SAFETY BARRIER
DATA SHEET
This safety barrier is used for intrinsic safety explosionproofing of electronic instrumentation systems to ensure safe operation in the process of generating explosive gases. It is used in combination with field instruments installed in hazardous area as an intrinsic safety explosion-proof system.
PWX
SPECIFICATIONS
Explosion-proof structure: Intrinsic safety explosion-proof Applicable gas: FCX transmitter gas (3aG4) O ptical switch signal converter gas (3aG4 and 2G4) Optical repeater gas (3aG4 and 2G4) Optical fiber type multi-point temperature converter gas (3aG4 and 2G4) FCX-AII, AIII series transmitter (Ex ia IICT4) Safety hold rating: 250V AC and 250V DC Combination instrument: FCX Series transmitter, optical repeater, optical switch signal converter, optical fiber type multi-point temperature converter (Inspection guarantee No. of safety barrier should be attached to instrument) FCX-AII, AIII series transmitter (Device Certification) Ambient temperature of combination instrument: 60˚C or less Modification of combination instrument: M odification is prohibited (unit can be replaced). Grounding: Class A grounding Mounting method: S afety barrier should be installed in non-hazardous area using the supplied clip screw. Terminal structure: I nput/output terminal; rod type plug-in system [up to 4mm2(12AWG)] Earth; M4 screw terminal (with nut) Rated operating voltage: 25.8V DC ±0.5% Total resistance: Terminal 1 to 3 ... 340Ω Terminal 2 to 4... [0.9V+20 Ω] or short Intrinsic safety max. voltage: 28V Intrinsic safety max. current: 93mA Fuse: 50mA
External wiring condition:
Combination instrument FCX transmitter Optical switch signal converter Optical repeater Allowable external Allowable external Allowable external Applicable wiring resistance wiring static capacity wiring inductance gas (less than ) (less than F ) (less than mH ) Note)
3aG4 3aG4 2G4 3aG4 2G4
16
0.059
1
under application
under application under application
86 86 86 86 30
0.022 0.22 0.022 0.22 0.0504
1 5 1 5 1.91
Optical fiber 3aG4 type multi-point temperature 2G4 converter FCX-AII, AIII series transmitter ExiaIICT4
Note) Indicates allowable resistance of external wiring terminal when input resistance 250Ω of upper distributor is substracted.
Explosion-proof structure: Intrinsic safety explosion-proof Allowable common mode voltage: AC 0.5Vrms Error: 0.01% or less Ambient temperature: 5 to 95% RH Error: 0.01% or less Dimensions (H×W×D): 61.5×93.5×14.2mm Mass: About 125g Indoor installation structure, plastic case Structure:
Code symbols
12345678
PWX A B C D
A 0 01
Description Application FCX transmitter (4 to 20mA, 2-wire system), 3aG4 Optical switch signal converter, 3aG4 (under application) Optical switch signal converter, 2G4 (under application) Optical repeater, 3aG4 Optical repeater, 2G4 Optical fiber type multi-point temperature converter,3aG4 Optical fiber type multi-point temperature converter,2G4 Entity, ia IIC (FCX-AII, AIII transmitter can be combined.) Object TIIS Intrinsic safety explosion-proofing
A
Scope of delivery
Main unit, mounting clip
EDS13-18b
Date Apr. 1, 2011
PWX
Outline diagram (Unit: mm)
Hazardous area terminal 1 3 25.0 9 4 7.5 11.5 7.5 Earth terminal (M4 screw with nut) 2 1 Non-hazardous area terminal
2
49.2
85.0 93.5
61.5
14.2
Mounting clip plug-in hole
Mounting method (supplied mounting clip used)
95 M4 screw
Use of combination instrument
Hazardous area Non-hazardous area Safety barrier 3 PWX 4
+ Intrinsic safety – instrument
1 2
General-use instrument Operating voltage should be 250V AC/250V DC or less.
Class-1 grounding
Caution on Safety *Before using this product, be sure to read its instruction manual in advance.
International Sales Div Sales Group Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome, Shinagawa-ku, Tokyo 141-0032, Japan http://www.fujielectric.com Phone: 81-3-5435-7280, 7281 Fax: 81-3-5435-7425 http://www.fjielectric.com/products/instruments/ Information in this catalog is subject to change without notice.
Printed in Japan
很抱歉,暂时无法提供与“EDS13-18B”相匹配的价格&库存,您可以联系我们找货