0
登录后你可以
  • 下载海量资料
  • 学习在线课程
  • 观看技术视频
  • 写文章/发帖/加入社区
会员中心
创作中心
发布
  • 发文章

  • 发资料

  • 发帖

  • 提问

  • 发视频

创作活动
EDS11-162

EDS11-162

  • 厂商:

    FUJI(富士电机)

  • 封装:

  • 描述:

    EDS11-162 - Digital Controller COMPACT CONTROLLER M [CC-M] (FIXED FUNCTION/ STEP OUTPUT TYPE) - Fuji...

  • 数据手册
  • 价格&库存
EDS11-162 数据手册
Digital Controller COMPACT CONTROLLER M [CC-M] (FIXED FUNCTION/ STEP OUTPUT TYPE) PDC1 DATA SHEET The Compact Controller M (fixed function/step output type) is a single-loop process controller. Receiving 1 to 5V DC signals as well as those from thermocouples and resistance bulbs as input signals, it performs advanced controls such as PID control, square root extraction, and non-linear control. FEATURES 1. Single-loop controller with control output The controller has a single-loop control function. 2. High visibility ensured by color graphic display A color LCD is adopted for clear graphic displays such as bar graph and trend displays. 3. Networking (option) Communication can be carried out over our PLC-link (T-link) or Modbus (RS485) network. 4. Memory card (option) The data such as process input data and control output data can be saved in memory cards. FUNCTIONAL DIAGRAM External input terminal Personal computer Bar graph indicator To other controllers Communication terminal Valve position input (AI1) Linearize Filter A/D converter MV P I D Non-linear Process value input (PV1) R,A D/A converter External output terminal Control output (Pulse output: DO1, DO2) Valve position output (voltage:AO2,AO5) Compensated PV signal (AO3) Set point transmit signal (AO4) Manual mode output (M:DO6) Local mode output (DO7) Remote request (DO8) Fault output (FLT) High alarm output (DO9) Low alarm output (DO10) Deviation upper limit alarm (DO4) Deviation lower limit alarm (DO5) Rate of change upper/lower limit alarm (DO3) H L Pulse width conversion Internal input terminal 4 to 20mA, thermocouple/ resistance bulb conversion R-SV(PV2) Pulse input (DI1,DI2) Pulse input switching Command (DI9) Forced M command (DI10) PV tracking (DI7) R-ACK(DI8) Square-root extraction Limiter M Limiter SH SL R A.M M mode L mode M mode R C R mode Fault Alarm : Option FLT lamp EDS11-162 Date Aug. 19, 2005 PDC1 SPECIFICATIONS 1. Control Functions (1) PID control • Number of loops and PID: 1 loop (1 control output / 1PID) • Proportional band (P): 1.0 to 3276.7%, set at 3000.0% for delivery • Integration time (I): 0.1 to 3276.7 s, set at 3000.0 s for delivery • Derivative time (D): 0.0 to 900.0 s, set at 0.0 s for delivery (2) Computation cycle: 100 ms (3) Alarm function • Kinds : Each high/low of PV and SV, PV change rate alarm, high/low deviations. 2. Input Signals Performance in standard operating conditions (23± 2°C, 55± 10% RH, power supply voltage 100 V AC to 240 V AC power frequency 50/60 Hz, or 24 V DC, without vibration and external noise). 2-1 Analog input signal • Number of inputs: 3 (points used) • Inpute signal types: DC voltage, thermocouple (option), resistance bulb (option) One thermocouple input or one resistance bulb input are selectable in Code Symbol. (1) DC voltage/DC current • Open-angle input is assigned to AI1 in an unchangeable manner. • Input range: Selectable among 0 to 5 V DC, 1 to 5 V DC and 0 to 10 V DC Initial set before delivery : 1 to 5 V DC • Input accuracy: ± 0.1% of input span± 1 digit • Scaling (Engineering data conversion): Settable within a range from -32767 to 32767 4, 3, 2, 1 or 0 digit below decimal point is selectable. Initial set before delivery : 0.00% to 100.00% • Engineering unit: Settable in up to 8 characters Usable characters: Alphabets numerals, symbols such as +, – ,*,etc. • Input accuracy guarantee range: -5% to 105% of input range. However, minus inputs are excluded. • Maximum continuous permissible voltage: ± 35 V • Input resistance: 1 MΩ or more • Influence by ambient temperature: ± 0.1% FS/10°C or less. • Influence by power supply fluctuation: ± 0.1% FS or less. • Isolation: Non-isolated from internal circuit. • In case of current input: Shunt resistor need to be connected to the analog input terminal. (250 Ω shunt resistor is optional item) (2) Thermocouple (option) • Types and measurable ranges: * See Table 1. • Input accuracy: ± 0.2% FS ± 1 digit [Note]B type: ± 5% between 0 to 400˚C S and R type: ± 1%between 0 to 500˚C All type of TC: ± 5% under–100˚C • Reference junction compensation error: ± 1.0°C (provided measurable range is –50°C and higher) [Note]Reference junction compensation resistor is connected at external input terminal in case of thermocouple input is ordered. • Input accuracy guarantee range: –5% to 105% of input range • Input resistance: 1MΩ or more • Influence by signal source resistance: About 0.25 µV/Ω • Influence by ambient temperature: ± 0.2% FS/10°C ± 1°C or less. • Influence by power supply fluctuation: ± 0.2% FS ± 1˚C or less • Burnout detection: Provided • Isolation: Isolated from internal circuit. (3) Resistance bulb (option) • Types and measurable ranges: * See Table 1. • Input accuracy: ± 0.2% FS ± 1 digit • Input accuracy guarantee range: -5% to 105% of input range • Allowable wiring resistance: 10Ω or less per wire, provided wiring resistance must be equal among 3 wires (Zener barrier connection unallowable) • Influence by ambient temperature: ± 0.2% FS/10˚C or less. • Influence by power supply fluctuation: ± 0.2% FS or less • Burnout detection: Provided • Isolation: Isolated from internal circuit. [Note] FS: full span. • Sampling period: 100 ms 2-2 Digital input signal • Number of inputs: 6 inputs • Electrical specifications: No-voltage contact or transistor contact ON/0 V, OFF/24 V, ON current/about 8 mA Isolated from the internal circuit by photocoupler. Not isolated between each digital input and output. • Contact rating: 30 V DC, 10 mA or more 2 • Signal judgment: No-voltage contact Contact resistance; 200 Ω or less at ON, 100 kΩ or more at OFF Transistor contact 1V max at ON., leakage current 100µA max. at OFF 3. Output Signals Performance in standard operating conditions (23± 2°C, 55± 10% RH, power supply voltage 100 V AC to 240 V AC power frequency 50/60 Hz, or 24 V DC, without vibration and external noise). 3-1 Analog output signal (1) Auxiliary analog output • Number of outputs: 4 (points used) • Types of signal : Selectable among 0 to 5 V DC, 1 to 5 V DC and 0 to 10 V DC Initial set before delivery: 1 to 5 V DC • Output accuracy: ± 0.1% FS • Load resistance: 15 kΩ or more • Output guarantee range: • 1 to 5 VDC : –12.5% to 112.5% • 0 to 5 VDC : 0% to 112.5% • 0 to 10VDC : 0% to 105% • Influence by power supply fluctuation: ± 0.1% FS or less • Isolation : Non-isolated from internal circuit 3-2 Control output signal • Number of outputs: 1 pair Increasing pulse; DO1 Decreasing pulse; DO2 • Electrical specifications: Transistor open collector 1 V max. at ON, 10 µA max at OFF. Isolated from the internal circuit by photocoupler. Not isolated between each digital input and output. • Output rating : 30 V DC, 100 mA max. (resistive load) [Note] Control outputs should be crossed sequentially by an external sequence so that the increasing and decreasing pulse signals are not turned to ON at the same time. 3-3 Digital output signal • Number of outputs: 8 (points used) • Electrical specifications: Transistor open collector 1 V max. at ON, 10 µA max at OFF. Isolated from the internal circuit by photocoupler. Not isolated between each digital input and output. • Output rating : 30 V DC, 100 mA max. (resistive load) 3-4 Fault output signal (terminal symbol FLT) • Number of outputs: 1 output • Electrical specifications: Transistor open collector 1 V max. at ON, 10 µA max at OFF. Isolated from the internal circuit by photocoupler. Not isolated between each digital input and output. • Output rating : 30 V DC, 100 mA max. (resistive load) 4. Display • Display unit : 16 Colors graphic liquid crystal display, with CFL back light and contrast adjust function. • Contents of display: • Menu • Loop panel Bar graph display, digital display, etc. • Tuning screen • Trend screen • Alarm and alarm historical screen • Analog input/output and digital input/ output indication screen • Parameter setting screen 5. Setting and Operation (1) Set point setting method • Setting key : Up key/down key • Setting speed : About 40 s/FS • Setting resolution: 0.05% FS/each key press (2) Control output operation method • Operation key : Up key, down key (3) Operation mode • Selectable operation modes: C (or R), A and M modes [Note] C: Cascade mode (mode of operation according to external set value) R: Remote mode (mode of operation according to external set value) A: Auto mode (mode of operation according to the value set on front face of this controller) M: Manual mode (operation mode in which operator manipulates control output manually) [Supplement] In the C and R modes, operations are the same, i.e., only the markings on the nameplate are different. • Setting method : Selection is required in Code Symbol among the following. C-A-M A-M R-A-M • Operation mode changeover: Balance bumpless transfer from A to R and from A to C. Balanceless bumpless transfer in other mode changeover. [Note] Balance bumpless transfer is a mode in which the operator is required to balance each SV for transfer. Balanceless bumpless transfer is a mode in which the controller automatically balances each SV for transfer. 3 PDC1 (4) Security • Method • Password : Setting of a password : Settable in 4 numerals (within 0000 to ffff) Initial set before delivery: 0000 • Contents of security: Inhibition of parameter setting (5) Other setting items • Tag name : Settable in up to 8 characters Usable characters; alphabes, numerals, symboles such as +, – ,*,etc. 8. Operating and storage conditions • Installation site : Indoors • Operating temperature: 0 to 50˚C 0 to 40°C in case of multiple mounting Temperature change rate: Max. 10˚C / h • Transport and storage temperature: -20 to 70˚C (Temperature change rate: Max. 20˚C / h) • Operating humidity: 5 to 90% RH, condensation unallowable • Transport and storage humidity: 5 to 95% RH, condensation unallowable • Operating continuous vibration: 4.9 m/s2 or less • Transport and storage shock: Fall of 60cm max. in packed status 9. Power Failure and restart Function • Permissible duration of momentary power failure: 20 ms at 90V AC (100 V to 240 V AC only) [Note] In case of 24 V DC, system power supply unit (model: PXJ) is recommended to avoid power failure problem. • Behavior at power failure detection: Control stops at detection of power failure. • Power recovery mode: Selectable initial start and continuous start 10. Self-Diagnosis • Control and computation circuit failure: Monitoring with watchdog timer • Input signal failure: • Voltage/current input Monitoring of range over • Thermocouple and resistance bulb Monitoring of disconection • Behavior at failure: : FLT is indicated, FLT lamp lights, FLT output signal turns on, control stops and control output is OFF (Open-angle of valve is held). 11. Structure • Enclosure : Plastic (material: PC-ABS) • Finish color : Front frame and enclosure both gray • Flame resistance: UL94V-0 • Protection : Front face; IP54 (display unit and operation key) • External dimensions (width x height x depth): Screw terminal type 72 x 144 x 272 mm Compression terminal type 72 x 144 x 280 mm • Mass : 1.9 kg or less 6. Power Supply • Voltage rating : 100 V to 240 V AC/24 V DC [as specified in Code Symbol] • Allowable range: 85 V to 264 V AC/20 V to 30 V DC [as specified in Code Symbol] • Frequency : 47 to 63 Hz • Power consumption: 60 VA or less (100 V to 240 V AC)/ 30 W or less (24 V DC) [as specified in Code Symbol] • Power supply output voltage: (terminal symbol VP and PC) 20V to 30V DC,max. 40mA 7. General performance and characteristics • Insulation resistance: 500 V DC, 50 MΩ or more. • Dielectric strength: • 2,000 V AC for 1 minute between power terminal and ground terminal in case of 100 V to 240 V AC power supply • 500 V AC for 1 minute between power terminal and ground terminal in case of 24 V DC power supply. • 500 V AC for 1 minute between signal communication terminals and ground terminal • Rush current : 60 A or less. (100 V AC to 240 V AC power supply) • Clock : Set and display year, month, day, hour, minute, second Accuracy : ± 100 ppm (monthly gain/ loss about 4 minutes) except of time lag shorter than 1 s / power ON / OFF action. • Memory backup: • Protection by lithium battery. (expected battery life is about 2 years under room temperature) • Parameter and program are stored in non-volatile memory. 4 • Mounting method: Flush on indoor panel Vertical mounting as standard Tilted mounting allowed within backward angle 0° to 45°. • Data storage capacity: Memory card capacity 4MB 20MB 32MB Data storge about 180 thousand data about 900 thousand data about 1.35 million data 90° to 45° For panel cutout dimension, refer to Panel Cutout Dimensions • External terminal: Selectable in Code Symbol between the following. Screw terminal type (M3.5) Compression terminal type 12. Communications (option) 12-1 Modbus(R) protocol interface (option) • Communication mode: Host communications • Communication protocol: Modbus(R) protocol • Physical specifications: EIA RS485 • Communication mode: Two-wire, half-duplex, start-stop synchronous mode • Connection mode: Multi-drop connection • Communication speed: Selectable from 2.4, 4.8, 9.6, 19.2, and 38.4 kbps. Default setting: 19.2 kbps • Communication distance: Total extension; Max. 500 m • Data length: Fixed to 8 bits • Parity: Selectable from ODD, EVEN, or None. • Stop bit: Selectable from 1 or 2. • Insulation: Isolated from internal circuit • End of line resistor: 100 Ω (option) • Communication item: Parameter, measured value • RS232/RS485 converter (recommended item) Type: K3SC-10 (Insulated type by OMRON) 12-2 T-link interface (option) • Communication mode: Communication with upper level • High order communication: Connection with CPU capsule I/O transmission; 8 words output • Low order communication: None • Common item: Topology; Multidrop Communication speed; 500 kbps Communication distance; Max. 500 m in total extension distance Isolation; Not isolated from internal circuit Terminating resistor; 100 Ω (separately available) 13. Memory Card Interface (option) • Specification : Compact Flash® (Based on CFA) • Compatible memory card: 5 V flash memory card Capacity 4, 20 and 32 MB • Application : Process data logging (3 points) • Saving period : 1s to 2h [Note] The data of max. 16 points (4 screens) can be storaged at storage time as 1 s. • Format method: Dependent on this controller • Data readout : Readout by PC using PCMCIA card slot • Recommended memory card: Made by Sandisk corporation Sandisk compact Flash memory card is standardized and on the market. 14. Standards under Conformity (1) General safety: IEC 1010-1 (1990) EN 61010-1 (1993) (2) EMC : Emission EN 50081-2 (1994) Immunity EN 50082-2 (1995) [Caution on use] 1. Unlike the preceding models, a potentiometer interface (resistance input) for inputting the open angle of a motoroperated valve is not incorporated. For the above purpose, therefore, voltage input is required with a signal converter externally connected. Also, since open-angle input is assigned between AI1 and SC, this input will be indicated on the MV indicator. 2. Control output is assigned to the multi-connector section. So, a 34-pin multi-connector should be prepared depending on your specifications, referring to "Items to be ordered separately (items separately available)." 3. For control output, crossing interlock with relays or the like interlock is required so that both incremental and decremental pulse signals will not turn on simultaneously. 5 PDC1 Table 1 List of Thermocouple and Resistance Bulb Measurable range Input signal Thermocouple J J K K K R B T T E E S N U WRe5-26 PL2 Resistance bulb Pt100 00 Input type code Input range code Measurable range˚C 01 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 00 01 02 03 04 05 06 07 JPt100 08 09 10 11 12 13 14 0.0~400.0 0.0~800.0 0.0~400.0 0.0~800.0 0.0~1200.0 0.0~1600.0 0.0~1800.0 -200.0~200.0 -150.0~400.0 0.0~800.0 -200.0~800.0 0.0~1600.0 0.0~1300.0 -200.0~400.0 0.0~2300.0 0.0~1300.0 0.0~150.0 0.0~300.0 0.0~500.0 0.0~600.0 -50.0~100.0 -100.0~200.0 -200.0~600.0 -200.0~850.0 0.0~150.0 0.0~300.0 0.0~500.0 0.0~600.0 -50.0~100.0 -100.0~200.0 -200.0~600.0 SCOPE OF DELIVERY Controller, panel mounting bracket, instruction manual (depend on code symbols) Items to be ordered separately (items separately available) Item Terminating resistor (100 Ω) 34-pin multi-connector (Note 1) Type PDZR1001 PDZR2001 PDZC1001 PDZC2001 PDZC3001 PDZC4001 Shunt resistor (250 Ω) Communication cable (Note2) For screw terminals between PDC and PDC For screw terminals between PDC and PLC For screw terminals between PDC and PC For compression terminal between PDC and PDC For compression terminal between PDC and PLC For compression terminal between PDC and PC Extension case (under development) Printed instruction manual PDZX6101 (written in Japanese) for compact controller M (PDC1) Printed instruction manual PDZX7101 (written in English) for compact controller M (PDC1) Instruction manual in CD-ROM PDZQ1001 (common for Japanese and English) (Note 3) Fixture (Note 4) PDZA1001 Improved fixture 1 CD-ROM version instruction manual 1 Printed instruction manual 1 Printed instruction manual 1 PDZE2002 PDZK6xx1 PDZK5xx1 PDZK4xx1 PDZK3xx1 PDZK2xx1 PDZK1xx1 With M3.5 solderless terminal at both ends With M3.5 solderless terminal at both ends 9-pin connector on PC side With compression terminal at both ends With M3.5 solderless terminal on PLC side 9-pin connector on PC side For CC-F replacement 1 1 1 1 1 1 1 PDZS1001 PDZS2001 Specificatio For screw terminal For compression terminal Soldering type straight terminal Soldering type right-angle terminal Solderless type straight terminal Solderless type right-angle terminal For screw terminal For compression terminal Unit of sale 1 1 1 1 1 1 1 1 (Note 1) Screw terminal type required for using control output and digital input/output (see Outline Diagram). Prepare separately if needed. (Note 2) Transmission cable for T-link/Modbus communication. (Note 3) This CD-ROM contains the instruction manuals written in Japanese and English. (Note 4) An improved fixture adopted starting from the PDC-2. For the shape and dimensions, refer to Outline Diagram. Block diagram of electrical isolation Solid line shows isolation from the other units or circuits. Power supply Power supply unit DI / DO unit Ground Ground DO1 to DO10 DI1 to DI10 PV1 TC or RTD input unit AI / AO unit PV2 AI1 to AI6 (Note) AI1 is exclusively used for open-angle input. AO1 to AO5 Modbus Communication unit (Note) (Note) Not isolated from the analog input/output section in case of T-link. T-link 6 CODE SYMBOLS 1 2 3 4 5 6 7 8 9 10111213 1415 PDC 2- 10 1 1 1 2 A C D E A B C A R Y Description Equipment function With fixed function Number of control loops 1 loop (1 control output) External terminal M3.5 screw Compression terminal Input signal 1 to 5 V DC (DC4 to 20mA) Thermocouple : 1 Resistance bulb Pt100 : 1 Resistance bulb JPt100 : 1 Note 1 Power supply voltage 100 V to 240 V AC (usable range 85 V to 264 V AC), 50/60 Hz 24 V DC (usable range 20 V to 30 V DC) Setting method C-A-M type A-M type R-A-M type Backup operation unit None Communication function/memory card interface Notes 2 and 3 (Slave communication) (Master communication) (Memory card interface) Without Without Without Without Without With Modbus Without Without Modbus Without With T-link Without Without T-link Without With Y C Instruction manual None CD-ROM version instruction manual (common for both Japanese and English) Note 4 Note 1) For current input, conversion into a voltage is required using a shunt resistor. This resistor is separately available. Note 2) The communication cable and terminating resistor are separately available. Note 3) Memory card should be purchased from a dealer such as personal computer shop. Note 4) The relevant manual is stored in the PDF file format. For reading the manual, Adobe® Acrobat® Reader is required. The CD-ROM also contains the Acrobat® Reader setup program. Input signal and measurable range will meet the following specifications for product delivery. For specification of voltage input : 0.00 to 100.00% scale For specification of thermocouple : K thermocouple, measurable range 0.0 to 400.0°C For specification of resistance bulb : Measurable range 0.0 to 150.0°C with both Pt and JPt Y M C U A S 7 PDC1 OUTLINE DIAGRAM (screw terminal type) (Unit : mm) 67.5 Terminal Cover Panel Panel thickness 8mm or less Covering fixture 20 72 21.6 Fixture 272 16 Note) When there is any object like other instrument or floor below the controller, an open space of 100 mm min. is required between the bottom face of controller and such an object. OUTLINE DIAGRAM (compression type) (Unit : mm) 67.5 Panel thickness 8mm or less Panel Covering fixture Terminal Cover 20 100Min 137.5 134 280 Fixture 144 72 21.6 16 Note) When there is any object like other instrument or floor below the controller, an open space of 100 mm min. is required between the bottom face of controller and such an object. PANEL CUTOUT DIMENSIONS For mounting one unit For mounting multiple ”n” units 250 or more 250 or more 100Min 137.5 144 138 68 +0.7 0 (72.2 n-4) +1 0 8 138 Number of units n2 +1 0 +1 0 FIXTURE 50 16 160 205 9 PDC1 EXTERNAL CONNECTION DIAGRAM (Screw terminal type, M3.5 screw section) ThermoVoltage couple Resistance input input builb input (+) VPD b ○ 11 B ○ 12 A ○ 13 I+1 I-1 Io1 I+2 I-2 Io2 Note1) PCD FLT DO1 DI1 DI2 VST2 T1 T2 31 32 33 34 35 Note1) 36 Note1) 37 Note1) RS485 communication (Modbus) or T-link host communication Note1) 51 52 53 54 55 56 57 AO1 AO2 AO3 AO4 AO5 SC SC Note4) Note1) Note1) Note1) Note1) AI1 AI2 AI3 AI4 AI5 SC MI+1 71 72 73 74 75 76 77 78 79 80 81 82 83 Note1) Note1) Note1) Note1) 24V external supply (+) Voltage input Process value input (−) Rcj Voltage External input setting input 14 15 16 (+) (-) (COM) 24V external supply (-) 58 MOD+ SC MI-1 59 MODMI+2 60 VST MI-2 PC 61 VP 62 PCD VPD G 63 L/+ 64 N/∼ Grounding Note3) DO1 23 Note3) DO2 24 DO3 25 DO4 26 DO5 27 DO6 28 DO7 29 DO8 30 DO9 31 DO10 32 VPD 33 PCD 34 (Same as screw No. 34) DI1 13 DI2 14 DI3 15 DI4 16 DI5 17 DI6 18 DI7 19 DI8 20 + - MI+3 1 Note1) Note1) Note1) Note1) Instrument power source 100 to 240V AC or Instrument power source 24V DC + + (Same as screw No. 33) (Same as screw No. 34) MI-3 MI-4 AO1 AO2 AI1 AI2 AI3 AI4 SC 2 4 MI+4 3 5 (Same as screw No.51) 6 (Same as screw No.52) 7 (Same as screw No.71) 8 (Same as screw No.72) 9 (Same as screw No.73) 10 (Same as screw No.74) 11 (Same as screw No.55,57,76) 24V power source for DIO 24V (Same as screw No.82) DI9 21 DI10 22 PCD (Same as screw No.62) PCD 12 (Same as screw No.62) Note 1) Screw terminals No. 16, 35, 36, 37, 51, 72, 73, 74, 75, 77, 78, 79, 80 and MULTI-CONNECTOR No. 1, 2, 3, 4 do not used (can't connect). Note 2) Control output is allocated to MULTI-CONNECTOR No. 23 and 24. Prepare a mulit-connector (any one below) separately. PDZC1001 PDZC2001 PDZC3001 PDZC4001 Soldering type straight terminal Soldering type right-angle terminal Solderless type straight terminal Solderless type right-angle terminal Note 3) Control output should be cross-connected to each other, externally. + M L1 L2 Do1 Do2 Note 4) Connect open-angle input between screw terminals Nos. 71 and SC or multi-connector pin 7 and 11. 10 EXTERNAL CONNECTION DIAGRAM (Compression terminal type) Voltage input 24V external supply (+) (-) VPD PCD RS485 (+) communication (-) (Modbus) or T-link host communication (COM) 24V power for DIO 1 AI1 2 SC 3 AI2 4 AI3 5 SC 6 AI4 7 AI5 8 SC 9 AI6 10 SC 11 VP 12 PC 13 DI9 14 DI10 15 DO9 16 DO10 17 MOD+ 18 MOD19 COM 20 VPD 21 PCD Note3) Note1) Note1) Note1) Note1) Note1) VPD Note1) Note1) Note1) Note1) Note1) Note1) Note1) PCD Note1) Note1) Note1) External setting input Note1) Note1) 22 MI+2 23 MI-2 24 MI+3 25 MI-3 26 MI+4 27 MI-4 28 DO6 29 DO7 30 DO8 31 DIO-COM PCD 32 DI6 33 DI7 34 DIO-COM 35 DI8 36 OPT+ 37 OPT38 COM 39 I+2 40 Io2 41 Rcj2 42 I-2 Process value input Note1) 43 Note1) 44 Note1) 45 VPD Note1) Note1) Note1) Rcj (+) (−) b A B 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 MI+1 MI-1 AO1 SC AO2 AO3 SC AO4 FLT DO1 Note2) DO2 Note2) DO3 DO4 DO5 DI1 DIO-COM DI2 PCD DI3 DIO-COM DI4 DI5 I+1 Io1 Rcj1 I-1 G N/- L/+ Grounding ∼ Voltage Thermoinput couple input Resistance bulb input Instrument power source 100 to 240V AC or Instrument power source 24V DC - + The area enclosed with a dotted line is the circuit within the main unit. Note 1) Compression terminal No. 3, 4, 6, 7, 9, 22, 23, 24, 25, 26, 27, 32, 36, 37, 38, 40, 41, 43, 44, 45, 60, 62, 63 donot be use (can’t connect). Note 2) Control output should be cross-connected to each other, externally. + M L1 L2 DO1 DO2 Note 3) Cannect open-angle input between compression terminals Nos. 1 and SC. 11 PDC1 [Note] Windows® is the registered trade mark of Microsoft corporation. [Note] Modbus® is a registered trademark of Schneider Electric Limited. [Note] Compact Flash® is the registered trade mark of Sandisk corporation. [Note] Pentium® is the registered trade mark of lntel corporation. [Note] Adobe® and Acrobat® are trade marks of Adobe Systems Incorporated. Caution on Safety *Before using this product, be sure to read its instruction manual in advance. Head Office 6-17, Sanbancho, Chiyoda-ku, Tokyo 102-0075, Japan http://www.fesys.co.jp/eng Instrumentation Div. International Sales Dept. No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187 http://www.fic-net.jp/eng Information in this catalog is subject to change without notice. Printed in Japan
EDS11-162 价格&库存

很抱歉,暂时无法提供与“EDS11-162”相匹配的价格&库存,您可以联系我们找货

免费人工找货