32 33 34 35 Io PI+ PI– FLT AC (Pulse width input or pulse number input) DO (FLT output)
DO (Local mode)
LS
14 15
SC R-REQ R-ACK
AI, AO common bus DO (Remote request) DI (Remote acknowledge)
AC
16
Instrument power (AC)
DO (High alarm) DO (Low alarm) Instrument power (24V DC, AC power) 24V power for DI, DO Earth
H L
58 59 60 61 62
– –
PC* PCD G
VP* VPD
+ Instrument power (24V DC power, AC power) + 24V power for DI, DO
Note: * Symbols for AC instrument power are VPO, PCO, approx. 24V DC (0.1A max.) output.
Connections for process value input terminal block
1 to 5V DC The 5th digit of code symbols A 4 to 20mA DC The 5th digit of code symbols B 4 to 20mA DC with inner DC power supply of CC-S The 5th digit of code symbols B
+ – + – + –
11 31 12 PC 60
+ –
11 31 12
Thermocouple The 5th digit of code symbols C,D,E,F Resistance bulb
31
+ –
+ –
11 31 12
+ –
11 12
+
11 31 12
The 5th digit of code symbols G,W
–
5
PNG1
COMMUNICATION CONNECTOR
6 7 8 RXD + 9 RXD – 1 SIG GND 2 SHLD(SD) 3 INH 4 TXD+(T1) 5 TXD–(T2) Green Red Yellow Brown Black White 6 7 8 RXD + 9 RXD – 1 SIG GND 2 SHLD(SD) 3 INH 4 TXD+(T1) 5 TXD–(T2)
Note:Symbol in ( ): T-link terminal symbol
6 7 8 RXD + 9 RXD –
LINE TERMINATION REGISTOR
1 SIG GND 2 SHLD(SD) 3 INH 4 TXD+(T1) 5 TXD–(T2)
6 7 8 RXD + 9 RXD –
1 SIG GND 2 SHLD(SD) 3 INH 4 TXD+(T1) 5 TXD–(T2) Green Red Yellow Brown
HOST MASTER CONTROLLER
Black White
End station
First station
Host Termination Resistor Communication cable
PNG1
PNG1
PNG1
PNG1
Caution on Safety *Before using this product, be sure to read its instruction manual in advance.
Head Office
6-17, Sanbancho, Chiyoda-ku, Tokyo 102-0075, Japan http://www.fesys.co.jp/eng
Sales Div. International Sales Dept.
No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187 http: //www.fic-net.jp/eng
Information in this catalog is subject to change without notice.
Printed in Japan