PROGRAM CONTROLLER X (96mm)
DATA SHEET
The program controller X (PVX) is a high performance controller designed on the basis of many years of Fuji’s successful experience and advanced technologies.
PVX
FEATURES
1. Display of 3 different datas
Three different datas such as measured value (PV), set value (SV) and time can be monitored simultaneously.
2. 20-segment program patterns (9 patterns)
Program patterns can be linked in series or repeated.
3. Full multi-input type
The program controller accepts a large number of inputs (full multi-input). Up to 11 kinds of thermocouples, 1 resistance bulb, 6 different voltage inputs and a current input can be connected.
4. Wide input/output functions (option)
The program controller is able to expand the input/output functions up to 8 points of digital inputs, 11 points of digital outputs and 2 points of auxiliary analog outputs.
SPECIFICATIONS
96 × 96mm Full multi-input • Thermocouple: J, K, R, B, T, E, S, N, U, WRe5-26, PL-II • Platinum resistance bulb: Pt100 • DC voltage/current Input accuracy: ± 0.2% of full scale, ± 1 digit Input sampling cycle: 100ms Control action: PID with auto-tuning Control output: • Relay contact • Voltage pulse output (for SSR drive) • Current output Alarm output: 2 points (ALM1, ALM2) Program function: • Number of patterns: 9 patterns (max.) • Number of segments/patterns: 20 segments • Multi-memory (PID, etc.): 9 sets • Pattern linkage/repeat function: possible • Time setting: hour/minute or minute/ second
Operation mode: • Program operation
• Fixed value (FIX) operation • Manual (MAN) operation
Panel size: Input:
Digital input/output:
• Time signal output: 4 points (TS1, TS2, TS3, TS4) • External command input: 4 points (Reset, Run, Hold, Advance) • Pattern select input: BCD 1 digit (23, 22, 21, 20) • Status output (Output informations): 3 points (Reset, Run/Hold, End) • Auxiliary analog output: 2 points (AO1, AO2) • Expansion digital output: 2 points (TS5, TS6 or ALM3, ALM4) Flexible supply voltage: 100 to 240V AC
Option:
Power source:
EDS11-124d
Date Jan. 31, 1997
PVX
FUNCTIONS AND PERFORMANCE
1. Input
(1) Input accuracy:
± 0.2% of full scale, ± 1 digit (under standard condition), cold junction compensation error: ± 1°C
3. Program setting
(1) Program function Number of patterns: 9 patterns (max.) Number of segments/patterns: 20 segments Multi-memory (PID, etc.): 9 sets (2) Operation mode
Program operation Fixed value (FIX) operation Manual (MAN) operation
(2) Input:
Thermocouple (range code setting) J J K K K R B T T E E S N U WRe5-26 PL-II : : : : : : : : : : : : : : : : 0 0 0 0 0 0 0 –199.9 –150 0 –199.9 0 0 –199.9 0 0 to to to to to to to to to to to to to to to to 400°C 800°C 400°C 800°C 1200°C 1600°C 1800°C 200°C 400°C 800°C 800°C 1600°C 1300°C 400°C 2300°C 1300°C Resistance bulb (range code setting) 0 0 0 0 –50 –100 –199.9 –199.9 JPt100(*)Ω: 0 0 0 0 –50 –100 –199.9 Pt100Ω(*): to to to to to to to to to to to to to to to 150°C 300°C 500°C 600°C 100°C 200°C 600°C 850°C 150°C 300°C 500°C 600°C 100°C 200°C 600°C
(3) Program operation
Pattern selection, program reset, start, stop and skip are possible with front panel key, digital input.
(4) Time setting
Setting of hour/minute or minute/second Hour/minute: 0 (hr) 0 (min) to 99 (hr) 59 (min) Minute/second: 0 (min) 0 (sec) to 99 (min) 59 (sec)
4. Control action
(1) Auto-tuning PID action
P: 0.0 to 999.9% (ON/OFF control, P=0) I: 0 to 3200sec (integral action OFF, I=0) D: 0.0 to 900.0sec (derivative action OFF, D=0)
(2) Multi-memory
PID, etc; up to 9 sets
(R: ± 1% within the range of 0 to 400°C) (B: ± 5% within the range of 0 to 500°C)
°F display; possible 0.1°C/°F display; possible (1000°C/°F span or less)
5. Digital input/output
(1) Digital input Usual specification :
16V DC, 15mA
DC voltage/current (full programmable scale; –999 to 9999) 0 to 10mV DC, 0 to 100mV DC, 0 to 1V DC, 0 to 5V DC 1 to 5V DC, 0 to 10V DC, 4 to 20mA DC Note: * Pt100…IEC Pub751-1983
External command input :
Reset: Program reset Run: Program start Hold: Program stop Advance: Segment feed
(3) Input sampling cycle: 100ms
2. Output
(1) Control output Relay contact output :
220V AC/30V DC, 3A (resistive load) SPDT contact Electrical expected life: more than 105 operations Minimum ON/OFF current: 0.1A (24V DC)
Pattern select input :
BCD input; 1 digit (23, 22, 21, 20)
(2) Digital output Time signal output (TS1, TS2, TS3, TS4)
Open-collector output: 4 points, 24V DC, 50mA
Status output :
Open-collector output: 3 points, 24V DC, 50mA Reset: Program reset status Run/Hold: Program start/stop status End: Program end status
SSR drive output :
ON: 10 to 18V DC OFF: max. 0.5V Max. current: 20mA DC
6. Option output
(1) Expansion digital output Expansion alarm output (ALM3, ALM4) or expansion time signal output (TS5, TS6)
Open-collector output: 2 points, 24V DC, 50mA
Current output :
4 to 20mA DC (allowable load: 600Ω or less)
(2) Alarm output (ALM1, ALM2) Relay contact output :
2 points 220V AC/30V DC, 1A (resistive load) SPST contact Electrical expected life: more than 105 operations Minimum ON/OFF current: 0.1A(24V DC)
(2) Auxiliary analog output Output points : 1 or 2 points Output data : Measured value, set value or manipulated
value
Output accuracy : ± 0.2% of full scale Kinds of output :
1 to 5V DC 0 to 5V DC 0 to 10V DC Additional function : Scaling
2
7. Operating conditions, etc.
Power supply voltage: 100 ( -15%) to 240 (+10%) VAC, 50/
60Hz
CODE SYMBOLS
12345678 9 10 11 12 13
Power consumption: 30VA or less Ambient temperature: 0 to 50°C Ambient humidity: 90%RH or less (free from condensation) Memory backup: Lithium battery (5 years expected: 0 to 40°C) Dimensions (H × W × D): 96 × 96 × 173.5mm Mass{weight}: 1kg (approx.) Mounting angle: Backward inclination within 15°
PVX
1 2 3 C P D
TS1 -
Y
E
Description
Control output Relay contact output SSR/SSC drive output Current output (4 to 20mA DC) Digital input External command input (4 points) Pattern select input (4 points) External command input +Pattern select input
T S
Time signal output, 1 to 4 Output status Expansion digital output (open-collector output, 2 points) Without Used as time signal (TS5, 6) Used as alarm (ALM3, 4) 0 1 2 Auxiliary analog output signal Without Voltage output, 1 point Voltage output, 2 points Note:Prior to delivery from factory: 0 to 10V DC Communication function Without With T-link Front panel indication and instruction manual (option) English
Y T A
Y T
E
Note : If the range is not designated on order, the product will be delivered with the following range selected. K thermocouple 0 to 400°C.
3
PVX
FUNCTIONAL BLOCK DIAGRAM
DI Reset External command input Run Hold Advance 23 Pattern select input 22 21 20 Fixed value,SV Program setting, 20 segments Ficed value (FIX) Sensor input AI Filter PV PID with auto-tuning Man Control parameter 9 patterns 9 sets Reset External command input Pattern select input Status output Run/Hold End 3 points Run/Hold End Status output Reset
Program SV Auto MV Control output
Full multi-input Manual operation Guarantee soak function PV start function Pattern linkage function Pattern repeat function (99,max.) Auxiliary analog output, 1/2 points (PV/SV/MV) AO (Option)
Time signal output, 4 points (+2 points) (Note) Alarm output, 2 points (+2 points) (Note) Communication function with T-Link (Note)
DO
Power supply, 100 to 240V AC
Note :+2 points···Either time signal or alarm output can added (option). :Communication function with T-link can be added (option).
4
OUTLINE DIAGRAM
(Unit:mm)
96 12 173.5
115
Panel mounting bracket
Panel cutout
100 min.
116 min.
92 +0.8 0
Connection diagram
92 +0.8 0
Control output 1 (Contact output, 4 to 20mA DC, SSR/SSC drive output)
MV1-COM
+ -
TRX-COM
9 10 11 12 13 14 15 16 17
Status output Pattern select input Time signal 1-4 output Alarm 3-4 output or time signal 5-6 output
18 19 20 21
ALM3/TS5
TRX1 27 TRX2 28 A02 29 RTD Input signal, PV + + Aux. mV TC analog output -4~20mA A B
1 2 3
MV1-1 MV1-2 ALM1
TS1 TS2 TS3
90.5
36 37
ALM4 /TS6
Alarm output 1
ALM2
A01 30 ALM/TS-COM A0-COM 31
4
Alarm output 2
TS4 DORESET
5
Power supply, 100 to 240V AC
ALMCOM
22 DI-23 23 DI-22
1
6
DOAC RUN/HOLD DO-END DO-COM
7 AC 8G
DIRESET 24 DI-2 DIRUN 25 DI-20 DIHOLD 26 DICOM DIADVANCE
32 33 34 35
External command input
+
V
+
38 SC 39 40 41 42
250Ω (Note)
Note:A resistor(250Ω± 0.1%) should be used for 4 to 20mA DC input.
SCOPE OF DELIVERY
Main unit and panel mounting bracket
5
PVX
Caution on Safety *Before using this product, be sure to read its instruction manual in advance.