PUM Series Multi-loop module type Temperature controller DATA SHEET
EvEnt input/output modulE [pumE]
PUME
PUME is a digital input / output module used as an auxiliary input / output of control modules. Each module, 30mm wide, is equipped with 8 points of digital input, 8 points of digital output, and high-speed RS-485 port. By connecting with PUM control modules, it realizes a compact and highperformance system.
FEAtuRES
I. User-friendly structure and functions 1. Lateral connection : Max.16 units + control module 16 units = total 32 units Simple wiring for power supply and communication 2. Detachable structure: Terminal block, main unit, and the base part → Easy wiring with detachable terminal blcok → Main units exchangeable without re-wiring 3. Status LED for each input/output → Easy to monitor input / output status 4. Smart loader communication: Connect one module and all connected modules are able to communicate using a loader software. II. Large scale system using high speed RS-485 1. Modbus RTU protocol for large volume communication 2. High-speed communication: Maximum 115.2kbps 3. Highly-efficient communication: Parameters dispersed on the address map are re-allocated to contiguous address III. Various functions to extend control module functions 1. Digital input (Optional feature : logic operation NOT/AND/OR) - Run / Standby switch - Auto / Remote / Manual switch - Start timer - Others 2. Digital output (Optional feature : logic operation NOT/AND/OR) - Control output (including distribution output) - Alarm output - Timer output - Others
SYStEm SpECiFiCAtion
1. Product type: M ulti-loop module type temperature controller 2. Module type 1) Analog module: Total maximum 16 units a) Control module (4 loop/unit) b) Extended input/output module - Analog input/output module (Input/output 4 points/unit) - Analog input module (Input 4 points/unit) - Analog output module (output 4 points/unit) 2) Extended input/output (digital) module: Maximum 16 units - Event input/output module (Input/output ; 8 points/unit) 3) Enhanced communication module: 1 unit 3. Connecting method: Lateral connecting with connectors - For power supply and RS-485 communication, any one of connected modules is required to be connected. 4. No. of loop, input/output 1) Control loop: Max. 64 2) No.of input / output: DI 128 points / DO 128 points
EDS11-167a
Date Apr. 1, 2011
PUME
EVENT INPUT/OUTPUT MODULE SPECIFICATION
1. General specification
(1) Power supply: 24V DC ±10% (2) Power consumption: Max. 3.2 W (135 mA) [when 24V DC is applied] (3) Insulation resistance: 20MΩ or more (500V DC) (4) Withstand voltage: Power supply ↔ digital input ↔ digital output ↔ communication terminal 1000V AC 1 min. Others (digital input between blocks, digital output between blocks) 500V AC 1 min. (5) Applied standards: UL, C-UL, CE marking, RoHS directive [Pending for UL, C-UL marking]
(7) No. of connectable units: 33 units (master and slave) (32 units if any modules other than PUM series are included in slaves.) (8) Data format: Data bit; 8, parity; even / odd / none (9) Protocol: Modbus RTU compatible (10) Insulation: No insulation with loader communication port Functional insulation with any other input / output
4.2 Loader communication (RS-232C) interface
(1) Communication standards: RS-232C compatible (2) No. of port: 1 port (3) Communication, synchro method: Half-duplex, asynchronous cycle (4) Communication speed: 19.2kbps (fixed) (5) Data format: Data bit 8, no parity (6) Protocol: Modbus RTU compatible (7) Connection method: 2.5 diameter mini-plug / jack [on the front of the module] (Common cable with PXG, PXH) (8) Insulation: No insulation with RS-485 Functional insulation with any other input / output
2. Digital Input
(1) No. of input: 8 points (4 points/common × 2 blocks) (2) Input type: Voltage contact input, sink/source common (bidirectional) (3) Input rating: 24V DC, input impedance approx. 4.7kΩ (4) Input judgment: ON judgment: 16 to 26.4V DC OFF judgment: 0 to 5V DC (5) Input read cycle (min. pulse width): 200ms (6) Insulation: Functional insulation with internal circuit (7) Option: NOT/AND/OR logic operation, Latch action
5. Display, configuration 5.1 Display
(1) Display: Status display LED (2 colors × 2 points + 16 points) (2) Display contents: RUN/FAULT, RS-485 TX/RX, Input × 8 points, output × 8 points
3. Digital Output
(1) No. of output: 8 points (4 points/common × 2 blocks) (2) Output type: Select from a) and b) according to model type specification a) Relay contact output - Contact structure: SPST contact - Contact capacity: 220V AC / 30V DC, 1A - Insulation: Functional insulation with internal circuit b) Transisitor open collector (sink) output - Rating: 24V DC, 100mA (Residual voltage when power is ON: 1.5V DC or less) - Insulation: Functional insulation with internal circuit (3) Option: C ontrol output/Event output selection, NOT/AND/OR logic operation, Latch action
5.2 Setting device
(1) Setting device: Rotary SW × 1 [on the front of the module] (2) Set contents: RS-485 Station No. (Station No.= setting value + 17)
6. Power outage
(1) Impact of power outage: Outage of 2ms or less ; no impact (2) Operation after power outage: Start from the first step (cold start) (3) Memory backup: Nonvolatile memory (EEPROM) No. of update ; 100,000
7. Self diagnosis 4. Communication function 4.1 RS-485 interface
(1) Communication standards: RS-485 compatible (2) No. of port: 1 port (3) Communication, synchro method: Two-wire, half-duplex, asynchronous cycle (4) Communication speed: 9.6k, 19.2k, 38.4k, 115.2kbps (5) Communication distance: 1km (38.4kbps or less), 250m (115.2kbps) (6) Recommended cable: KPEV-SB 0.5sq-equivalent Diagnosis method: Program error monitoring by watch dog timer
8. Structure
(1) Installation method: DIN rail mounting or mounting with M3 screws inside a cabinet (2) Dimensions: 30 (W) × 100 (H) × 85 (D) mm (excluding terminal cover and projected part) (3) Weight: Approx. 200 g
2
(4) Extrenal terminal - Digital input / digital output: Detachable terminal block (M3 screw × 20 terminals) - Power supply connection: Terminal block on the base part (M3 screw × 2 terminals) Power is supplied via side connectors in case of lateral connecting. (Max. 33 units) - RS-485 communication connection: Terminal block on the base part (M3 screw × 3 terminals) RS-485 communication is connected via side connectors in case of lateral connecting. - Loader communication port: 2.5 diameter mini-plug / jack [on the front of the module] (5) Case material: Polyphenylene oxide (flame retardant grade : UL94V-0 equivalent) (6) Case color: Case ; red Terminal, base part ; black (7) Protection - Body: IP20 grade protection (ventilation slits on the top and the bottom of the body) - Terminal: IP00 grade protection, terminal cover is available as an option
10. Transporting, storage condition (packing condition)
(1) Storage temperature: -20 to 60°C (2) Ambient humidity: 90%RH or less (no condensing) (3) Vibration: 10 to 70Hz, 9.8m/s2 (1G) or less (4) Shock: 294m/s2 (30G) or less
11. Packing list
Temperature controller: 1unit Instruction manual: 1 copy
12. Loader software
(1) Distribution medium: Free download from Fuji Electric Systems HP (http://www.fic-net.jp/eng/index. html) (2) Recommended operating environment PC: DOS/V (PC-AT compatible) OS: Windows XP (operation confirmed in Japanese / English) RAM: 256M bytes or more Free space on the hardware: 500M bytes or more Display resolution: 1024 × 768 or over Serial interface: RS-232C 1 port (without RS-232C, USB serial converter cable required) (3) Connection with PUM Via loader interface on the front face of the module (special cable available from Fuji is required) or via RS-485
9. Normal operating condition
(1) Ambient temperature*: -10 to 50°C * “Ambient temperature” is the temperature underneath the controller inside the equpiment or the cabinet where the controller is installed. (2) Ambient humidity: 90% RH or less (non condensing) (3) Vibration: 10 to 70Hz, 9.8m/s2 (1G) or less
3
PUME
CODE SYMBOLS
[Event input/ouput module]
12345678 9 10
Digit
P UM
YY1
0
Digit Description 4 < Module type > Event input/output module [Di 8 points / Do 8 points] 5 < Output type > Transisitor open collector (sink) output Relay contact output 10 Japanese English
E C R A B
12345678
Digit
[Accessories]
Digit Description 6 RS-485 terminating resistance 7 DIN rail mounting end plate 8 Side conneting terminal cover (right & left 1 set) Front face screw terminal cover Loader connecting cable (RS-232C)
P UM Z *
A A A A L
0 0 0 0 0
1 2 3 4 1
[Table 1] Insulation block diagram
Power Loader communication port RS-485 communication port Di1 to 4 Di5 to 8 Do1 to 4 Do5 to 8
Functional insulation (1000V AC) Functional insulation (500V AC)
4
OUTLINE DIAGRAM (Unit : mm)
Front terminal cover (Option)
(10)
Base part (Main unit is detached)
85 Hole for screw mounting
30
Terminal block (at attach/detach)
LOADER
STATION
1.5
6
100
50 DIN rail Terminal screw M3 (30) Hole for screw mounting Main unit (at attach/detach) Locking tab
6.1
Terminal screw M3
5
At mounting to the DIN rail
Dimensions for screw mounting
2-M3 (30) 9±0.2
(8)
Notice at the installation
Please keep the distance of 30mm from this instrument to radiate. [50mm is recommended]
88.5±0.2
(100)
(3)
30 +0.7 +0.2
30 or more
30 or more
5
PUME
TERMINAL CONNECTION DIAGRAM
Loader interface plug (RS-232C) 3 TX 2 RX 1 GND
φ2.5 3-pole miniature plug
LOADER
STATION
Di4 Di3 Di2 Di1
21 22 23 24
21
11 12 13 14 15 16 17 18 19 20
Digital input 1 to 4
22 23 24
Digital output 1 to 4
Transistor O.C. (SINK)
24V DC
11
Relay
COM Do1 Do2 Do3 Do4
COM Do1 Do2 Do3 Do4
11 12 13 14 15
L L L L
12 13 14 15
25
24V DC Di8 Di7 Di6 Di5
26 27 28 29
25 26
Digital input 5 to 8
27 28 29
Digital output 5 to 8
Transistor O.C. (SINK)
24V DC
16
Relay
COM Do5 Do6 Do7 Do8
COM Do5 Do6 Do7 Do8
16 17 18 19 20
L L L L
17 18 19 20
30
24V DC
30
Base part
Power
1 2
1 3 4
2 5
24V DC Communication RS485
3
A(+) B(-)
6
+
4
-
5
SG
Operation parameter
Parameter (name) Run/Standby switch Digital input latch releases command Digital output latch releases command 0: 1: 0: 1: 0: 1: Read/write date setting range Run Standby OFF Release latch OFF Release latch Factory default 0 (RUN) 0 (OFF) 0 (OFF) Registor No. 40021 40022 40023
Communication parameter
Parameter (name) RS-485 Parity setting Read/write date setting range 0: NONE 1: ODD 2: EVEN 0 to 25 (×20ms) 0: Read only 1: Read/Write 0: 9.6kbps 1: 19.2kbps 2: 38.4kbps 3: Forbidden 4: 115.2kbps 0: PUMC not connected (RS485 Enable) 1: PUMC connected (RS485 Disable) Factory default 0 (NONE) Registor No. 40111
RS-485 Response interval time RS-485 Communication permission RS-485 Communication speed
1 1 (R/W) 1 (9.6kbps)
40113 40114 40115
Enhanced communication module (PUMC) connection
0
40116
Configuration parameter
Parameter (name) FAULT output set value Standby output set value Standby mode setting LED2 Lamp Allocation Read/write date setting range 0: HOLD 1: OFF 0000 to FFFF 0: DI=Input value, DO=Standby output set value 1: DI=All OFF, DO=Standby output set value 0 to 2 Factory default 0 (HOLD) 0000 0 1 Registor No. 40260 40268 40270 40222
7
PUME
DI parameter
Parameter (name) DI1 Input option Read/write date setting range 0 to 15 (bit data : 0000 to 1111) bit0 : LATCH bit1 : NOT bit2 : AND bit3 : OR 0000 to 00FF 0000 to 00FF 0 to 15 (bit data : 0000 to 1111) 0000 to 00FF 0000 to 00FF 0 to 15 (bit data : 0000 to 1111) 0000 to 00FF 0000 to 00FF 0 to 15 (bit data : 0000 to 1111) 0000 to 00FF 0000 to 00FF 0 to 15 (bit data : 0000 to 1111) 0000 to 00FF 0000 to 00FF 0 to 15 (bit data : 0000 to 1111) 0000 to 00FF 0000 to 00FF 0 to 15 (bit data : 0000 to 1111) 0000 to 00FF 0000 to 00FF 0 to 15 (bit data : 0000 to 1111) 0000 to 00FF 0000 to 00FF Factory default Registor No. 0 (bit data 0000) 40701
DI1 DI1 DI2 DI2 DI2 DI3 DI3 DI3 DI4 DI4 DI4 DI5 DI5 DI5 DI6 DI6 DI6 DI7 DI7 DI7 DI8 DI8 DI8
Input Input Input Input Input Input Input Input Input Input Input Input Input Input Input Input Input Input Input Input Input Input Input
logic operation logic operation option logic operation logic operation option logic operation logic operation option logic operation logic operation option logic operation logic operation option logic operation logic operation option logic operation logic operation option logic operation logic operation
AND OR AND OR AND OR AND OR AND OR AND OR AND OR AND OR
0000 0000 0 (bit 0000 0000 0 (bit 0000 0000 0 (bit 0000 0000 0 (bit 0000 0000 0 (bit 0000 0000 0 (bit 0000 0000 0 (bit 0000 0000
data 0000)
data 0000)
data 0000)
data 0000)
data 0000)
data 0000)
data 0000)
40703 40704 40705 40707 40708 40709 40711 40712 40713 40715 40716 40717 40719 40720 40721 40723 40724 40725 40727 40728 40729 40731 40732
8
DO parameter
Parameter (name) DO1 Output type DO1 DO1 DO1 DO1 Master module St. No. Master module Ch. No. BIT position Output option Read/write date setting range 0: Event output 1: Control output 0 to 255 1 to 4 0000 to 00FF 0 to 15 (bit data : 0000 to 1111) bit0 : LATCH bit1 : NOT bit2 : AND bit3 : OR 0000 to 00FF 0000 to 00FF -100.0 to 100.0% -100.0 to 100.0% 1 to 120 sec. 0.0 to 100.0% 0.0 to 100.0% 0 to 3 0: Event output 1: Control output 0 to 255 1 to 4 0000 to 00FF 0 to 15 (bit data : 0000 to 1111) 0000 to 00FF 0000 to 00FF -100.0 to 100.0% -100.0 to 100.0% 1 to 120 sec. 0.0 to 100.0% 0.0 to 100.0% 0 to 3 0: Event output 1: Control output 0 to 255 1 to 4 0000 to 00FF 0 to 15 (bit data : 0000 to 1111) 0000 to 00FF 0000 to 00FF -100.0 to 100.0% -100.0 to 100.0% 1 to 120 sec. 0.0 to 100.0% 0.0 to 100.0% 0 to 3 0: Event output 1: Control output 0 to 255 1 to 4 0000 to 00FF 0 to 15 (bit data : 0000 to 1111) 0000 to 00FF 0000 to 00FF -100.0 to 100.0% -100.0 to 100.0% 1 to 120 sec. 0.0 to 100.0% 0.0 to 100.0% 0 to 3 Factory default Registor No. 0 (Event output) 40401 0 1 0001 0 (bit data 0000) 40402 40403 40404 40405
DO1 DO1 DO1 DO1 DO1 DO1 DO1 DO1 DO2 DO2 DO2 DO2 DO2 DO2 DO2 DO2 DO2 DO2 DO2 DO2 DO2 DO3 DO3 DO3 DO3 DO3 DO3 DO3 DO3 DO3 DO3 DO3 DO3 DO3 DO4 DO4 DO4 DO4 DO4 DO4 DO4 DO4 DO4 DO4 DO4 DO4 DO4
Output logic operation AND Output logic operation OR Scaling base Scaling span Proportion cycle Lower limits Upper limits Limit type Output type Master module St. No. Master module Ch. No. BIT position Output option Output logic operation AND Output logic operation OR Scaling base Scaling span Proportion cycle Lower limits Upper limits Limit type Output type Master module St. No. Master module Ch. No. BIT position Output option Output logic operation AND Output logic operation OR Scaling base Scaling span Proportion cycle Lower limits Upper limits Limit type Output type Master module St. No. Master module Ch. No. BIT position Output option Output logic operation AND Output logic operation OR Scaling base Scaling span Proportion cycle Lower limits Upper limits Limit type
0000 0000 0.0 100.0 30 0.0 100.0 0 0 (Event output) 0 1 0002 0 (bit data 0000) 0000 0000 0.0 100.0 30 0 100.0 0 0 (Event output) 0 1 0004 0 (bit data 0000) 0000 0000 0.0 100.0 30 0.0 100.0 0 0 (Event output)
40407 40408 40409 40410 40411 40412 40413 40414 40415 40416 40417 40418 40419 40421 40422 40423 40424 40425 40426 40427 40428 40429 40430 40431 40432 40433 40435 40436 40437 40438 40439 40440 40441 40442 40443
0 40444 1 40445 0008 40446 0 (bit data 0000) 40447 0000 40449 0000 40450 0.0 40451 100.0 40452 30 40453 0.0 40454 100.0 40455 0 40456
9
PUME
DO parameter
Parameter (name) DO5 Output type DO5 DO5 DO5 DO5 DO5 DO5 DO5 DO5 DO5 DO5 DO5 DO5 DO6 DO6 DO6 DO6 DO6 DO6 DO6 DO6 DO6 DO6 DO6 DO6 DO6 DO7 DO7 DO7 DO7 DO7 DO7 DO7 DO7 DO7 DO7 DO7 DO7 DO7 DO8 DO8 DO8 DO8 DO8 DO8 DO8 DO8 DO8 DO8 DO8 DO8 DO8 Master module St. No. Master module Ch. No. BIT position Output option Output logic operation AND Output logic operation OR Scaling base Scaling span Proportion cycle Lower limits Upper limits Limit type Output type Master module St. No. Master module Ch. No. BIT position Output option Output logic operation AND Output logic operation OR Scaling base Scaling span Proportion cycle Lower limits Upper limits Limit type Output type Master module St. No. Master module Ch. No. BIT position Output option Output logic operation AND Output logic operation OR Scaling base Scaling span Proportion cycle Lower limits Upper limits Limit type Output type Master module St. No. Master module Ch. No. BIT position Output option Output logic operation AND Output logic operation OR Scaling base Scaling span Proportion cycle Lower limits Upper limits Limit type Read/write date setting range 0: Event output 1: Control output 0 to 255 1 to 4 0000 to 00FF 0 to 15 (bit data : 0000 to 1111) 0000 to 00FF 0000 to 00FF -100.0 to 100.0% -100.0 to 100.0% 1 to 120 sec. 0.0 to 100.0% 0.0 to 100.0% 0 to 3 0: Event output 1: Control output 0 to 255 1 to 4 0000 to 00FF 0 to 15 (bit data : 0000 to 1111) 0000 to 00FF 0000 to 00FF -100.0 to 100.0% -100.0 to 100.0% 1 to 120 sec. 0.0 to 100.0% 0.0 to 100.0% 0 to 3 0: Event output 1: Control output 0 to 255 1 to 4 0000 to 00FF 0 to 15 (bit data : 0000 to 1111) 0000 to 00FF 0000 to 00FF -100.0 to 100.0% -100.0 to 100.0% 1 to 120 sec. 0.0 to 100.0% 0.0 to 100.0% 0 to 3 0: Event output 1: Control output 0 to 255 1 to 4 0000 to 00FF 0 to 15 (bit data : 0000 to 1111) 0000 to 00FF 0000 to 00FF -100.0 to 100.0% -100.0 to 100.0% 1 to 120 sec. 0.0 to 100.0% 0.0 to 100.0% 0 to 3 Factory default Registor No. 0 (Event output) 40457 0 1 0010 0 (bit data 0000) 0000 0000 0.0 100.0 30 0.0 100.0 0 0 (Event output) 0 1 0000 0 (bit data 0000) 0000 0000 0.0 100.0 30 0.0 100.0 0 0 (Event output) 0 1 0000 0 (bit data 0000) 0000 0000 0.0 100.0 30 0.0 100.0 0 0 (Event output) 40458 40459 40460 40461 40463 40464 40465 40466 40467 40468 40469 40470 40471 40472 40473 40474 40475 40477 40478 40479 40480 40481 40482 40483 40484 40485 40486 40487 40488 40489 40491 40492 40493 40494 40495 40496 40497 40498 40499
0 40500 1 40501 0000 40502 0 (bit data 0000) 40503 0000 40505 0000 40506 0.0 40507 100.0 40508 30 40509 0.0 40510 100.0 40511 0 40512
10
Internal DO data area parameter
Internal Internal Internal Internal Internal Internal Internal Internal Internal Internal Internal Internal Internal Internal Internal Internal Parameter (name) DO data area 1 DO data area 2 DO data area 3 DO data area 4 DO data area 5 DO data area 6 DO data area 7 DO data area 8 DO data area 9 DO data area 10 DO data area 11 DO data area 12 DO data area 13 DO data area 14 DO data area 15 DO data area 16 Read/write date setting range Event output 1: ON 0: OFF Control output 0.00 to 100.00 Factory default 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Registor No. 41001 41002 41003 41004 41005 41006 41007 41008 41009 41010 41011 41012 41013 41014 41015 41016
Monitor parameter
Parameter (name) System FAULT status DO calculated result monitor DI calculated result monitor DI terminal monitor 0000 0000 0000 0000 to to to to Read/write date setting range FFFF FFFF FFFF FFFF Factory default Registor No. 30064 31002 31001 31003
11
PUME
Caution on Safety *Before using this product, be sure to read its instruction manual in advance.
International Sales Div Sales Group Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome, Shinagawa-ku, Tokyo 141-0032, Japan http://www.fujielectric.com Phone: 81-3-5435-7280, 7281 Fax: 81-3-5435-7425 http://www.fjielectric.com/products/instruments/ Information in this catalog is subject to change without notice.
Printed in Japan