FFI SYSTEM
MASTER STATION
DATA SHEET
This instrument controls signal exchange with FFI system field instruments, and transmits process values and alarm signals in the field instruments to the host system. It can support a maximum of 8 field instruments, uses RS-232C or Ethernet communication for transmission to the host side and has functions for duplex configuration to secure redundancy.
PNT···3
FEATURES
1. Connection of up to 8 filed instruments A single master station can support up to 8 field instruments via an optical star coupler. 2. General-use transmission interface A host system is connectable via the general-use RS232C or Ethernet interface . This interface allows a personal computer or a control device to collect the data of field instrument and set parameters in the field instrument. 3. System duplicable (with Ethernet) This station has functions compatible with a duplex system so that system redundancy is ensured.
SPECIFICATIONS
Functional specifications 1. Interface with field instruments
Applicable optical fiber cable: silica fiber ... core/clad diameter 100/140 µm Optical connector: FC connector Transmission distance: 1.5 km max. (between field instruments and master station) Number of connectable field instruments: Max. 8 instruments via an optical star coupler Transmission cycle: 0.2 sec (transmission with each field instrument at intervals of 0.2 sec)
Synchronous system: Start-stop synchronization Communication interval: 1 sec or longer Transmission distance: 15 m or less (2) Ethernet Protocol: TCP/IP, UDP/IP Transmission specification: 10BASE-T Code format: Manchester code Transmission speed: 10 Mbps Communication interval: 200 ms or longer
3. Indicating function (LED lights up on instrument front)
POWER: LINK/ACT: FLT/ALM: BATT: OPR: Lights up when power supply is turned on. Lights up in Ethernet communication. Lights up when an error occurs. Lights up when a battery alarm occurs in field instrument. Lights up in the operating status.
4. Duplexing function (available in Ethernet specification)
Using two master stations, the optical star coupler and host system can be connected in two lines for duplex configuration. If the primary master station become faulty or the primary line is disconnected in the duplex configuration, the standby line can be activated owing to system redundancy. In the duplex configuration, communication with field instruments starts on reception of a working command from the host system.
2. Interface with host system
(1) RS-232C Transmission method: Polling/selecting method Code format: Binary format Transmission speed: 9600 bps
EDS11-156a
Date Apr. 1, 2011
PNT···3
5. Operating conditions
Power supply: 100V AC, 50/60 Hz Power consumption: Approx. 10 VA Ambient temperature: 0 to +50°C Storage temperature: -10 to +60°C Ambient humidity: 90% RH or less
CODE SYMBOLS
12345678
PNT 1 2 3
0003
Description Transmission and duplexing functions Ethernet without duplexing Ethernet with duplexing RS-232C (without duplexing)
Physical specifications
Enclosure: Indoor type Case material: Polycarbonate Mounting method: Rack mounting Mass: Approx. 0.6 kg Power supply and ground connection: Via front panel screw terminals (M4) RS-232C connection: Front panel connector (D-SUB 9 pins) Ethernet connection: Front panel connector (modular connector of 8 poles)
SCOPE OF DELIVERY
Master station (including fixture)
RELATED DEVICES
• Field instruments (pressure/differential pressure transmitters, temperature transmitter, etc.) • Optical star coupler ... EDS8-48 • Hand-held communicator ... EDS8-44
ORDERING INFORMATION
1. Part name 2. Model type 3. IP address in Ethernet specification (shown below) 10.55.136.01 These digits need to be specified in hexadecimal notation (allowed within 01 to FF).
2
SYSTEM BLOCK DIAGRAM
Without duplex configuration
Host system
RS-232C or Ethernet Master station Control room
Field
Optical star coupler
Field equipment
max. 8 units
Duplex system (available with Ethernet)
Host system
Ethernet Master station Control room
Field
Optical star coupler
Field equipment
max. 8 units
3
PNT···3
OUTLINE DIAGRAM
(Unit : mm)
Space for connector 2 φ 4.7 mounting holes 6.5 1.6
49 30
Min. 100
132
POWER LINK/ACT FLT/ALM BATT. OPR
Receptacle for optical connector
OPT.
Connector for RS-232C
130
E
170
160
AC
100
Terminal block (M4 screw) Fixture
In RS-232C specification
POWER LINK/ACT FLT/ALM BATT. OPR
OPT.
Connector for Ethernet
Ethernet
E AC 100
In Ethernet specification
Caution on Safety *Before using this product, be sure to read its instruction manual in advance.
International Sales Div Sales Group Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome, Shinagawa-ku, Tokyo 141-0032, Japan http://www.fujielectric.com Phone: 81-3-5435-7280, 7281 Fax: 81-3-5435-7425 http://www.fjielectric.com/products/instruments/ Information in this catalog is subject to change without notice.