PUM Series Multi-loop module type Temperature controller DATA SHEET
EnhancEd communication modulE (PRoFiBuS) [PumcP]
PUMCP
PUMCP is a communication module, which connects module type temperature controller PUM series with PROFIBUS system. Compatible with PROFIBUS DP-V0, and designed for high-speed communication at the maximum speed of 12Mbps. Being able to up to 16 units (64 channel) of PUMA (control module), PUMCP requires minimum wiring, less space, and saves labor for engineering.
FEatuRES
I. Program-less connection to PROFIBUS 1. PROFIBUS DP-V0 compatible High-speed communication at max.12Mbps 2. Access to all parameters of control module (PUMA/ PUMB) via PROFIBUS 3. High-speed data communication with connected control modules (PUMA/PUMB) - Quick data importing and setting data reflection II. User-friendly structure and functions 1. Lateral connection : Max.16 units (64 channels) + event input/output module 16 units = total 32 units Simple wiring for power supply and communication 2. Detachable structure: Terminal block, main unit, and the base part → Easy wiring with detachable terminal blcok → Main units exchangeable without re-wiring
EnhancEd communication modulE (PRoFiBuS) SPEciFication
1. General specification
(1) Power supply: 24V DC ±10% (2) Power consumption: Max. 3.2 W (135 mA) [when 24V DC is applied] (3) Insulation resistance: 20MW or more (500V DC) (4) Withstand voltage: Power supply ↔ loader communication 1000V AC 1 min. Power supply ↔ SLD/FG terminal, PROFIBUS communication 1000V AC 1 min. (5) Applied standards: UL, C-UL, CE Marking, RoHS directive [Pending for UL and C-UL]
SYStEm SPEciFication
1. Product type: M ulti-loop module type temperature controller 2. Module type 1) Analog module: Total maximum 16 units a) Control module (4 loop/unit) b) Extended input/output module - Analog input/output module (Input/output 4 points/unit) - Analog input module (Input 4 points/unit) - Analog output module (output 4 points/unit) 2) Extended input/output (digital) module: Maximum 16 units - Event input/output module (Input/output ; 8 points/unit) 3) Enhanced communication module: 1 unit 3. Connecting method: Lateral connecting with connectors - For power supply and RS-485 communication, any one of connected modules is required to be connected. 4. No. of loop, input/output 1) Control loop: Max. 64 2) No.of input / output: DI 128 points / DO 128 points
2. PROFIBUS communication module 2.1 PROFIBUS communication
(1) Compliant version: P ROFIBUS DP-V0 (Cyclic communication) (2) Station type: Slave device (3) Communication speed and distance
Speed Distance 9.6,19.2, 93.75 kbps 1200m or less 187.5 kbps 100m or less 500 kbps 400m or less 1.5Mbps 200m or less 3M,6M, 12Mbps 100m or less
(4) Station number: Settable station number 1 to 99 (5) Communication data length (Cyclic communication)
Remote input/output bits 64 bits 128 bits 256 bits 512 bits 864 bits Remote input/output words 8 words 16 words 32 words 64 words 108 words
(6) Connecting cable: Type A compatible cable for PROFIBUS (7) Connecting method: M3 screw terminal block (8) Termination resistace: External (220W, 1/2W) or depends on the internal SW setting.
EDS11-172a
Date Apr. 1, 2011
PUMCP
2.2 Display, configuration
Status display LED (2 colors × 2 points + 1 point) (2) Display contents: RUN/FAULT, control module connection status (TX/RX), PROFIBUS status (ONL) (3) Setting device and set contents (1) Display:
Setting device Front Inside Rotary SW × 2 Dip SW (3bits) × 1 Set contents PROFIBUS Station No. setting Word setting of data exchange
(2) Ambient humidity: 90% RH or less (non condensing) (3) Vibration: 10 to 70Hz, 9.8m/s2 (1G) or less
7. Transporting, storage condition (packing condition)
(1) Storage temperature: -20 to 60°C (2) Ambient humidity: 90%RH or less (no condensing) (3) Vibration: 10 to 70Hz, 9.8m/s2 (1G) or less (4) Shock: 294m/s2 (30G) or less
8. Packing list 3. Power outage
(1) Impact of power outage: Outage of 2ms or less ; no impact (2) Operation after power outage: Start from the first step (cold start) (3) Memory backup: Nonvolatile memory (EEPROM) No. of update ; 100,000 Temperature controller: 1unit Instruction manual: 1 copy
9. Loader software
(1) Distribution medium: Free download from Fuji Electric Systems HP (http://www.fic-net.jp/eng/index. html) (2) Recommended operating environment PC: DOS/V (PC-AT compatible) OS: Windows XP (operation confirmed in Japanese / English) RAM: 256M bytes or more Free space on the hardware: 500M bytes or more Display resolution: 1024 × 768 dots or over Serial interface: RS-232C 1 port (without RS-232C, USB serial converter cable required) (3) Connection with PUM Via loader interface on the front face of the module (special cable available from Fuji is required)
4. Self diagnosis
Diagnosis method: Program error monitoring by watch dog timer
5. Structure
(1) Installation method: DIN rail mounting or mounting with M3 screws inside a cabinet (2) Dimensions: 30 (W) × 100 (H) × 85 (D) mm (excluding terminal cover and projected part) (3) Weight: Approx. 200 g (4) Extrenal terminal - PROFIBUS communication: Detachable terminal block (M3 screw × 20 terminals) - Power supply connection: Terminal block on the base part (M3 screw × 2 terminals) Power is supplied via side connectors in case of lateral connecting. (Max. 33 units) - Loader communication port: 2.5 diameter mini-plug / jack [on the front of the module] (5) Case material: Polyphenylene oxide (flame retardant grade : UL94V-0 equivalent) (6) Case color: Case ; red Terminal, base part ; black (7) Protection - Body: IP20 grade protection (ventilation slits on the top and the bottom of the body) - Terminal: IP00 grade protection, terminal cover is available as an option
codE SYmBolS
[Enhanced communication module]
Digit
12345678 9 10
P UM
YY1
0
Digit Description 4 < Module type > Enhanced communication module 5 < Communication function > PROFIBUS communication 10 < Operation manual > Japanese English
Digit
C P A B
12345678
[Accessories]
Digit Description 6 DIN rail mounting end plate 7 Side conneting terminal cover (right & left 1 set) 8 Front face screw terminal cover Loader connecting cable (RS-232C)
P UM Z *
A02 A03 A04 L01
[table 1] insulation block diagram
Power Loader communication port
Functional insulation (1000VAC) Functional insulation (500VAC)
6. Normal operating condition
(1) Ambient temperature*: -10 to 50°C * “Ambient temperature” is the temperature underneath the controller inside the equpiment or the cabinet where the controller is installed.
PROFIBUS communication
2
outlinE diaGRam (unit : mm)
Front terminal cover (Option)
(10)
Base part (Main unit is detached)
85 Hole for screw mounting
30
Terminal block (at attach/detach)
STATION No. LOADER ×10
×1
1.5
6
100
50 DIN rail Terminal screw M3 (30) Hole for screw mounting Locking tab Main unit (at attach/detach)
6.1
Terminal screw M3
5
At mounting to the DIN rail
Dimensions for screw mounting
2-M3 (30) 9±0.2
(8)
Notice at the installation
Please keep the distance of 30mm from this instrument to radiate. [50mm is recommended]
88.5±0.2
(100)
30 +0.7 +0.2
(3)
30 or more
30 or more
3
PUMCP
tERminal connEction diaGRam
Loader interface plug (RS-232C) 3 TX 2 RX 1 GND
φ2.5 3-pole miniature plug
STATION No. LOADER
×10
×1
RTS 2P5
21 22 23
21 22 23 24 25 26 27 28 29 30
11 12 13 14 15 16 17 18 19 20
Don’t connect
11 12 13
B(+) A(−)
24 25
14 15 16 17 18 19 20
26
2M SLD FG Don’t connect
27 28 29 30
Base part
Power DC24V +
1
2
1 3 4
2 5
-
3
4
5
Don’t connect
4
PROFIBUS communication module status
Contents Setting error Readout/Write data setting range Factory-set value — 0101h: St. No. configuration SW (St. No.) is invalid value 0102h: DIP SW (No. of words to exchange data) is invalid value 0203h: St. No. stored in EEPROM is invalid value 0204h: No. of words to exchange data that is stored in EEPROM is invalid value 0205h: Exchange pattern of Output data is invalid value 0206h: Exchange pattern of Input data is invalid value 0207h: Output area device size is invalid value 0208h: Input area device size is invalid value 0209h: Window communication pattern is invalid value 020Ah: Output area St. No. is invalid value 020Bh: Output area register No. is invalid value 020Ch: Input area St. No. is invalid value 020Dh: Input area register No. is invalid value 0211h: Window communication (EEPROM) is invalid value Register No. 30232
5
PUMCP
PROFIBUS communication setting
Contents PROFIBUS communication St. No. PROFIBUS communication setting for Output area Readout/Write data setting range 1 to 125 0 : 0 word 1 : 8 words 2 : 16 words 3 : 32 words 4 : 64 words 5 : 108 words 0 : 0 word 1 : 8 words 2 : 16 words 3 : 32 words 4 : 64 words 5 : 108 words 0 to 108 words 0 to 108 words 0: No Window communication 1: 1-word data communication 2: 2-word data communication 3: 4-word data communication 4: 8-word data communication *The above is the max. No. of words Factory-set value 1 0 Register No. 40001 40003
PROFIBUS communication setting for Input area
0
40004
Output area device size Input area device size Window communication pattern
0 0 0
40104 40105 40106
6
Memory allocation (Output area)
Contents Output area entry St. No. (1st word) Readout/Write data setting range 0: Not used 1 to 16: Control/Analog module 17 to 32: Event module Note: Other than the above are not settable 0,40000 to 49999 (Note1) 0: Not used 1 to 16: Control/Analog module 17 to 32: Event module Note: Other than the above are not settable 0, 40000 to 49999 (Note1) … Factory-set value 0 Register No. 41001
Output area entry Register No. (1st word) Output area entry St. No. (2nd word)
0 0
41002 41003
Output area entry Register No. (2nd word) … Output area entry St. No. (108th word)
0 …
41004 … 41215 41216 Register No. 43001 43002 43003 43004 … … 43215 43216
Output area entry Register No. (108th word)
0: Not used 1 to 16: Control/Analog module 17 to 32: Event module Note: Other than the above are not settable 0, 40000 to 49999 (Note1)
0
0
Note1: Only the addresses written in “Output/Input area register No. (User’s manual: PROFIBUS communication module INP” TN5A0489-E) are settable. However, the parameters marked “*” in “Entry ban” column are not settable.
Memory allocation (Input area)
Contents Input area entry St. No. (1st word) Readout/Write data setting range 0: Not used 1 to 16: Control/Analog module 17 to 32: Event module Note: Other than the above are not settable 0, 30000 to 49999 (Note2) 0: Not used 1 to 16: Control/Analog module 17 to 32: Event module Note: Other than the above are not settable 0, 30000 to 49999 (Note2) … Factory-set value 0
Input area entry Register No. (1st word) Input area entry St. No. (2nd word)
0 0
Input area entry Register No. (2nd word) Input area entry St. No. (108th word) …
0
Input area entry Register No. (108th word)
0: Not used 1 to 16: Control/Analog module 17 to 32: Event module Note: Other than the above are not settable 0, 30000 to 49999 (Note2)
0
0
Note2: Only the addresses written in “Output/Input area register No. (User’s manual: PROFIBUS communication module INP” TN5A0489-E) are settable. However, the parameters marked “*” in “Entry ban” column are not settable.
7
PUMCP
Caution on Safety *Before using this product, be sure to read its instruction manual in advance.
International Sales Div Sales Group Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome, Shinagawa-ku, Tokyo 141-0032, Japan http://www.fujielectric.com Phone: 81-3-5435-7280, 7281 Fax: 81-3-5435-7425 http://www.fjielectric.com/products/instruments/ Information in this catalog is subject to change without notice.
Printed in Japan