Digital Controller
COMPACT CONTROLLER M [CC-M] (FIXED FUNCTION/CONTINUOUS OUTPUT TYPE)
PDA1
DATA SHEET
The Compact Controller M (fixed function/continuous output type) is a single-loop process controller. Receiving 1 to 5V DC signals as well as those from thermocouples and resistance bulbs as input signals, it performs advanced controls such as PID control, square root extraction, non-linear control, and feed forward control.
FEATURES
1. Single-loop controller with control output The controller has a single-loop control function. 2. High visibility ensured by color graphic display A color LCD is adopted for clear graphic displays such as bar graph and trend displays. 3. Networking (option) Communication can be carried out over our PLC-link (Tlink) or Modbus (RS485) network. 4. Backup (option) In the event of a failure of the main unit, the built-in backup operation device takes over the operation, thus preventing adverse effect on the system. 5. Memory card (option) The data such as process input data and control output data can be saved in memory cards.
FUNCTIONAL DIAGRAM
External input terminal Personal computer Bar graph indicator To other controllers Communication terminal External output terminal Compensated PV signal (AO3) Control output (current:MI) Control output (voltage:AO2,AO5) Set point transmit signal (AO4) Manual mode output (M:DO6) Local mode output (DO7) Remote request (DO8) Fault output (FLT) High alarm output (DO9) Low alarm output (DO10) Deviation upper limit alarm (DO4) Deviation lower limit alarm (DO5) Rate of change upper/lower limit alarm (DO3) FLT lamp Alarm
External MV input (AI2) Feed forward input (AI3) Linearize A/D converter Process value input (PV1) Filter Feed forward computation
−
Internal input terminal
4 to 20mA, thermocouple/ resistance bulb conversion R-SV(PV2) Pulse input switching (DI1,DI2) Pulse input switching Command (DI9) Forced M command (DI10) PV tracking (DI7) External MV command (DI5) R-ACK(DI8)
Square-root extraction Limiter Non-linear
P I D
+ +
MH ML
Limiter
M
SH SL
R A.M
M mode L mode
M mode
R C
R mode
Fault : Option
Internal output terminal
D/A converter
+
R.A
EDS11-161
Date Aug. 19, 2005
PDA1
SPECIFICATIONS
1. Control Functions (1) PID control • Number of loops and PID : 1 loop (1 control output / 1PID) • Proportional band (P) : 1.0 to 3276.7%, set at 3000.0% for delivery • Integration time (I) : 0.1 to 3276.7 s, set at 3000.0 s for delivery • Derivative time (D) : 0.0 to 900.0 s, set at 0.0 s for delivery (2) Computation cycle : 100 ms (3) Alarm function • Kinds : Each high/low of PV, SV and MV, PV change rate alarm, MV change rate alarm, high/low deviations. 2. Input Signals Performance under reference condition (23 ± 2˚C, 55± 10%RH, 100 V to 240 V AC, 50/60Hz power supply frequency or 24 V DC power supply voltage, free from vibration and the effect of external noise) 2-1 Analog input signal • Number of inputs : 4 (points used) • Input signal types : DC voltage, DC current, thermocouple (option), resistance bulb (option) One thermocouple inputs or one resistance bulb inputs are selectable. (1) DC voltage / DC current • Input range: Selectable among 0 to 5 V DC, 1 to 5 V DC and 0 to 10 V DC Initial set before delivery : 1 to 5 V DC • Input accuracy: ± 0.1% of input span± 1 digit • Scaling (Engineering data conversion) : Settable within a range from -32767 to 32767 4, 3, 2, 1 or 0 digit below decimal point is selectable. Initial set before delivery : 0.00% to 100.00% • Engineering unit: Settable in up to 8 characters Usable characters: Alphabets numerals, symbols such as +, – ,*,etc. • Input accuracy guarantee range: –5% to 105% of input range (minus input excluded). • Maximum continuous permissible voltage: ± 35 V • Input resistance: 1 MΩ or more • Influence by ambient temperature: ± 0.1% FS/10°C or less. • Influence by power supply fluctuation: ± 0.1% FS or less. • Isolation : Non-isolated from internal circuit.
• In case of current input: Shunt resistor need to be connected to the analog input terminal. (250 Ω shunt resistor is optional item) (2) Thermocouple (option) • Types and measurable ranges: * See Table 1. • Input accuracy: ± 0.2% FS ± 1 digit [Note]B type: ± 5% between 0 to 400˚C S and R type: ± 1%between 0 to 500˚C All type of TC: ± 5% under–100˚C • Reference junction compensation error: ± 1.0°C (provided measurable range is –50°C and higher) [Note]Reference junction compensation resistor is connected at external input terminal in case of thermocouple input is ordered. • Input accuracy guarantee range: –5% to 105% of input range. • Input resistance: 1 MΩ or more • Allowable signal source resistance: 100 Ω or less (Zener barrier connection unallowable) • Influence by signal source resistance: About 0.25 µV/Ω • Influence by ambient temperature: ± 0.2% FS/10°C ± 1°C or less. • Influence by power supply fluctuation: ± 0.2% FS ± 1˚C or less • Burnout detection: Provided • Isolation: Isolated from internal circuit. (3) Resistance bulb (option) • Types and measurable ranges: * See Table 1. • Input accuracy: ± 0.2% FS ± 1 digit • Input accuracy guarantee range: -5% to 105% of input range • Allowable wiring resistance: 10 Ω o r less per wire, provided wiring resistance must be equal among 3 wires (Zener barrier connection unallowable) • Influence by ambient temperature: ± 0.2% FS/10˚C or less. • Influence by power supply fluctuation: ± 0.2% FS or less • Burnout detection: Provided • Isolation: Isolated from internal circuit. [Note] FS: full span. • Sampling period : 100 ms 2-2 Digital input signal • Number of inputs : 7 inputs • Electrical specifications : No-voltage contact or transistor contact ON/0 V, OFF/24 V, ON current/about 8 mA Isolated from the internal circuit by photocoupler. Not isolated between each digital input and output. • Contact rating : 30 V DC, 10 mA or more
2
• Signal judgment : No-voltage contact Contact resistance; 200 Ω or less at ON, 100 kΩ or more at OFF : Transistor contact 1V max at ON., leakage current 100µA max. at OFF 3. Output Signals Performance under reference condition (23 ± 2˚C, 55± 10%RH, 100 V to 240 V AC, 50/60Hz power supply frequency or 24 V DC power supply voltage, free from vibration and the effect of external noise) 3-1 Analog output signal (1) Control output • Number of outputs :1 • Output signal : 4 to 20 mA DC • Output accuracy : ± 0.2% FS • Load resistance : 600 Ω or less • Output accuracy guarantee range : 2 to 22 mA DC • Influence by ambient temperature : ± 0.2% FS/10˚C or less • Influence by power supply fluctuation : ± 0.2% FS or less • Isolation : Non-isolated from internal circuit (2) Auxiliary analog output • Number of outputs: : 4 (points used) • Types of signal : Selectable among 0 to 5 V DC, 1 to 5 V DC and 0 to 10 V DC Initial set before delivery: 1 to 5 V DC • Output accuracy : ± 0.1% FS • Load resistance : 15 kΩ or more • Output guarantee range : 1 to 5 VDC : –12.5% to 112.5% : 0 to 5 VDC : 0% to 112.5% : 0 to 10VDC : 0% to 105% • Influence by power supply fluctuation : ± 0.1% FS or less •Isolation : Non-isolated from internal circuit 3-2 Digital output signal • Number of outputs : 8 (points used) • Electrical specifications : Transistor open collector 1 V max. at ON, 10 µA max at OFF. Isolated from the internal circuit by photocoupler. Not isolated between each digital input and output. • Output rating : 30 V DC, 100 mA max. (resistive load) 3-3 Fault output signal (terminal symbol FLT) • Number of outputs : 1 output • Electrical specifications
: Transistor open collector 1 V max. at ON, 10 µA max at OFF. Isolated from the internal circuit by photocoupler. Not isolated between each digital input and output. • Output rating : 30 V DC, 100 mA max. (resistive load) 4. Display • Display unit
: 16 Colors graphic liquid crystal display, with CFL back light and contrast adjust function. • Contents of display : Menu : Loop panel (1 loops) Bar graph display, digital display, etc. : Tuning screen : Trend screen : Alarm and alarm historical screen : Analog input/output and digital input/ output indication screen : Parameter setting screen
5. Setting and Operation (1) Set point setting method • Setting key : Up key/down key • Setting speed : About 40 s/FS • Setting resolution : 0.05% FS/each key press (2) Control output operation method • Operation key : Up key, down key and high-speed key • Operation speed : About 40 s/FS (usual), about 8 s/FS (high speed) (3) Operation mode • Kinds of operation mode : C (or R), A, M and HM [Note] C : Cascade mode (operation according to remote set point) R : Remote mode (operation according to remote set point) A : Auto mode (operation according to the local set point) M : Manual mode (control output to be manually operated by operator) HM : Hard manual mode (the mode in which operation is performed with a backup operating device) [Remark] C and R have different nameplates, while operation is the same. • Setting method : Selectable from the followings by specifieing the code symbols. C-A-M A-M R-A-M • Changeover : Balance bumpless changeover from Auto to Remote and from Auto to Cascade Balanceless bumpless in other changeover [Note] Balance bumpless changeover is a method where each setting value needs to be balanced by operator himself at the time of changeover. Balanceless bumpless changeover is a method where each setting value is automatically balanced by the controller at the time of changeover.
3
PDA1
: Setting of a password : Settable in 4 numerals (within 0000 to ffff) Initial set before delivery: 0000 • Contents of security : Inhibition of parameter setting (5) Other setting items • Tag name : Settable in up to 8 characters Usable characters; alphabes, numerals, symboles such as +, – ,*,etc. 6. Power Supply • Voltage rating : 100 V to 240 V AC/24 V DC [According to Code Symbols] • Allowable range : 85 V to 264 V AC/20 V to 30 V DC [According to Code Symbols] • Frequency : 47 to 63 Hz • Power consumption : 60 VA or less (100 V to 240 V AC) : 30 W or less (24 V DC) [According to Code Symbols] • Power supply output voltage (terminal symbol VP and PC) : 20V to 30V DC,max. 40mA 7. General performance and characteristics • Insulation resistance : 500 V DC, 50 MΩ or more. • Dielectric strength : 2,000 V AC for 1 minute between power terminal and ground terminal in case of 100 V to 240 V AC power supply : 500 V AC for 1 minute between power terminal and ground terminal in case of 24 V DC power supply. : 500 V AC for 1 minute between signal communication terminals and ground terminal • Rush current : 60 A or less. (100 V AC to 240 V AC power supply) • Clock : Set and display year, month, day, hour, minute, second accuracy : ± 100 ppm (deviation per month: about 4 min) except of time lag shorter than 1 s / power ON / OFF action. • Memory backup : Protection by lithium battery. (expected battery life is about 2 years under room temperature) Parameter and program are stored nonvolatile memory. 8. Operating and storage conditions • Location : Indoor • Operating temperature : 0 to 50˚C : 0 to 40°C in case of multiple mounting ( Temperature change rate : Max. 10˚C / h) • Transport and storage temperature : -20 to 70˚C ( Temprature change rate : Max. 20˚C / h) (4) Security • Method • Password • Operating humidity : 5 to 90% RH, condensation unallowable • Transport and storage humidity : 5 to 95% RH, condensation unallowable • Operating continuous vibration : 4.9 m/s2 or less • Transport and storage shock : Fall of 60cm max. in packed status 9. Power Failure and restart Function • Permissible duration of momentary power failure : 20 ms at 90V AC (100 V to 240 V AC only) In the case of 24V DC, it is recommended to avoid power failure problem that system power supply unit with permissible duration of momentary power failure of 20ms or more (PXJ, for example) is used. • Behavior at power failure detection : Control stops at detection of power failure. • Power recovery mode : Selectable initial start and continuous start 10. Self-Diagnosis • Control and computation circuit failure : Monitoring with watchdog timer • Input signal failure : Voltage/current input Monitoring of range over : Thermocouple and resistance bulb Monitoring of disconnection • Behavior at failure : FLT is indicated, FLT lamp lights, FLT output signal turns on, control stops and control output is held. 11. Structure • Enclosure : Plastic (material: PC-ABS) • Finish color : Front frame and enclosure both gray • Flame resistance : UL94V-0 • Protection : Front face; IP54 (display unit and operation key) • External dimensions (W x H x D) Screw terminal type : 72 x 144 x 272mm Compression terminal type : 72 x 144 x 280mm • Mass : 1.9 kg or less • Mounting method : Flush on indoor panel Vertical mounting as standard Tilted mounting allowed within backward angle 0° to 45°.
90° to 45°
For panel cutout dimension, refer to Panel Cutout Dimensions • External terminal : Screw terminal type (M3.5) or Compression terminal type (by the code symbols)
4
12. Backup Function (option) • Method : With backup operation unit • Number of control outputs : 1 output • Output signal : DC4 to 20mA • Indicator : 21-segment LED • Operation key : Control output up, control output down, • Operation resolution : 5% • Backup changeover : Changeover has been made by the HM (Hard Manual) switch. However, changeover cannot be made when the backup operation unit is faulty. : Balanceless and bumpless switching to the HM mode 13. Communications (option) 13-1 Modbus(R) protocol interface (option) • Communication mode: Host communications • Communication protocol: Modbus(R) protocol • Physical specifications: EIA RS485 • Communication mode: Two-wire, half-duplex, startstop synchronous mode • Connection mode: Multi-drop connection • Communication speed: Selectable from 2.4, 4.8, 9.6, 19.2, and 38.4 kbps. Default setting: 19.2 kbps • Communication distance: Total extension; 500 m • Data length: Fixed to 8 bits • Parity: Selectable from ODD, EVEN, or None. • Stop bit: Selectable from 1 or 2. • Insulation: Insulated from internal circuit • End of line resistor: 100 Ω (option) • Communication item: Parameter, measured value • RS232/RS485 converter (recommended item) Type: K3SC-10 (Insulated type by OMRON) 13-2 T-link interface (option) • Communication behavier : Master • Master communication : Connecting to CPU capsule : I/O transmission ; 8-word outputs • Slave communication : None • Common item : Wiring system ; multi-drop : Communication speed ; 500kbps : Communication distance; Max. 500m in total : Isolation ; Not isolated from internal circuit : Terminator ; 100 Ω (optional item)
14. Memory Card Interface (option) • Specification : Compact Flash® (Based on CFA) • Compatible memory card : 5 V flash memory card Capacity 4, 20 and 32 MB • Application : Process data logging (3 points) • Saving period : 1s min. • Data storage capacity
Memory card capacity 4MB 20MB 32MB Data storge about 180 thousand data about 900 thousand data about 1.35 million data
[Remark] Values of 4 points are recorded simultaneously by one data. [Note] The data of max. 16 points (4 screens) can be storaged at storage time as 1 s. • Format method : Dependent on this controller • Data readout : Readout by PC using PCMCIA card slot • Recommended memory card : Made by Sandisk corporation Sandisk compact Flash memory card is standardized and on the market. Models ; SDCFB-4-101-00 (4MB) SDCFB-20-101-00 (20MB) SDCFB-32-101-00 (32MB) 15. Standards under Conformity (1) General safety : IEC 1010-1 (1990) EN 61010-1 (1993) (2) EMC : Emission EN 50081-2 (1994) Immunity EN 50082-2 (1995)
5
PDA1
Table 1
List of Thermocouple and Resistance Bulb Measurable range
Input signal Thermocouple J J K K K R B T T E E S N U WRe5-26 PL2 Resistance bulb Pt100 00 Input type code Input range code Measurable range˚C 01 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 00 01 02 03 04 05 06 07 Resistance bulb JPt100 00 08 09 10 11 12 13 14 0.0~400.0 0.0~800.0 0.0~400.0 0.0~800.0 0.0~1200.0 0.0~1600.0 0.0~1800.0 -200.0~200.0 -150.0~400.0 0.0~800.0 -200.0~800.0 0.0~1600.0 0.0~1300.0 -200.0~400.0 0.0~2300.0 0.0~1300.0 0.0~150.0 0.0~300.0 0.0~500.0 0.0~600.0 -50.0~100.0 -100.0~200.0 -200.0~600.0 -200.0~850.0 0.0~150.0 0.0~300.0 0.0~500.0 0.0~600.0 -50.0~100.0 -100.0~200.0 -200.0~600.0
SCOPE OF DELIVERY
Controller, panel mounting bracket, instruction manual (depend on code symbols)
Optional Items
Item Terminator for communication (100 Ω) 34-pin multiple connector (Note1) Type PDZR1001 PDZR2001 PDZC1001 PDZC2001 PDZC3001 PDZC4001 Shunt resistor (250 Ω) PDZS1001 PDZS2001 Communication cable (Note2) For screw terminal, from PDA to PDA For screw terminal, from PDA to PLC For screw terminal, from PDA to PC For compression terminal, from PDA to PDA For compression terminal, from PDA to PLC For compression terminal, from PDA to PC Replacing case Compact Controller M (PDA1) Instruction Manual in book form (in Japanese) Compact Controller M (PDA1) Instruction Manual in book form (in English) Instruction Manual on CD-ROM (in Japanese and English) (Note3) Mounting bracket (Note4) (Note 1) (Note 2) (Note 3) (Note 4) PDZK1xx1 PDZK2xx1 PDZK3xx1 PDZK4xx1 PDZK5xx1 PDZK6xx1 PDZE1002 PDZX1101 M3.5 solderless terminals at both ends M3.5 solderless terminals at both ends 9-pin connector at PC side end With compression terminal at both ends With M3.5 solderless terminal on PLC side 9-pin connector on PC side For replasing CC-F Instruction manual in book form Instruction manual in book form Instruction manual on CD-ROM Improved mounting bracket 1 1 1 1 1 1 1 1 Specification For screw terminal For compression terminal Solder type straight terminal Solder type right angle terminal Solderless type straight terminal Solderless type right angle terminal For screw terminal For compression terminal Available unit 1 1 1 1 1 1 1 1
PDZX2101
1
PDZQ1001
1
PDZA1001
1
Screw terminal type. Required when using digital input/output. Cable for T-link/Modbus communication. The instruction manual in Japanese and English are included. This is the improved mounting bracket adopted from PDA-2. Refer to the outline diagram for shape and dimensions.
Block diagram of electrical isolation
Solid line shows isolation from the other units or circuits. Power supply Power supply unit DI / DO unit Ground Ground DO1 to DO10
DI1 to DI10
PV2 PV1 TC or RTD input unit AI / AO unit AI1 to AI6 MI1 AO1 to AO5 Modbus
(Note)
Communication unit
T-link
(Note) The communication unit is not isolated from the AI/AO unit when using T-link.
6
CODE SYMBOLS
1 2 3 4 5 6 7 8 9 10111213 1415 PDA 2- 10 1 1 1 2 A C D E A B C A R Y A D Description Controller function With fixed function Number of control loops 1 loop (1 control output) External terminal M3.5 screw terminal Compression terminal Input signal 1 to 5 V DC Thermocouple Resistance bulb Pt100 : 1 Resistance bulb JPt100 : 1 Note 1 Note 2 Note 2 Note 2
Power supply voltage 100V to 240V AC (Usable range 85V to 264V AC) 50 / 60Hz 24V DC (Usable range 20 to 30V DC) Operation mode Cascade-Auto-Manual changeable type Auto-Manual changeable type Remote-Auto-Manual changeable type Backup operation unit Without For 1 control output, 100 to 240 V AC For 1 control output, 24 V DC Communicatioin / Memory card interface (Slave communication) (Master communication) (memory card interface) Note3 Note4 Without Without Without Without Without With Modbus Without Without Modbus Without With T-link Without Without T-link Without With Y C Instruction manual Without Instruction manual on CD-ROM (in Japanese and English)
Y M C U A S
Note 5
Note 1) For current input, a shunt resistor is used for conversion into voltage. Shunt resistor is optional item. Note 2) Thermocouple and resistance bulb input are opitons. Allowable up to 1 point. Note 3) Communication cable and terminator are optional items. Note 4) Recommended maker: Sandisk corporation. Note 5) This instruction manual is recorded in PDF format file. To read this manual, Adobe Acrobat Reader is required. Setup program of Acrobat Reader is also recorded on this CD-ROM.
7
PDA1
OUTLINE DIAGRAM (Unit : mm)
SCREW TERMINAL TYPE
67.5
Cover bracket Panel thickness 8 mm or less Panel Terminal cover
20
72 21.6 Mounting bracket 272 134
Note) The distance between other instruments and low end of PDA shall be more than 100mm.
COMPRESSION TERMINAL TYPE
67.5
Terminal cover Panel thickness 8 mm or less Panel Cover bracket
20
100MIN.
137.5
144
72
Mounting bracket
Note) The distance between other instruments and low end of PDA shall be more than 100mm.
8
100MIN.
21.6
280
137.5
144
MOUNTING BRACKET
50
16
160
205
PANEL CUTOUT DIMENSIONS
For mounting one unit
250 or more
For mounting multiple “n” units
250 or more
138
68
+0.7 0
(72.2n-4)
+1 0
138
Number of n2 n ; Q'TY
+1 0
+1 0
9
PDA1
EXTERNAL CONNECTION DIAGRAM
SCREW TERMINAL TYPE • • • • M3.5 screw terminal section
Voltage Thermocouple Resistance input bulb input input
(+)
VPD
b ○ 11 B ○ 12 A ○ 13
I+1 I-1 Io1 I+2 I-2 Io2 Note)
PCD
FLT DO1 DI1 DI2 VST2 T1 T2
31 32 Note) 33 34 35 Note) 36 Note) 37 Note)
(+)
RS485 communication (Modbus) or T-link host communication
Note)
51 52 53 54 55 56 57
AO1
Note)
Process value input
(−)
AO2 AO3 AO4 AO5 SC SC
Note) Note)
AI1 AI2 AI3 AI4 AI5 SC MI+1
71 72 73 74 75 76 77 78 79 80 81 82 83
Note) Note)
24V external supply (+) Manipulated output 1 Voltage input
Rcj
Voltage input
External setting input
14 15 16
(-)
(COM)
DO1 23 DO2 24 DO3 25 DO4 26 DO5 27 DO6 28 DO7 29 DO8 30 DO9 31 DO10 32 VPD 33 PCD 34
(Same as screw No. 32)
DI1 13 DI2 14 DI3 15 DI4 16 DI5 17 DI6 18 DI7 19 DI8 20
+ -
MI+3 1
Note) Note) Note) Note)
24V external supply (-)
(Same as screw No. 33) MI-3
MI-4 AO1 AO2 AI1 AI2 AI3 AI4 SC PCD
2 4
(Same as screw No. 34) MI+4 3
5 (Same as screw No. 51) 6 (Same as screw No. 52) 7 (Same as screw No.71) 8 (Same as screw No. 72) 9 (Same as screw No. 73) 10 (Same as screw No. 74) 11 (Same as screw No. 56,57,76)
58 MOD+ SC MI-1 59 MODMI+2 60 VST MI-2 PC 61 VP 62 PCD VPD G 63 L/+ 64 N/∼
Grounding
24V (Same as screw No. 82) (Same as screw No. 62)
DI9 21 DI10 22
Instrument power supply 100 to 240V AC or Instrument power supply 24V DC
-
+ +
PCD 12 (Same as screw No. 62)
Note) Screw terminal No. 16, 32, 35, 36, 37, 51, 71, 74, 75, 79, 80 Multiple connector terminal No. 1, 2, 3, 4 not usable (connection not allowed)
24V supply for DIO
10
EXTERNAL CONNECTION DIAGRAM
COMPRESSION TERMINAL TYPE
1 AI1 2 SC 3 AI2 4 AI3 5 SC 6 AI4 7 AI5 8 SC 9 AI6 10 SC 11 VP 12 PC 13 DI9 14 DI10 15 DO9 16 DO10 17 MOD+ 18 MOD19 COM 20 VPD 21 PCD Note) Note) Note) Note) Note) Note) Note) 22 MI+2 23 MI-2 24 MI+3 25 MI-3 26 MI+4 27 MI-4 28 DO6 29 DO7 30 DO8 31 DIO-COM 32 DI6 33 DI7 34 DIO-COM 35 DI8 36 OPT+ 37 OPT38 COM 39 I+2 40 Io2 Rcj2 41 42 I-2
Manipulated output 1
Voltage input
Note) Note) Note)
VPD
VPD
24 V external supply
(+) (-)
Note)
PCD
VPD PCD
RS485 communication (Modbus) or T-link host communication
(+) (-) (COM)
24 V supply for DIO
PCD
External setting input
Note) Note) Note) Note) Note)
Process value input Voltage input
Rcj
(+) (−)
43 MI+1 44 MI-1 45 AO1 Note) 46 SC 47 AO2 48 AO3 49 SC 50 AO4 51 FLT 52 DO1 Note) 53 DO2 Note) 54 DO3 55 DO4 56 DO5 57 DI1 58 DIO-COM DI2 PCD 59 DI3 Note) 60 61 DIO-COM 62 DI4 Note) 63 DI5 I+1 b 64 Io1 A 65 66 Rcj1 I-1 B 67
G N/- L/+
∼
Thermocouple input
Resistance bulb input
Grounding
Instrument power supply 100 to 240VAC or Instrument power supply 24VDC
-
+
The area enclosed with a dotted line is the circuit within the main unit.
Note) Compression terminal No. 1, 6, 7, 9, 22, 23, 24, 25, 26, 27, 32, 36, 37, 38, 40, 41, 45, 52, 53, 60, 62 not usable (connection not allowed)
11
PDA1
[Note] Windows is the registered trade mark of Microsoft corporation. [Note] Modbus is a registered trademark of Schneider Electric Limited. [Note] Compact Flash is the registered trade mark of Sandisk corporation. [Note] Pentium is the registered trade mark of lntel corporation. [Note] Adobe and Acrobat are trademarks of Adobe Systems Incorporated.
Caution on Safety *Before using this product, be sure to read its instruction manual in advance.
Head Office
6-17, Sanbancho, Chiyoda-ku, Tokyo 102-0075, Japan http://www.fesys.co.jp/eng
Instrumentation Div. International Sales Dept.
No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187 http://www.fic-net.jp/eng
Information in this catalog is subject to change without notice.
Printed in Japan