Optical Fieldbus System
DATA SHEET
System Composition Devices
Fieldbus is used for digital transmission of the next generation, which takes over the conventional 4 to 20mA analog current transmission. The optical fieldbus using optical fiber as a fieldbus signal transmission line, has features of optical transmission such as noise-resistance and thunder-resistance, in additions to the features of fieldbus. The optical fieldbus system is composed of field devices, such as a pressure transmitter, a differential pressure transmitter, temperature transmitter, and optical star coupler for blanching optical signals, and a host control system.
Example of system configuration (single system)
Fieldbus configuration tool
FOCUS system
(or another manufacture's system)
FOCUS operator station Control LAN (Ethernet)
Controller ICS-2000 Electrical fieldbus Control room Fieldbus connecting unit
FEATURES
1. Noise-resistance, thunder-resistance Optical signals are free from effects of external noise and inductive thunder, providing highly reliable transmission. The use of non-metallic cables eliminates the propagation of inductive thunder, ensuring excellent thunder-proof transmission. 2. Reliability with redundancy Duplex host devices are available by using 2 optical cables (between star coupler and control room) to improve the system reliability. 3. Intrinsic safety explosion-proof Built-in power (battery) devices can be designed for intrinsic safety explosion-proof (intrinsic safety barrier is not required). Restriction of current flowing into the signal bus need not be taken into account, so any number of devices can be connected to one bus.
○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○
Field
Optical cable (optical fieldbus) Transmission distance; max. 1.2km Optical star coupler
Wiring cable (electrical fieldbus) Optical fieldbus Electrical fieldbus
Electrical fieldbus devices
Optical fieldbus devices Devices of this data sheet
Common specifications for system
Regulations: Specifications of Fieldbus Foundation Transmission speed: 31.25kbps Transmission cycle (macro-cycle): Standard; 1sec (400ms, min.) Optical cable: Composite cord, non-metallic cable Silica fiber... Core/cladding dia. 100/ 140µm or PCF fiber ... Core/cladding dia. 200/230µm Optical connector: FC connector or ST connector Transmission distance: Silica; 1.2 km (at transmission loss of optical cable, 4dB/km) PCF; 0.7km (at transmission loss of optical cable, 6dB/km) Ambient temperature: Silica; -30 to +70˚C, PCF: -20 to +60˚C, as noted in specifications for each devices Number of units connected: Up to 16 units including host and field devices (for 1 unit of star coupler)
EDS25-1a
Date Nov. 24, 1999
Optical fieldbus equipment
Contents 1. FFX-P series transmitter ................................................................................................................... 3 1) Pressure transmitter Type: FBB 2) Absolute pressure transmitter Type: FBH 3) Differential pressure/flow transmitter Type: FFG 4) Remote seal type pressure transmitter Type: FBF 5) Remote seal type differential pressure transmitter Type FFH 6) Level transmitter Type: FPL 2. FFX-T series temperature transmitter .......................................................................................... 22 1) Temperature transmitter (integrated type) Type: FUP 2) Temperature transmitter (separated type) Type: FUT 3. FFX-T series multi-point temperature converter 4. FFX-Z series optical-pneumatic converter 5. Optical star coupler Type FRM ................................. 27 Type: ZLK ................................. 30 Type FXB .................................. 33
2
Optical fieldbus equipment
FFX-P SERIES TRANSMITTERS
DATA SHEET
These transmitters are capacitance type high accuracy transmitters used for measuring the pressure, etc. of various fluids. The transmission unit incorporates a microprocessor for digitizing signals, thereby achieving a high accuracy and an intelligent transmitter. The signal transmission path adopts an optical fiber and composes an optical fieldbus system in combination with an optical star coupler and host system.
Model Configuration
Pressure transmitter (type: FBB) Reference page Common specifications Individual specifications Code symbols Outline diagram Tr-2 Tr-3 Tr-6 Tr-13 Common specifications Individual specifications Code symbols Outline diagram Absolute pressure transmitter (type: FBH) Reference page Tr-2 Tr-3 Tr-7 Tr-14
Differential pressure/flow transmitter (type: FFG) Reference page Common specifications Individual specifications Code symbols Outline diagram Tr-2 Tr-3 Tr-8 Tr-15
Remote seal type pressure transmitter (type: FBF) Reference page Common specifications Individual specifications Code symbols Outline diagram Tr-2 Tr-4 Tr-10 Tr-16
Remote seal type differential pressure transmitter (type: FFH) Level transmitter (type: FPL) Reference page Common specifications Individual specifications Code symbols Outline diagram Tr-2 Tr-4 Tr-11 Tr-18 Common specifications Individual specifications Code symbols Outline diagram Reference page Tr-2 Tr-4 Tr-12 Tr-19
(Tr-1)
3
FFX-P series transmitter
Optical fieldbus equipment
SPECIFICATIONS
(1) Common specifications
Function and Performance
Liquid, gas or vapor Optical digital signal, Fieldbus Foundamation specification • Power supply: Built-in lithium battery Service life: Approx. 2 years under the following conditions Macro cycle; 1 sec Status read cycle; 4 sec Token go-round; 0.25 sec Voltage read cycle; 1 hr • Explosion protection: Intrinsic safety type, JIS ib II C T3 (under application) CENELEC ib II C T4 (under application) • Ambient temperature: -30 to +70˚C -10 to +60˚C for intrinsic safety type -10 to +60˚C for fluorinated oil specification • Storage temperature: -40 to +80˚C • Ambient humidity: 95% RH max. • Self-diagnosis: Display on indicator and transmission to host system
Item Measuring range error Detection unit error Amplifier error Battery voltage Battery voltage drop alarm — Host system Indicator
Structure and Material
• Casing structure: Immersion-proof type JIS C 0920 (IEC IP67, NEMA 4X or equivalent) • Process connections: Rc1/4 or 1/4-18NPT (as specified in code symbol) Screw for oval flange; 7/16-20UNF • Optical cable connections: G1/2 or 1/2-14NPT (as specified in code symbol) • Mounting: On 50A (2B) pipe using U-bolt or wall mounting • Coating: Epoxy/polyurethane double-coating Color; silver (Case cover is blue.) • External dimensions: Entered in outline diagram. • Material: Refer to code symbols.
• Service: • Output:
Optional Specifications
• Indicator: 5-digit LCD, % or real-scale indication (as specified in code symbol) Operating temperature range; -20 to +70˚C • Oxygen no-oil treatment: Fluorinated oil filled in, process wetted parts cleaned by degreasing Varies with ma terial. So refer to • For chlorine measurement: Fluorinated oil filled in code symbols. • NACE specification: Treatment against H2S complying with NACE specification
• Remote setting: The following items can be read and set from the host system.
Item Tag No. Serial No. Range limit Measuring range Damping constant Low cut point Unit of measured value Measured value — — — Reading Setting
• Zero point deviation: Zero point can be shifted within -100 to +100% of span limit. • Response time: Same as communication cycle ... at damping 0 (zero) • Standard: Fieldbus Foundation specification (basic device, device type 411, AI function block)
4
(Tr-2)
FFX-P series transmitter
(2) Individual specifications
Optical fieldbus equipment
Pressure Transmitter
• Span, range and overrange limit:
Type FBB FBB FBB FBB FBB 01 02 03 04 05 Range limit [kPa] -64 to +64 -100 to +500 -100 to +3000 -100 to +10000 -100 to +50000 Span limit [kPa] Min. Max. 1.6 12.5 75 250 1250 64 500 3000 10000 50000 Overrange limit [kPa] 100 1500 9000 15000 75000
Differential Pressure/Flow Transmitter
• Static pressure span, and overrange limit:
Type FFG FFG FFG FFG FFG FFG FFG FFG FFG FFG FFG FFG FFG FFG FFG FFG 11 22 23 24 25 26 33 34 35 36 38 43 44 45 46 47 -100 to +42000 -100 to +16000 Static pressure [kPa] -100 to +3200 -100 to +10000 Span limit [kPa] Min. Max. 0.1 0.15 0.8 1.6 3.25 12.5 0.8 1.6 3.25 12.5 75 0.8 1.6 3.25 12.5 50 1 6 32 64 130 500 32 64 130 500 3000 32 64 130 500 2000 Overrange limit [kPa] ±1 ±6 ± 32 ± 64 ± 130 ± 500 ± 32 ± 64 ± 130 ± 500 ± 3000 ± 32 ± 64 ± 130 ± 500 ± 2000
• Process temperature and negative pressure tolerance limit: (For details, see Fig. 1.)
Filled oil Silicone oil Fluorinated oil Silicone oil 13th code Y.G.N W.A.D R Process temperature -40 to +120˚C -20 to +80˚C -15 to +120˚C Negative pressure tolerance limit 2.7 kPa abs Atmospheric pressure 2.7 kPa abs
• Accuracy rating: • 0.1 x URL min.; ± 0.1% • Below 0.1 x URL; ± (0.05 + 0.005 x URL/CR)% URL; Upper range limit, CR; Calibration range • Temperature effect: Zero shift; ± (0.2 + 0.05 x URL/CR)%/55˚C Total effect; ± (0.25 + 0.05 x URL/CR)%/55˚C Note) Double the effects for material code (7th digit in code symbols) other than V and W. • Overrange effect: Zero shift at URL ± 0.2%/overrange limit • Mass: 4.5 to 5 kg
• Process temperature and negative pressure tolerance limit: (For details, see Fig. 1.)
Filled oil Silicone oil (*1) Fluorinated oil Silicone oil 13th code Y.G.N W.A.D R Process temperature -40 to +120˚C -20 to +80˚C -15 to +120˚C Negative pressure tolerance limit 2.7 kPa abs Atmospheric pressure 2.7 kPa abs
Note(*1): Types FFG 38 and FFG negative pressure.
47 cannot be used at a
Absolute Pressure Transmitter
• Span, range and overrange limit:
Type FBH FBH FBH FBH 1 2 3 4 Range limit [kPa abs] 0 to 16 0 to 130 0 to 500 0 to 3000 Span limit [kPa abs] Min. Max. 1.6 3.25 12.5 75 16 130 500 3000 Overrange limit [kPa] 500 500 1500 9000
• Process temperature and negative pressure tolerance limit: Process temperature; -40 to +85˚C Negative pressure; Depends on measuring range. • Accuracy rating: • 0.1 x URL min.; ± 0.2% • Below 0.1 x URL; ± (0.1 + 0.01 x URL/ CR)% URL; Upper range limit, CR; Calibration range • Temperature effect: Zero shift; ± (0.25 + 0.2 x URL/CR)%/55˚C Total effect; ± (0.3 + 0.2 x URL/CR)%/55˚C Note) Double the effects for material code (7th digit in code symbols) other than V and W. • Overrange effect: Zero shift at URL ± 0.2% overrange limit • Mass: 4.5 kg
• Accuracy rating: Linear output • 0.1 x URL min.; ± 0.1% • Below 0.1 x URL; ± (0.05 + 0.005 x URL/CR)% URL; Upper range limit, CR; Calibration range Square root output • 0.1 x URL min.; Output 50% min. ... ± 0.1% Output 20% min. and below 50% ... ± 0.25% Output 10% min. and below 20% ... ± 0.5% • Below 0.1 x URL; Output 50% min. ... ± (0.05 + 0.005 x URL/CR)% Output 20% min. and below 50% ... ± 2.5 x (0.05 + 0.005 x URL/CR)% Output 10% min. and below 20% ... ± 5 x (0.05 + 0.005 x URL/CR)% • Temperature effect:
Linear output URL; 32 kPa min. Zero shift; ± (0.2 + 0.05 x URL/CR)%/55˚C Total effect; ± (0.25 + 0.05 x URL/CR)%/55˚C URL; 1 kPa, 6 kPa Zero shift; ± (0.25 + 0.2 x URL/CR)%/55˚C Total effect; ± (0.3 + 0.2 x URL/CR)%/55˚C Note 1 Change at 20% point ± (0.6 + 0.5 x URL/CR)%/55˚C Square root output ± (0.5 + 0.125 x URL/CR)%/55˚C
Note 1; Double the effects for material code (7th digit in code symbols) other than V and W. (Tr-3)
5
FFX-P series transmitter
Optical fieldbus equipment
• Overrange and static pressure effects: Overrange effect: Zero shift at URL (linear output) URL; 1, 6kPa... ± 0.3%/1, 3.2MPa URL; 32kPa... ± 0.3%/10, 16MPa, ± 0.5%/42MPa, Note; Double the effects for material code (7th digit in code symbols) other than V and W. Static pressure effect (linear output)
URL; 1, 6kPa Zero Span ± 0.2%/ 1, 3.2MPa -0.15± 0.15%/3.2MPa URL; 32kPa ~ ± 0.1%/ 10MPa -0.15± 0.15%/10MPa
Remote Seal Type Differential Pressure Transmitter and Level Transmitter
• Span, range and overrange limit: Level transmitter (FPL), remote seal type differential pressure transmitter (FFH)
Type FPL FFH FPL FFH FPL FFH FPL FFH Range limit [kPa] 3 Flange rating 3 pressure 4 4 5 5 6 6 12.5 500 ± 500 3.25 130 ± 130 1.6 64 ± 64 Span limit [kPa] Min. Max. 0.8 32 Overrange limit [kPa] ± 32
• Mass:
5.3 to 5.5 kg
Remote Seal Type Pressure Transmitter
• Span, range and overrange limit:
Type FBF FBF FBF FBF FBF 01 02 03 04 05 Range limit [kPa] Flange rating pressure Span limit [kPa] Min. 1.6 12.5 75 250 1250 Max. 64 500 3000 10000 50000 Overrange limit [kPa] 100 1500 4500 15000 75000
• Process temperature and negative pressure tolerance limit:
Filled oil Fluorinated oil Silicone oil 13th code W.A.D H J Y.G S T K Process temperature -20 to +120˚C -15 to +250˚C +85 to +300˚C -40 to +120˚C -15 to +250˚C +85 to +300˚C -15 to +200˚C 2.7 kPa abs See Fig. 2. 0.13 kPa abs See Fig. 3. Negative pressure tolerance limit Atmospheric pressure
• Process temperature and negative pressure tolerance limit:
Filled oil Fluorinated oil Silicone oil 13th code W.A.D H J Y.G S T K Process temperature -20 to +120˚C -15 to +250˚C +85 to +300˚C -40 to +120˚C -15 to +250˚C +85 to +300˚C -15 to +200˚C Negative pressure tolerance limit Atmospheric pressure
2.7 kPa abs See Fig. 2. 0.13 kPa abs See Fig. 3.
• Accuracy rating: • 0.1 x URL min.; ± 0.2% • Below 0.1 x URL; ± (0.1 + 0.01 x URL/CR)% URL; Upper range limit, CR; Calibration range • Temperature effect: Zero shift; ± (0.7 x URL/CR)%/55˚C Total effect; ± (1.0 x URL/CR)%/55˚C Note) Double the effects for material code (7th digit in code symbols) other than W, A, B and C. • Overrange effect: Zero shift at URL ± 0.2%/flange rating pressure • Mass: 10.5 to 13.5 kg
• Accuracy rating: • 0.1 x URL min.; ± 0.2% • Below 0.1 x URL; ± (0.1 + 0.01 x URL/ CR)% URL; Upper range limit, CR; Calibration range • Temperature effect: Zero shift; ± (0.7 x URL/CR)%/55˚C Total effect; ± (1.0 x URL/CR)%/55˚C Notes)1. Level transmitter; Double the effects for material code (7th digit in code symbols) other than V and W. 2. Remote seal type differential pressure transmitter; Double the effects for material code (7th digit in code symbols) other than W, A, B, C and D. • Overrange effect: Zero shift at URL ± 0.3%/flange rating pressure Note; Double the effects for material code (7th digit in code symbols) other than V (level transmitter), W, A, B, C and D (remote seal type differential transmitter). • Static pressure effect: Zero shift; ± 0.2%/1 MPa Span shift; -0.15 ± 0.15%/flange rating pressure Note; Zero shift is a change in URL. Span shift is a change in CR. • Mass: Remote seal type differential pressure transmitter; 15 to 33 kg Level transmitter; 10.5 to 19.5 kg
6
(Tr-4)
FFX-P series transmitter
Optical fieldbus equipment
Filled fluid: Silicone oil (code Y, G, N) Filled fluid: Silicone oil (code R) [kPa abs] 101
[kPa abs]
Filled fluid: Silicone oil (code K)
Operating pressure
Operating pressure
101
53.3 Operating area
Operating area
Nonoperating area 0.27 0.13
4
2.7 Non-operating area –40 –15 60 85 120 [°C]
–15
100 Process temperature
200
[°C]
Process temperature
Fig. 1 Relation between process temperature and operating pressure (pressure and differential pressure/flow transmitters)
Fig. 3 Relation between process temperature and operating pressure (remote seal type pressure, remote seal type differential pressure and level transmitters)
Filled fluid: Silicone oil (code Y, G) [kPa abs] Filled fluid: Silicone oil (code S) Filled fluid: Silicone oil (code T) 101
Operating pressure
53.3 Operating area
13.3
2.7
Non-operating area
–40 –15
60 85 120 200 230250 Process temperature
300 [°C]
Fig. 2 Relation between process temperature and operating pressure (remote seal type pressure, remote seal type differential pressure and level transmitters)
SCOPE OF DELIVERY
Transmitter main frame and bracket for pipe mounting (as specified)
ACCESSORIES
• Oval flange: Used as a connection flange of pressure leading pipe connection port. For details, refer to DATA SHEET (EDS610) of the oval flange. • Equalizing valve: Refer to DATA SHEET (EDS6-10).
(Tr-5)
7
FFX-P series transmitter
Optical fieldbus equipment
CODE SYMBOLS
1) Pressure transmitter
12345678 9 10 11 12 13 14 15
FBB
0
1-
-
S T 1 2 3 4 5
Description Connections (4th code) Process connection Opt.cable connection Rc1/4 G1/2 1/4-18NPT 1/2-14NPT Measurement span (6th code) 1.6........... 64kPa 12.5....... 500kPa 7.5....... 3000kPa 250.... 10000kPa 1250.. 50000kPa Material (7th code) Process cover Diaphragm SCS14 SUS316L SCS14 Hastelloy C SCS14 Monel SCS14 Tantalum Hastelloy C lining Hastelloy C Monel lining Monel Tantalum lining Tantalum Other wetted parts SUS316 Hastelloy C Monel Tantalum Except when Hastelloy C 6th code is 5 Monel Tantalum
V H M T B L U A L P A G K
Indicator (9th code) None Digital, % indication Digital, actual scale indication Explosion-proof (10th code) None (for ordinary locations) JIS, intrinsic safety (under application) CENELEC, intrinsic safety (under application) Side vent/drain and mounting bracket (11th code) Side vent/drain Mounting bracket None None None Yes (stainless steel) Yes Except when None Yes 7th code is B, L or U Yes (stainless steel) F S Optical connector (12th code) FC type ST type Treatment and filled fluid (13th code) Treatment Filled fluid None Silicone oil None Fluorinated oil Degreasing Silicone oil Oxygen no-oil treatment Fluorinated oil ... Only for 7th code V Chlorine service Fluorinated oil ... Except when 7th code is V, M or L NACE specification Silicone oil ... Except when 6th code is 5 or 7th code is T or U None Silicone oil (for vacuum) A B C C D E F O-ring material (for process cover)(14th code) Viton Teflon Square Teflon.... Except when 7th code is B, L or U Bolt/nut (15th code) NACE bolt/nut (ASTM A193 B7M/ A194 2HM Except when NACE bolt/nut (ASTM A320 L7M/ A194 2HM 6th code is 5 SUS304/ SUS304... (For general application) SUS630/ SUS304... Specify when 6th code is 5.
A C D F
Y W G A D N R
8
(Tr-6)
FFX-P series transmitter
Optical fieldbus equipment
CODE SYMBOLS
2) Absolute pressure transmitter
12345678 9 10 11 12 13 14 15
F BH
0
1-
-
S T 1 2 3 4
Description Connections (4th code) Process connection Opt.cable connection Rc1/4 G1/2 1/4-18NPT 1/2-14NPT Measurement span (6th code) 1.6........... 64kPa abs 32.5....... 130kPa abs 12.5....... 500kPa abs 75........ 3000kPa abs Material (7th code) Process cover Pressure receiving diaphragm SCS14 SUS316L SCS14 Hastelloy C SCS14 Monel SCS14 Tantalum Other wetted parts SUS316 Hastelloy C Monel Tantalum...Except when 6th code is 1
V H M T A L P A G K
Indicator (9th code) None Digital, % indication Digital, actual scale indication Explosion-proof (10th code) None (for ordinary locations) JIS, intrinsic safety (under application) CENELEC, intrinsic safety (under application) Side vent/drain and mounting bracket (11th code) Side vent/drain Mounting bracket None None None Yes (stainless steel) Yes None Yes Yes (stainless steel) F S Optical connector (12th code) FC type ST type Treatment and filled fluid (13th code) Treatment Filled fluid None Silicone oil Degreasing Silicone oil NACE specification Silicone oil ... Except when 7th code is T A C D E O-ring material (for process cover)(14th code) Viton Bolt/nut (15th code) NACE bolt/nut (ASTM A193 B7M/ A194 2HM) NACE bolt/nut (ASTM A320 L7M/ A194 2HM) SUS304/ SUS304... (For general application)
A C D F
Y G N
(Tr-7)
9
FFX-P series transmitter
Optical fieldbus equipment
CODE SYMBOLS
3) Differential pressure/flow transmitter
12345678 9 10 11 12 13 14 15
F FG
1-
-
S T
Description Connections (4th code) Process connection Opt. cable connection Rc1/4 G1/2 1/4-18NPT 1/2-14NPT Static pressure and measurement span (5th and 6th codes) Static pressure Measurement span -0.1~+3.2 MPa 0.1.......... 1 kPa -0.1~+10 MPa 0.15........ 6 kPa -0.1~+3.2 MPa 0.8........ 32 kPa 1.6........ 64 kPa 3.25.... 130 kPa 12.5........ 500 kPa 75........... 3000 kPa -0.1~+4.2 MPa 0.8.......... 32 kPa 1.6.......... 64 kPa 3.25...... 130 kPa 12.5...... 500 kPa 50....... 2000 kPa -0.1~+10 MPa 0.8.......... 32 kPa 1.6.......... 64 kPa For material codes B, L and U 3.25...... 130 kPa 12.5...... 500 kPa Material (7th code) Process cover Diaphragm Other wetted parts SUS316 Hastelloy C Monel Tantalum SUS316 Hastelloy C Monel Tantalum Application (5/6th codes) 11, 22, 33, 34, 35, 43, 44, 45 11, 22, 33, 34, 35, 36, 43, 44, 45, 46 33, 34, 35, 36, 43, 44, 45, 46 33, 34, 35, 36 36, 38, 46, 47 23, 24, 25, 26
1 2 3 3 3 3 3 4 4 4 4 4 2 2 2 2
1 2 3 4 5 6 8 3 4 5 6 7 3 4 5 6
V H M T W B L U
SCS14 or SUS316 SCS14 or SUS316 SCS14 or SUS316 SCS14 or SUS316 SCS14 or SUS316 Hastelloy C lining Monel lining Tantalum lining
SUS316L Hastelloy C Monel Tantalum Hastelloy C Hastelloy C Monel Tantalum
V A L P Q S A G K
Indicator and output (9th code) Indicator Output None Linear None Square root Digital, % indication Linear Digital, actual scale indication Linear Digital, % indication Square root Digital, actual scale indication Square root Explosion-proof (10th code) None (for ordinary locations) JIS, intrinsic safety (under application) CENELEC, intrinsic safety (under application)
10
(Tr-8)
FFX-P series transmitter
Optical fieldbus equipment
CODE SYMBOLS
12345678
9 10 11 12 13
14 15
F FG
1-
-
A C D F F S
Description Side vent/drain and mounting bracket (11th code) Side vent/drain Mounting bracket None None None Yes (stainless steel) Except when Yes None 7th code is B, L or U Yes Yes (stainless steel) Optical connector (12th code) FC type ST type Treatment and filled fluid (13th code) Treatment Filled fluid None Silicone oil None Fluorinated oil Degreasing Silicone oil Oxygen no-oil treatment Fluorinated oil ... Only for 7th codes V and W Chlorine service Fluorinated oil ... Except when 7th code is V, M or L NACE specification Silicone oil ... Except when 7th code is T or U None Silicone oil (for vacuum) A B C C D E F O-ring material (for process cover) (14th code) Viton Teflon Square Teflon ... Except when 7th code is B, L or U Bolt/nut (15th code) NACE bolt/nut (ASTM A193 B7M/ A194 2HM) Note 1 NACE bolt/nut (ASTM A320 L7M/ A194 2HM) SUS304/ SUS304..... (For general application) ... Note 2 SUS630/ SUS304..... Specify when 5th code is 3 or 4
Y W G A D N R
Note 1; Static pressure is limited to 10 MPa at maximum. Note 2; Allowed for 5th codes 1, 2 and 3. However, static pressure is limited to 10 MPa at maximum.
(Tr-9)
11
FFX-P series transmitter
Optical fieldbus equipment
CODE SYMBOLS
4) Remote seal type pressure transmitter
12345678
9 10 11 12 13
FBF S T
1Opt.cable connection (4th code) G1/2 1/2-14NPT Flanges (5th code) Material 0 1 2 3 4 5 P Q R K 1 2 3 4 5
Description
SUS304
None (wafer type)
Screw-in type
Rating JIS 10K 80A JIS 10K 100A JIS 30K 50A ANSI/JPI 150LB 3B ANSI/JPI 150LB 4B ANSI/JPI 600LB 2B For JIS 80A, ANSI/JPI 3B For JIS 100A, ANSI/JPI 4B For JIS 50A, ANSI/JPI 2B JIS G1 thread
Applicable 6th code 1, 2 1, 2 3 1, 2 1, 2 3 1, 2 1, 2 3 4, 5
Measurement span (6th code) 1.6............ 64kPa 12.5........ 500kPa 75......... 3000kPa...... Available only with 7th codes W, A, B, C, D, H, M and T 250..... 10000kPa Applicable to 5th code K 1250... 50000kPa Specify W as 7th code. Material and diaphragm extension (7th code) Other wetted parts Seal diaphragm SUS316 SUS316L SUS316L SUS316 SUS316L SUS316 SUS316L SUS316 SUS316L SUS316 Hastelloy C Hastelloy C Hastelloy C Hastelloy C Hastelloy C Hastelloy C Hastelloy C Hastelloy C Hastelloy C Hastelloy C Monel Monel Tantalum Tantalum Titanium Titanium Zirconium Zirconium A L P A G K A B G C H J K F S Indicator (9th digit) None Digital, % indication Digital, actual scale indication Explosion-proof (10th code) None (for ordinary locations) JIS, intrinsic safety (under application) CENELEC, intrinsic safety (under application) Capillary length (11t code) 1.5m 3m 5m 6m 7m 8m Available for 5th code 0, 1, 3, 4, P or Q and 13th code Y, W, G, A or D 10m Optical connector (12th code) FC type ST type Treatment and filled fluid (13th code) Treatment Filled fluid None Silicone oil None Fluorinated oil Degreasing Silicone oil Oxygen no-oil treatment Fluorinated oil ... Available for 7th code W, A, B, C or D Chlorine service Fluorinated oil ... Available for 7th code H, F, G, K, L or T None Silicone oil (for high temperature) *1 None Silicone oil (for high temperature) None Silicone oil (for high temperature and vacuum) None Silicone oil (for high temperature and vacuum) *2 None Silicone oil (for high temperature and high vacuum) Diaphragm extension (mm) 0 50 When these codes 100 are used in 150 combination with 200 13th code S, T or K, 0 only 5th codes 1, 4 50 and Q are available. 100 150 200 0 0 Available only with 6th code 0 2 and 5th code 0, 3 or P 0
W A B C D H F G K L M T P R
Y W G A D H J S T K
*1: Available for 6th code 1, 2 or 3 and 7th code W, A, B, C or D *2: Available for 6th code 2 and 7th code W, A, B, C or D
12
(Tr-10)
FFX-P series transmitter
Optical fieldbus equipment
CODE SYMBOLS
5) Remote seal type differential pressure transmitter
12345678 9 10 11 12 13
F FH S T
1Opt.cable connection (4th code) G1/2 1/2-14NPT Flanges (5th code) Material 0 1 2 3 4 5 6 7 P Q 3 4 5 6
Description
SUS304
None (wafer type)
Rating JIS 10K 80A JIS 10K 100A JIS 30K 80A JIS 30K 100A ANSI/JPI 150LB 3B ANSI/JPI 150LB 4B ANSI/JPI 300LB 3B ANSI/JPI 300LB 4B For JIS 80A, ANSI/JPI 3B For JIS 100A, ANSI/JPI 4B
Measurement span (6th code) 0.8............ 32kPa 1.6............ 64kPa 3.25........ 130kPa 12.5........ 500kPa Material and diaphragm extension (7th code) Other wetted parts Seal diaphragm SUS316 SCS316L SCS316L SUS316 SCS316L SUS316 SCS316L SUS316 SCS316L SUS316 Hastelloy C Hastelloy C Hastelloy C Hastelloy C Hastelloy C Hastelloy C Hastelloy C Hastelloy C Hastelloy C Hastelloy C Monel Monel Tantalum Tantalum Titanium Titanium Zirconium Zirconium A L P A G K A B G C H J K F S Indicator (9th digit) None Digital, % indication Digital, actual scale indication Explosion-proof (10th code) None (for ordinary locations) JIS, intrinsic safety (under application) CENELEC, intrinsic safety (under application) Capillary length (11t code) 1.5m 3m 5m 6m 7m 8m Available for 13th code Y, W, G, A or D 10m Optical connector (12th code) FC type ST type Treatment and filled fluid (13th code) Treatment Filled fluid None Silicone oil None Fluorinated oil Degreasing Silicone oil Oxygen no-oil treatment Fluorinated oil ... Available for 7th code W, A, B, C or D Chlorine service Fluorinated oil ... Available for 7th code H, F, G, K, L or T None Silicone oil (for high temperature) None Silicone oil (for high temperature) None Silicone oil (for high temperature and vacuum) *1 None Silicone oil (for high temperature and vacuum) None Silicone oil (for high temperature and high vacuum) Diaphragm extension (mm) 0 50 When these codes 100 are used in 150 combination with 200 13th code S, T or K, 0 only 5th codes 1, 3, 5, 7 50 and Q are available. 100 150 200 0 0 Available only with 5th code 0 0, 2, 4, 6 or P 0
W A B C D H F G K L M T P R
Y W G A D H J S T K
*1: Available for 7th code W, A, B, C or D
(Tr-11)
13
FFX-P series transmitter
Optical fieldbus equipment
CODE SYMBOLS
6) Level transmitter
12345678 9 10 11 12 13
FPL
1Connections (4th code) Low pressure connection RC1/4 1/4-18NPT Flanges (5th code) Material 0 1 2 3 4 5 6 7 3 4 5 6
Description Opt.cable connection G1/2 1/2-14NPT
S T
SUS304
Rating JIS 10K 80A JIS 10K 100A JIS 30K 80A JIS 30K 100A ANSI/JPI 150LB 3B ANSI/JPI 150LB 4B ANSI/JPI 300LB 3B ANSI/JPI 300LB 4B
Measurement span (6th code) 0.8............ 32kPa 1.6............ 64kPa 3.25........ 130kPa 12.5........ 500kPa Material (7th code) High pressure side (flange side) Diaphragm Other wetted part SCS316L SUS316 Hastelloy C Hastelloy C Monel Monel Tantalum Tantalum A L P A G K Y A B C D E F G H F S Indicator (9th digit) None Digital, % indication Digital, actual scale indication Explosion-proof (10th code) None (for ordinary locations) JIS, intrinsic safety (under application) CENELEC, intrinsic safety (under application) Diaphragm extension (mm)(11th code) 0...... For any 7th code 50 100 7th code V only 150 200 50 100 7th code H only 150 200 Optical connector (12th code) FC type ST type Treatment and filled fluid (13th code) Treatment Filled fluid None Silicone oil None Fluorinated oil Degreasing Silicone oil Oxygen no-oil treatment Fluorinated oil ... Available for 7th code V Chlorine service Fluorinated oil ... Available for 7th code H or T None Silicone oil (for high temperature) None Silicone oil (for high temperature) None Silicone oil (for high temperature and vacuum) None Silicone oil (for high temperature and vacuum) None Silicone oil (for high temperature and high vacuum) Low pressure side Diaphragm SCS316L.....*1 Hastelloy C Monel Tantalum
Process cover SCS14 SCS14 SCS14 SCS14
V H M T
Y W G A D H J S T K
*2
*1: Hastelloy C for 6th code 6 *2: Available for 7th code V
14
(Tr-12)
FFX-P series transmitter
Optical fieldbus equipment
OUTLINE DIAGRAM (Unit: mm)
1) Pressure transmitter
P
241 80 108 70
FBB S 0 T
V H M 1– T
A C
Mounting pipe JIS 50A (2B)
U-bolt (M8)
290
225 8
70
ø102
54 15 B Optical cable connection Indicator (option) Vent/drain plug 31 27 47 A Pressure connection
FBB S 0 T
41.3
B L 1– U
A C
4–7/16-20UNF Screw depth 13 27 View from arrow P
300 41.3
ø15
ø7
ø102 8
54 A Pressure connection 2–7/16–20UNF Screw depth 10 ø16 ø12
+0.2 +0.1
15 3
2.5
E Details of area B
D
40
ø18.5 Details of area A
27 47
Type D E
G1/2
1/2–14NPT
ø4 Details of area A
(Tr-13)
ø2
Rc1/4
1/4–18NPT
0 - 0.1
FBBS
FBBT
1
15
FFX-P series transmitter
Optical fieldbus equipment
OUTLINE DIAGRAM (Unit: mm)
2) Absolute pressure transmitter
P
241 80 108 70
FBH S 0 T
V H M 1– T
A C
Mounting pipe JIS 50A (2B)
U-bolt (M8)
290
225 8
70
ø102
54 15 B Optical cable connection Indicator (option) Vent/drain plug 31 27 47
A Pressure connection
41.3
4–7/16-20UNF Screw depth 13 27 View from arrow P
ø15
15 3
ø7
8
Type D E
FBHS Rc1/4 G1/2
FBHT 1/4–18NPT 1/2–14NPT
E Details of area B
D
ø18.5 Details of area A
2.5
16
(Tr-14)
FFX-P series transmitter
Optical fieldbus equipment
OUTLINE DIAGRAM (Unit: mm)
3) Differential pressure/flow transmitter
P
241 80 108 70
FFG S T
V H M 1– T W
A C
Mounting pipe JIS 50A (2B)
U-bolt (M8)
290
225 8
70
ø102
54 15 B Optical cable connection Indicator (option) Vent/drain plug 37 27 47 A Low pressure connection A High pressure connection
FFG S T
41.3
LH
B L 1– U
A C
A Pressure connection
8–7/16-20UNF Screw depth 13
300 41.3 27
ø102
ø15
ø7
3
8
15
54 D ø18.5 Details of area A
E Details of area B
4-7/16-20UNF Screw depth 10 40 Vent/drain plug 27 47
2.5
ø16 Type D E FFGS Rc1/4 G1/2 FFGT 1/4–18NPT 1/2–14NPT ø12 +0.1
+0.2
1
ø4
Details of area A
(Tr-15)
2 –0.1
0
28
View from arrow P
17
FFX-P series transmitter
Optical fieldbus equipment
OUTLINE DIAGRAM (Unit: mm)
4) Remote seal type pressure transmitter
0 1 S2 1 FBF T32 3 4 5
131
241 80
1
108 70
øF
t
øK øJ øH
Inner diameter of gasket seat U-bolt (M8)
Mounting pipe JIS 50A (2B)
L 20
15 B Indicator (option) Optical cable connection View from arrow Q Type FBF * * * W1 FBF * * * H1 FBF * * * M1 FBF * * * T1 FBF * * * P1 FBF * * * R1 FBF * * * A1 FBF * * * F1 FBF * * * B1 FBF * * * G1 FBF * * * C1 FBF * * * K1 FBF * * * D1 FBF * * * L1 L 0 Mass (kg) 10.5
288
Q
ø102
70
S
225 8
50 100 150 200
11.5 12.5 13 13.5
54
N-øh Hole øG 29 27 47
P1 FBF S Q 2 TR3
P
1
288
FBFS FBFT
G1/2 1/2-14NPT
15
ø102
54 29 27 47
ø15
Type
E
E Details of area B
3
P
2-M6 Depth 9 Type FBF * 0 * * 1 FBF * 1* * 1 FBF * 2 * * 1 FBF * 3* * 1 FBF * 4 * * 1 FBF * 5* * 1 øF øG øH øJ øK 73 96 48 73 96 48 t 38 38 42 44 44 P 116 141 50 116 141 N-øh 8-19 8-19 8-19 4-20 8-20 8-20 FLANGE JIS-10k-80A JIS-10k-100A JIS-30k-50A ANSI / JPI 150lb 3B ANSI / JPI 150lb 4B ANSI / JPI 600lb 2B Type FBF * P 1 * 1 2 FBF * Q 1 * 1 2 FBF * R 3 * 1 øH øJ øK t P FLANGE 185 150 126 100 210 175 151 103 165 130 84 52 191 152.5 126 100 229 190.5 151 103 165 127 84 52
126 100 151 103 84 52
73 38 96 38
116 80A, 3B 141 100A, 4B
45.5 50
48 45.5 50 50A, 2B
Note) "S" depends on code specification.
18
(Tr-16)
FFX-P series transmitter
Optical fieldbus equipment
OUTLINE DIAGRAM (Unit: mm)
4) Remote seal type pressure transmitter
FBF S K 4 W1 T5
241 80 108 70
131
Mounting pipe JIS 50A (2B) U-bolt (M8)
15 B Indicator (option) Optical cable connection View from arrow Q
288 ø15
ø102 3
70
225 8
S
Q
E
ø30 -0.2 -0.1 ø23.6 -0.2
54 Packing G1 29 27 47
Details of area B E G1/2 1/2-14NPT
-0.1
2 2 18 53 47 100 20
Type FBFS FBFT
Note) "S" depends on code specification.
(Tr-17)
15
19
FFX-P series transmitter
Optical fieldbus equipment
OUTLINE DIAGRAM (Unit: mm)
5) Remote seal type differential pressure transmitter
Low pressure side
131
131
S
FFH S T
0 1 2 3 4 5 6 7
241
1
80 108 70
High pressure side
øF
S
øK øJ øH
Inner diameter of gasket seat U-bolt (M8)
Mounting pipe JIS 50A (2B)
15 B Indicator (option) Optical cable connection View from arrow Q Type ø15
FFH * * * W1 FFH * * * H1 FFH * * * M1 FFH * * * T1 FFH * * * P1 FFH * * * R1 FFH * * * A1 FFH * * * F1 FFH * * * B1 FFH * * * G1 FFH * * * C1 FFH * * * K1 FFH * * * D1 FFH * * * L1
L
L 20
t
70
225 8
288 E
15
3
LH
Mass (kg) 15 to 20.5 0 50 100 150 200 16 to 31.5 16.5 to 32 17 to 32.5 17.5 to 33
Q
ø102
Details of area B
54 N- øh Hole øG 29 27 47
Note) "S" depends on code specification.
P
FFH S P TQ
1
288
Type FFH * 0 * * 1 FFH * 1 * * 1 FFH * 2 * * 1 FFH * 3 * * 1 FFH * 4 * * 1 FFH * 5 * * 1 FFH * 6 * * 1 FFH * 7 * * 1 Type FFHS FFHT
øF 185 210 210 240 191 229 210 254
øG 150 175 170 195 152.5 190.5 168 200 E
øH 126 151 126 151 126 151 126 151
øJ 100 103 100 103 100 103 100 103
øK 73 96 73 96 73 96 73 96
t 38 38 48 52 44 44 49 52
P 116 141 116 141 116 141 116 141
N-øh 8-19 8-19 8-23 8-25 4-20 8-20 8-23 8-23
FLANGE JIS-10k-80A JIS-10k-100A JIS-30k-80A JIS-30k-100A ANSI / JPI 150lb 3B ANSI / JPI 150lb 4B ANSI / JPI 300lb 3B ANSI / JPI 300lb 4B
ø102
54 29 27 47
G1/2 1/2-14NPT Type FFH * P * * 1 FFH * Q * * 1 øH 126 151 øJ 100 103 øK 73 96
P
2-M6 Depth9 P FLANGE
116 For JIS-80A, ANSI/JPI 3B 141 For JIS-100A, ANSI/JPI 4B
20
(Tr-18)
FFX-P series transmitter
Optical fieldbus equipment
OUTLINE DIAGRAM (Unit: mm)
6) Level transmitter
1 2
L 20 øG
t
A Low pressure connection
ø102
øF øH øJ øK
Q
54
N- øh Hole
Inner diameter of gasket seat
Vent/drain plug 41.3
27
ø15
3
ø7
8
15
E Details of area B
D
ø18.5 Details of area A 126
2.5
46.4
241
Type FPLS FPLT Type øF
D Rc1/4
E G1/2
15 B Indicator (option) Optical cable connection View from arrow Q
1/4-18NPT 1/2-14NPT øG øH øJ øK 73 96 73 96 73 96 73 96 t 38 38 48 52 44 44 49 52 N-øh 8-19 8-19 8-23 8-25 4-20 8-20 8-23 8-23 FLANGE JIS-10k-80A JIS-10k-100A JIS-30k-80A JIS-30k-100A ANSI / JPI 150lb 3B ANSI / JPI 150lb 4B ANSI / JPI 300lb 3B ANSI / JPI 300lb 4B L 1 2 Type FPL * * * * 1- * * Y 0 365 150 FPL * * * V1- * * A FPL * * * H1- * * E 50 FPL * * * V1- * * B FPL * * * H1- * * F 100 359 144 FPL * * * V1- * * C FPL * * * H1- * * G 150 FPL * * * V1- * * D FPL * * * H1- * * H 200 Mass (kg) 10.5 to 14 11 to 18 11.5 to 18.5 12 to 19 12.5 to 19.5
FPL * 0 * * 1 185 150 126 100 FPL * 1 * * 1 210 175 151 103 FPL * 2 * * 1 210 170 126 100 FPL * 3 * * 1 240 195 151 103 FPL * 4 * * 1 191 152.5 126 100 FPL * 5 * * 1 229 190.5 151 103 FPL * 6 * * 1 210 168 126 100 FPL * 7 * * 1 254 200 151 103
(Tr-19)
70
8
21
Optical fieldbus equipment
FFX-T Series Temperature Transmitter
DATA SHEET
This temperature transmitter is equipped with a thermocouple and a platinum resistance bulb for measuring temperatures of various kinds of fluids. The electronic unit has a built-in micro-processor for processing signals in digital mode to provide highly accurate and intelligent measurements. The signal transmission line uses optical fiber cables to realize an optical fieldbus system with optical star coupler and host system.
Composition of models
1) Temperature transmitter (integrated type); Type FUP 2) Temperature transmitter (separated type); Type FUT
Specifications
Functional specifications
• Measured fluid: Liquid, gas, vapor • Measuring range
Integrated type (FUP) Separated type (FUT) J Thermocouple E Thermocouple K Thermocouple R Thermocouple T Thermocouple Resistance bulb Pt100 -200 to +400˚C -200 to +400˚C -200 to +400˚C -200 to +400˚C -200 to +750˚C -200 to +800˚C -200 to +1200˚C 0 to +1600˚C -200 to +350˚C -200 to +600˚C
• Self-diagnosis: Display on indicator and transmission to host
Item Measuring range error Sensor error Amplifier fault Battery voltage Battery voltage-drop alarm — Host Indicator
Note)
When the operating temperature range is not specified at the time of ordering, the transmitter will be adjusted within the maximum measuring range prior to delivery.
• Remote setting: Read-out from hose devices and setting items
Item Tag No. Serial No. Maximum range Measuring range Damping constant Unit of process variable Process variable — — — Read-out Setting
• Operating pressure: Flange type...Flange rated pressure Screw type... 4MPa or less • Output: Optical digital signal, specifications of Fieldbus Foundation • Burnout: Previous output is retained at burnout of sensor. With BAD status • Explosion-proof: Intrinsic safety explosion-proof, JIS ib II C T3 (under application), CENELEC ib II C T4 (under application) • Zero point deviation: 80% between minimum and maximum temperatures within measuring range • Power supply: Built-in lithium battery Life: About 2 years ... under the following conditions. Macro-cycle: 1sec Status read cycle; 4sec Token go-round; 0.25sec Voltage read cycle; 1hr
• Ambient temperature: -30 to +70˚C Intrinsic safety explosion-proof; -10 to +60˚C • Storage temperature: -40 to +80˚C • Ambient humidity: 95%RH or less • Regulation: Fieldbus Foundation specifications (basic device, device type 411, AI function block)
Performance specifications
1. Sensor (for integrated type) • Accuracy rating: Thermocouple; JIS C 1604 Class 2 Resistance bulb; JIS C 1604 Class B • Response time (time constant): Protective tube, ø4.8mm... About 8sec Protective tube, ø12mm... About 70sec
22
FFX-T Series Temperature Transmitter
Optical fieldbus equipment
Relation between measured fluid flow velocity and insertion length
2. Electronic unit (integrated/separated type) • Accuracy rating:
Type FUP FUT FUT A (integrated type) A (separated type) B (separated type) J Thermocouple Sensor J Thermocouple Temperature range -140 to +400˚C Under. -140˚C * -100 to +750˚C Under. -100˚C * FUP FUT FUT C (integrated type) C (separated type) D (separated type) E Thermocouple -80 to +800˚C Under. -80˚C * FUP FUT FUT E (integrated type) E (separated type) F (separated type) K Thermocouple K Thermocouple -150 to +400˚C Under. -150˚C * 0 to +1200˚C Under. 0˚C * FUT FUT FUP FUT FUT G (separated type) G (separated type) J (integrated type) L (separated type) K (separated type) M (separated type) FUT FUT N (separated type) P (separated type) JPt100 JPt100 -200 to +400˚C -200 to +500˚C ± 0.6˚C ± 0.7˚C -200 to +600˚C ± 0.9˚C R Thermocouple T Thermocouple Pt100 0 to +1600˚C -200 to +350˚C -200 to +400˚C ± 1.2˚C ± 2˚C ± 0.6˚C ± 1˚C ± 1.8˚C ± 3˚C ± 4˚C ± 0.8˚C ± 0.6˚C E Thermocouple -200 to +400˚C Accuracy rating ± 0.6˚C ± 1˚C ± 1.1˚C ± 1.9˚C ± 0.6˚C
When inserting the protective tube into the fluid piping, the temperature sensor receives the stress of the flow of fluid, so the strength of the protective tube to be inserted should be taken into account. Study the insertion length of the temperature sensor to be used referring to the relation between the flow velocity and insertion length shown in Fig. 1. When inserting the sheath type into flow, a protective tube should be provided separately.
1300 1000
Insertion length L (mm)
100
Water
Air
Note
1. Accuracy with segmented line compensation 2. Reference junction compensation error not included.
10 0.1
1 10 Flow velocity (m/ S)
100
Fig. 1 Relation between flow velocity and insertion length (Protective tube, ø12mm)
• Reference junction compensation accuracy: ± 1˚C (for thermocouple) • Ambient temperature effect: (Variation at -30 to +70˚C) ± 0.5% of Max. measured temperature; ± 1% of the above temperature range marked "*" • Wiring resistance: (For separated type) Thermocouple: Less than 100Ω , resistance bulb; less than 10Ω
Option specifications
• Indicator: 5-digit LCD display, % or scale display Operating temperature range; -20 to +70 ˚C
Scope of delivery
Instrument main unit, pipe mounting brackets (for separated type)
Structure and material
• Casing: Immersion-proof type, JIS C 0920 (IEC IP67, NEMA4X or equivalent) • Optical cable connections: G1/2 or 1/2-14NPT • Mounting method: (1) Integrated type (FUP); screw or flange mounting ... according to code symbols (2) Separated type (FUT); 50A (2B) pipe mounting with U-bolt or wall mounting • Coating: Epoxy/urethane, double coating Color; silver (blue for case cover) • Mass: (1) Integrated type (FUP); 3 to 5kg, depending on the length of sensor (2) Separated type (FUT); about 2.4kg • Insertion length: (Length of integrated type sensor) 100 to 2000 mm ... Refer to the code symbols. • Minimum bending radius: (Allowable bend of integrated type sensor) 14.4mm ... Sheath type (ø4.8mm) only • Dimensions: See outline diagram. • Material: (Material of integrated type sensor protective tube) SUS304 or SUS316... according to code symbols
23
FFX-T Series Temperature Transmitter
Optical fieldbus equipment
CODE SYMBOLS
Temperature transmitter (integrated type)
12345678 9 10 11 12 13 14
FUP S T A C E J L A G K A L P
1-
-
Description Opt. cable connection (4th digit) G1/2 1/2-14NPT Measuring range (5th digit) J Thermocouple E Thermocouple K Thermocouple 3-wire system Pt 100 (1989) 3-wire system Pt 100 (1997) -200 to 400˚C -200 to 400˚C -200 to 400˚C -200 to 400˚C -200 to 400˚C
Explosion-proof (6th digit) For general-use (non-explosion-proof) JIS Intrinsic safety (under application) CENELEC Intrinsic safety (under application) Indicator (7th digit) None Digital, % display Digital, actual scale display F S A B S W 0 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 1 1 2 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 0 1 2 3 4 5 6 7 8 9 Optical connector (9th digit) FC type ST type Type of protective tube (10th digit) ø12 ø4.8(sheath type) Protective tube material (11th digit) SUS304 (10th digit B not applicable) SUS316 Insertion length (mm) (12th, 13th digit) 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 10th digit A not applicable 1800 1900 2000 Mounting method (14th digit) Flange JIS 10K-25A RF Flange JIS 20K-25A RF Flange JIS 30K-25A RF Flange JIS 63K-25A RF Screw-in G 3/4B Screw-in R 3/4 Screw-in 3/4-14NPT Flange ANSI 150LB, 1B Flange ANSI 300LB, 1B Flange ANSI 600LB, 1B
Temperature transmitter (separated type)
12345678 9
FUT S T A B C D E F G H J K L M N P A G K A L P
1-
Description Opt. cable connection(4th digit) G1/2 1/2-14NPT Input signal, measuring range (5th digit) J Thermocouple -200 to 400˚C J Thermocouple -200 to 750˚C E Thermocouple -200 to 400˚C E Thermocouple -200 to 800˚C K Thermocouple -200 to 400˚C K Thermocouple -200 to 1200˚C R Thermocouple 0 to 1600˚C T Thermocouple -200 to 350˚C 3-wire system Pt 100 (1989) -200 to 400˚C 3-wire system Pt 100 (1989) -200 to 600˚C 3-wire system Pt 100 (1997) -200 to 400˚C 3-wire system Pt 100 (1997) -200 to 600˚C 3-wire system JPt 100 -200 to 400˚C 3-wire system JPt 100 -200 to 500˚C Explosion-proof (6th digit) For general-use (non-explosion-proof) JIS Intrinsic safety (under application) CENELEC Intrinsic safety (under application) Indicator (7th digit) None Digital, % display Digital, actual scale display F S Optical connector (9th digit) FC type ST type
24
FFX-T Series Temperature Transmitter
Optical fieldbus equipment
Outline diagram
1) Temperature transmitter (integrated type)
FUP
1–
A B
ø70
0 17 28 39 P
ø102
222 49 T
L
øD1
øD
øD2 4- ød
241 80 54
1
8
Type 122 FUP * * * * 1 - * * * * * 0 70 FUP * * * * 1 - * * * * * 1 15 B Optical cable connection "P" view FUP * * * * 1 - * * * * * 2 Indicator (option) FUP * * * * 1 - * * * * * 3 FUP * * * * 1 - * * * * * 7 FUP * * * * 1 - * * * * * 8 FUP * * * * 1 - * * * * * 9 ø15 3
Flange JIS 10K-25A RF JIS 20K-25A RF JIS 30K-25A RF JIS 63K-25A RF ANSI 150lb,1B ANSI 300lb,1B ANSI 600lb,1B
T 14 16 20 27 14.5 17.5 17.5
D1 125 125 130 140 108 124 124
D2 90 90 95 100 79.4 88.9 88.9
d 19 19
t
1.0 19 23 16 20 20 1.6
15
A "B" detail
FUP
1–
A B
4 5 6
L 223 20 38 ø102
Type FUPS * * * 1 - * A* * *
A G1/2
D ø12
L 100 to 1300 (to be specified) M 54 M G3/4 Rc 3/4
FUPT * * * 1 - * A* * * 1/2-14NPT FUPS * * * 1 - * B* * * G1/2
ø4.8 100 to 2000 (sheath (to be specified) FUPT * * * 1 - * B* * * 1/2-14NPT type)
Type FUP * * * * 1 - * * * * * 4 FUP * * * * 1 - * * * * * 5 FUP * * * * 1 - * * * * * 6 FUP * * * * 1 - * * * * * 4 FUP * * * * 1 - * * * * * 5 FUP * * * * 1 - * * * * * 6
3/4-14NPT
G3/4 Rc 3/4
3/4-14NPT
øD
25
FFX-T Series Temperature Transmitter
Optical fieldbus equipment
Outline diagram
2) Temperature transmitter (separated type)
241 80 108 70
Mounting pipe JIS 50A (2B)
U-bolt (M8)
Terminal block (for sensor connection)
225
266
8
70
ø102
54 15 B Optical cable connection Indicator (option) 27 47
ø15
3
Type
15
FUTS G1/2
FUTT 1/2-14NPT
D "B" detail M3 screw
D
A B
6.5
+ – E Thermocouple
B E Resistance bulb Connection diagram
26
Optical fieldbus equipment
FFX-T Series Multi-point Temperature Converter
DATA SHEET
This multi-point temperature converter is used to receive input signals from a maximum of 8 points of thermocouple or resistance bulb temperature sensors and convert these signals into optical digital output signals. The signal transmitter using optical fiber cables configures an optical fieldbus system together with an optical star coupler and a host system.
Specifications
Functional specifications
Thermocouple (J, E, K, R, T type) Resistance bulb (Pt100, JPt100, 3-wire system) • Input points: 8 points, max. Temperature sensors should be of the same type and the same range. • Output: Optical digital signal, Fieldbus Foundation specifications • Power supply: 24V DC (20 to 30V) or 85 to 264V AC 50/ 60 Hz, according to code symbols • Power consumption: About 1W ... 24V DC About 5VA ... 85-264V AC • Explosion-proof: Intrinsic safety explosion-proof, JIS ib II C T3 (under application) CENELEC ib II C T4 (under application), 24V DC only Used in combination with safety barrier (PWXCA001) • Zero point deviation: 80% of minimum-maximum temperatures within measuring range • Remote setting: Read-out from host system and setting items
Item Tag No. Serial No. Maximum range Measuring range Damping constant Unit of process variable Process variable — — — Read-out Setting
• Input:
Previous output value is retained at burnout of sensor. With BAD status • Self-diagnosis: Detection of faults and transmission to host system; measurement error, sensor burnout, amplifier fault • Ambient temperature: -30 to +60˚C Intrinsic safety explosion-proof; -10 to +60˚C • Storage temperature: -40 to +70˚C • Ambient humidity: 95%RH or less • Regulation: Fieldbus Foundation specifications (Basic device, device type 411, AI function block)
• Burnout:
Performance specifications
• Accuracy rating:
Type FRM1A FRM1B FRM1C FRM1D FRM1E FRM1F FRM1G FRM1H FRM1 J FRM1 L FRM1 K FRM1 M FRM1N FRM1P R Thermocouple T Thermocouple Resistance bulb Pt100 Resistance bulb Pt100 Resistance bulb JPt100 -200 to +300˚C -200 to +500˚C ± 0.9˚C ± 1.5 ˚C -200 to +600˚C ± 1.8˚C K Thermocouple E Thermocouple Sensor J Thermocouple Temperature range -200 to +400˚C -200 to +75˚C -200 to +400˚C -200 to +800˚C -200 to +600˚C -200 to +1200˚C 0 to +1600˚C -200 to +350˚C -200 to +300˚C Accuracy rating ± 1.2˚C ± 2.2˚C ± 1.2˚C ± 2.4˚C ± 1.8˚C ± 3.6˚C ± 4.8˚C ± 1˚C ± 0.9˚C
• Measuring range:
Type FRM1A FRM1B FRM1C FRM1D FRM1E FRM1F FRM1G FRM1H FRM1J FRM1L FRM1K FRM1M FRM1N FRM1P R Thermocouple T Thermocouple Resistance bulb Pt100 Resistance bulb Pt100 Resistance bulb JPt100 -200 to +300˚C -200 to +500˚C -200 to +600˚C K Thermocouple E Thermocouple Sensor J Thermocouple Temperature range -200 to +400˚C -200 to +750˚C -200 to +400˚C -200 to +800˚C -200 to +600˚C -200 to +1200˚C 0 to +1600˚C -200 to +350˚C -200 to +300˚C
Note)
Accuracy: With linearize, reference junction compensation error not included • Reference junction compensation accuracy: ± 1˚C (for thermocouple) • Measuring cycle : 2sec (at any input point) • Ambient temperature effect: (Variations at -30 to +60˚C) ± 0.5% of maximum measuring temperature • Allowable wiring resistance: Thermocouple; less than 100Ω Resistance bulb; less than 10Ω • Insulation: Fully insulated between input and output and between output and power supply by optical interface
Power supply 24V DC 85 to 264V AC Withstand-voltage 500V AC, 1min 2000V AC, 1min Insulation resistance More than 100MΩ at 500V DC More than 100MΩ at 500V DC
27
FFX-T Series Multi-point Temperature Converter
Optical fieldbus equipment
Structure and materials
• Casing: Splash-proof type (IEC IP65 or equivalent) • Optical/power cable connection port: G1/2 o r 1/2-14NPT ... according to code symbols • Sensor cable connection port: G11/4 or 11/4-11NPT ... according to code symbols • Mounting method: Mounting on 50A (2B) pipe with U-bolt or wall mounting .... according to code symbols • Mass: Approx. 9kg • Coating: Epoxy/urethane double coating • Dimensions: See outline diagram.
Scope of delivery
Instrument main unit, U-bolt (for pipe mounting)
CODE SYMBOLS
12345678 9 10
F RM 1 A B C D E F G H J K L M N P
1-
Description Input points (4th digit) 8 points Measuring range (5th digit) J Thermocouple -200 to +400˚C J Thermocouple -200 to +750˚C E Thermocouple -200 to +400˚C E Thermocouple -200 to +800˚C K Thermocouple -200 to +600˚C K Thermocouple -200 to +1200˚C R Thermocouple 0 to +1600˚C T Thermocouple -200 to +350˚C Resistance bulb -200 to +300˚C 3-wire system Pt 100 (1989) Resistance bulb -200 to +600˚C 3-wire system Pt 100 (1989) Resistance bulb -200 to +300˚C 3-wire system Pt 100 (1997) Resistance bulb -200 to +600˚C 3-wire system Pt 100 (1997) Resistance bulb -200 to +300˚C 3-wire system JPt 100 Resistance bulb -200 to +500˚C 3-wire system JPt 100
A G K 1 2 F S
Explosion-proof (6th digit) For general-use (non-explosion-proof) JIS Intrinsic safety (under application) *1 CENELEC Intrinsic safety (under application) Power supply (7th digit) DC24V AC85 to 264V 50/60Hz Optical connector (9th digit) FC type ST type Cable connection and mounting (10th digit) Cable connection Mounting G1/2, 11/4 Pipe mounting Wall mounting G1/2, 11/4 Pipe mounting NPT1/2, 11/4 Wall mounting NPT1/2, 11/4
A B C D
*1: Not applicable for the 7th digit code 2
28
FFX-T Series Multi-point Temperature Converter
Optical fieldbus equipment
Outline diagram
348.5 200 176 70 128 47.5
414 350 291
440
210
series
Multi-point Temperature Converter
U-bolt (M8) 4- ø9 (for mounting) Blind plug B Power cable connection B Optical cable connection A Sensor cable connection E "B" detail Mounting pipe JIS 50A (2B)
16.5 16.5
50
40
D "A" detail
38.5 120.5
59.5 120.5
Type FRM1 * * *1– * A B
D G11/4
E G1/2
C FRM1 * * *1– * D 11/4–11NPT 1/2–14NPT
29
Optical fieldbus equipment
FFX-Z Series Optical-Pneumatic Converter
DATA SHEET
This instrument is used to convert optical digital signals into pneumatic signals proportional to the set value given from the host system for operating pneumatic actuatres such as pneumatic positioners, diaphragm valves, etc. The adoption of optical fiber cables to the signal transmission line configures an optical fieldbus system together with an optical star coupler and a host system.
Specifications
Functional specifications
• Input: Optical digital signal, Fieldbus Foundation specifications • Output: Pneumatic output; 20 to 100kPa • Supply air pressure: 140kPa • Power supply: Built-in lithium battery Life: About 1.5 years ... under the following conditions Macro-cycle; 1sec Status read cycle; 4sec Token go-round; 0.25sec Voltage read cycle; 1hr • Explosion-proof: Intrinsic safety explosion-proof, JIS ib II C T3 (under application) CENELEC ib II C T4 (under application) • Self-diagnosis: Display on indicator and transmission to host
Item Measuring range error Detector error Amplifier fault Battery voltage Battery voltage-drop alarm — Host Indicator
Performance specifications
• Accuracy rating: ± 0.5%, full scale (output ripple; about ± 0.2%) • Response speed: 3sec or less (90% response time at load capacity 0.5R) • Input/output characteristic: Linear • Air consumption: Steady time (at steady output); 8NR/min Maximum (at sudden change of output); 60NR/min
Structure and materials
• Casing: Splash-proof type, JIS C 0920 (IEC IP54 or equivalent) • Air piping connection port: Rc 1/4 o r 1/4 -18NPT (according to code symbols) • Optical cable connection: G1/2 or 1/2-14NPT (according to code symbols) • Mounting method: Mounting on 50A (2B) pipe with U-bolt or wall mounting • Coating: Epoxy/urethane double coating, color; silver (blue for case cover) • Mass: Approx. 5.3kg • Dimensions: See outline diagram.
• Remote setting: Read-out from host device and setting items
Item Tag No. Serial No. Output value Unit of output value Direction of emergency operation — — Read-out Setting
• Emergency operation: Direction of output pneumatic operation at input OFF is selected from the following 3 operations ... according to code symbols. Previous value hold / Scale-out below 0% (less than 5kPa) / Scale-out above 100% (more than 120kPa) • Ambient temperature: -20 to +60˚C Intrinsic safety explosion-proof; -10 to +60˚C • Storage temperature: -30 to +70˚C • Ambient humidity: 95%RH or less • Regulation: Fieldbus Foundation specifications (basic device, device type 411 AO function block)
Option specifications
• Indicator: 5-digit LCD display, % or actual scale display
Scope of delivery
Instrument main unit, pipe mounting brackets
30
FFX-Z Series Optical-Pneumatic Converter
Optical fieldbus equipment
CODE SYMBOLS
12345678 9 10 11
ZLK1 1 S T F S A L P
1-
Description Output air pressure/ supply pressure (4th digit) 20 to 100kPa / 140kPa Air piping connection/ opt.cable connection (5th digit) Rc1/4 / G1/2 1/4-18NPT / 1/2-14NPT Optical connector (6th digit) FC connector ST connector Indicator (7th digit) None Digital, % display Digital, actual scale display A G K A B C Y A Explosion-proof (9th digit) For general-use (non-explosion-proof) JIS Intrinsic safety (under application) CENELEC Intrinsic safety (under application) Emergency operation (at input OFF) (10th digit) Previous value hold Scale-out below 0% Scale-out above 100% Air set (11th digit) None With air regulater
31
FFX-Z Series Optical-Pneumatic Converter
Optical fieldbus equipment
Outline diagram
225 64.5 108 70
Mounting pipe JIS 50A (2B)
U-bolt (M8)
91
214
191
SUP 25 Indicator (option)
130
OUT 27 64 39 47 Pressure gauge (output) B Optical cable connection
2-air connection port
ø15
15
3
Type Air connection port Optical cable connection D
ZLK1S Rc 1/4 G 1/2
ZLK1T 1/4-18NPT 1/2-14NPT
D "B" detail
32
Optical fieldbus equipment
Optical Star Coupler
DATA SHEET
This optical star coupler is used to branch optical signals; signals from the host system are branched for transmission to each field device, while signals from field devices are transmitted to the host system. It is a reflection type star coupler capable of communications between field devices, and configures an optical fieldbus system together with field devices and host system.
Specifications
Function/performance
• Number of branches: 16 branches • Applicable optical fiber: Silica fiber ... core/cladding dia. 100/140 µm PCF fiber ... core/cladding dia. 200/230 µm ... according to code symbols • Applicable optical connector: FC connector or ST connector ... according to code symbols • Insertion loss: Silica; Max. 17.5dB PCF; Max. 18.5dB • Ambient temperature: Silica; -30 to +70˚C PCF; -20 to +60˚C • Storage temperature: Silica; -40 to +80˚C PCF; -30 to +70˚C • Ambient humidity: 95%RF or less Fieldbus Foundation specifications • Regulation: Silica fiber (A1d) device type 421 PCF fiber (A3C) device type 422
CODE SYMBOLS
12345678
FXB 1 2 1 2
001
Description Applicable optical fiber Silica; (100/140 µm) PCF; (200/230 µm) Applicable optical connector FC connector ST connector
Scope of delivery
Instrument main unit
Structure and materials
• Casing: Dust-proof type JIS C 0920 ... indoor-use (IEC IP50 or equivalent) • Coating: Melamine coating, color; Munsell 7.5BG6/1.5 • Mounting method: Wall mounting • Dimensions: See outline diagram. • Mass: Approx. 1.8kg • Material: Case, steel plate
33
Optical star coupler
Optical fieldbus equipment
Outline diagram
FXB 1
330 310 290
77
1.6
30
34
34
34
34
34
34
34
Receptacle (for FC connector)
20
13
2
70 100 165
4– ø9 (for mounting)
FXB
330 310 290
2
77
30
1.6
34
34
34
34
34
34
34
Receptacle (for ST connector)
Caution on Safety *Before using this product, be sure to read its instruction manual in advance.
Head Office
Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome, Shinagawa-ku, Tokyo 141-0032, Japan http://www.fesys.co.jp/eng
Instrumentation Div. International Sales Dept.
No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187 http://www.fic-net.jp/eng
Information in this catalog is subject to change without notice.
20
13
9
70 100 165
4– ø9 (for mounting)