EDS6-120

EDS6-120

  • 厂商:

    FUJI(富士电机)

  • 封装:

  • 描述:

    EDS6-120 - E SERIESE ELECTROMAGNETIC FLOWMETER(SEPARATE TYPE) - Fuji Electric

  • 数据手册
  • 价格&库存
EDS6-120 数据手册
E SERIESE ELECTROMAGNETIC FLOWMETER (SEPARATE TYPE) DATA SHEET The electromagnetic flowmeter is an instrument to measure the volumetric flow rate of liquid simply by applying a magnetic field from the outside utilizing the fact that an electric conductor which crosses a magnetic field at a certain velocity causes voltage to be induced in proportion to the velocity, which is known as Faraday’s law. This flowmeter is designed with the latest electronics technology, realizing a compact and light-weight structure and measurement with high accuracy. FMF1,2/FMH FEATURES 1. High accuracy When conductivity is above 5 µS/cm, flow rate of liquid can be measured regardless of density and viscosity. The measurement accuracy is as high as 0.6% of rate. 2. Free power supply The flowmeter operates on power supply 100 to 230V AC, 50/60Hz. 3. Grounding electrode Use of the grounding electrode of Hasteroy C in the flowmeter allows installation without an earth ring. 4. Change of settings. The setting of various parameters can be changed from the outside of the case cover. Application of the supplied magnetic stick to the outside glass surface enables the setting to change without opening the case cover. 5. Stable measurement of flow rate A digital filter for pulsating or noisy flow signal, flow rate output low cut, and damping function allows flow rate measurement to be stabilized. 6. Self-diagnosis function Since self-diagnosis function is provided for empty detection, trouble, and maloperation, the flowmeter can be used with safety. 7. Simultaneous display of instantaneous flow and total flow 2-stage display with LCD backlight which is visible in the dark. • Mounting method : Mounted via flange insertion type on opposite (with Guide rings) ··· 3A to 100A Note 1) Guide ring : A ring-shaped guide used for centering the sensor when a wafer type is mounted on the piping. Note 2) Flange with meter size 3A or 6A can be used for 15A. or flange mounting ··· 15A to 300A • Fluid pressure : 0 to 2000kPa or flange operating pressure, whichever is lower. • Meter size and measurement range See the following table for the full scale of measurable flow rate. Meter size 3A Note 3) 6A Note 3) 15A 25A 40A 50A Min.measurement range [m3/h] 0 to 0.012 0 to 0.06 0 to 0.3 0 to 0.6 0 to 1.8 0 to 3.0 0 to 9.0 0 to 12.0 0 to 30.0 0 to 54.0 0 to 90.0 0 to 120.0 Max. measurement range [m3/h] 0 to 0.24 0 to 1.2 0 to 6.0 0 to 12.0 0 to 36.0 0 to 60.0 0 to 180.0 0 to 240.0 0 to 600.0 0 to 1080 0 to 1800 0 to 2400 SPECIFICATIONS Detector (Model: FMF) • Measurement item : General-use industrial water, waste water, and other liquids with conductivity of more than 5µs/cm. Wafer type or flange type • Structure : 80A 100A 150A Note 4) 200A Note 4) 250A Note 4) 300A Note 4) Note 3) Meter size 3A and 6A : Wafer type only Note 4) Meter size 150A or more : Flange type only EDS6-120 Date Aug.3, 2001 FMF1,2/FMH • Fluid temperature : –25 to +130˚C (PFA, TFE lining) [˚C] 130 Fluid temperature 50 0 -25 -20 [˚C] 10 25 60 Ambient tempertaure Ambient temperature – fluid temperature allowable range • Material : Fluid wetted parts Note 1) Lining Signal electrode Earth electrode Earth ring Note 2) Tefron(PFA, TFE) Hasteroy C-4 equivalent Housing case Flange Note 3) Case of terminal box Aluminum alloy SUS316 equivalent Aluminum alloy Note 1) Materials of fluid wetted parts should be selected in consideration of erosion due to measuring fluid. Refer to the table of material selection on the attached sheet. Note 2) For earth ring attachments, see CODE SYMBOLS. Note 3) Flange type only • Wiring connection port : G1 /2 • Finish color : Silver, Lid ....Beige • Protection class : IP67 • Grounding : D-class grounding (100Ω or less) Conveter (Model: FMH) • Mounting method : Mounting on the pipe or wall • Input/output signal : Current output; 4 to 20mA DC Load rasistance 0 to 600Ω Pulse output; open-collector Capacity; 16 to 30V DC, 0.22A or less ON voltage; 2V or less Max. 5kHz Status output; open-collector Capacity: 16 to 30V DC, 0.22A or less ON voltage; 2V or less Status input; voltage input Capacity: 16 to 30V DC Internal resistance: 2kΩ • Pulse output : Total pulses are outputted by setting total constant. Pulse width 0.1 to 2000ms is settable. • Span setting : Flow rate full scale(FS) can be set by setting flow rate unit and flow rate value. Display cubic volume; m3, L, mL Display time unit ; /d, /h, /min, /s • Flow direction change : Flow direction can be reversed in flow direction mode. • Flow display : Real unit flow display, % display or user unit display is possible. Max 6 disits. • Total display : Totaled volume can be displayed by setting the unit of cubic volume. Displayed cubic volume unit ; m3, L, mL Totaled value is held when power failure occurs. • Fault diagnosis function : Various faults can be diagnosed by hardware check and process check. • Zero point adjustment : Zero point is automatically calibrated with key operation. 0 to 10% FS settable • Low cut : Momentary output can be cut to 0% at flow rate below the set cutoff point. Note) Output low cut and total low cut are set at the same value. • 0% signal lock : Display and output can be locked to 0% with status input. • Filter : A digital filter is included in the converter especially for pulsating or noisy flow signals. • Empty detection : Absence of liquid is detected and status signal is outputted only when diameter is more than 10A and conductivity is more than 20µS/cm. • Flow switch : 0 to 130% FS Status signal is outputted by setting high/ low limit flow. • Dumping time constant : 1 to 99.999 sec • Density setting : Available from 0.01 to 5.00g/cm3, and the weight of the fluid can also be indicated. • Converter case : Aluminum alloy • Wiring connection port : G1 /2 (with water-proof gland) • Finish color : Silver, Lid ....Beige • Protection class : IP67 • Grounding : D-class grounding (100Ω or less) • Mass : 4.5kg • Length of exclusive signal cable : 50m or less Other specifications For different materials of the electrode and earth-ring, contact with Fuji Electric. Standard performance • Accuracy rating of display and pulse output : Flow velocity 0.7m/s or more Accuracy ±0.5% of rate 0.0035 100 % of rate ± 0.7m/s 0or less Qv Qv : Measuring flow velocity • Accuracy rating of analog output : Flow velocity 0.7m/s or more Accuracy ±0.6% of rate 0.0035 100+0.1 % of rate ± 0.7m/s 0or less Qv Qv : Measuring flow velocity • Power consumption : 14VA or less • Operating condition : Ambient temperature; –25 to 60˚C (Detector : PFA, TFE lining) –20 to 60˚C (Converter) Ambient humidity; 95% RH or less (Note) Power voltage; 100 to 230V AC +10%, -15% Power frequency; 50/60Hz (Note) If ambient humidity exceeds 95% RH, select a submersible type in FMB model. 2 Length of straight pipe for installing the electromagnetic flowmeter The length of the up-stream/down-stream straight pipe of the flowmeter should be long enough to ensure accurate measurements. See below. 1-1) Upstream reducer pipe Flowmeter Flowing direction 2-1) Downstream reducer pipe Flowmeter Flowing direction 5D Downstream straight pipe unnecessary 1-2) Upstream diffuser pipe Flowmeter Flowing direction 2-2) Downstream diffuser pipe Flowmeter Flowing direction 5D Downstream straight pipe unnecessary 1-3) Various upstream valves Flowmeter Flowing direction 2-3) Various downstream valves Flowmeter Flowing direction Note) 10D Note) "5D" with sluice valve fully open 2 3D 1-4) Upstream 90° bend Flowmeter Flowing direction 2-4) Downstream 90° bend Flowmeter Flowing direction 5D 2 3D 1-5) Upstream T-pipe Flowmeter Flowing direction 2-5) Downstream T-pipe Flowmeter Flowing direction 5D 2 3D Minimum length of straight pipe between up-stream/down-stream joints and flowmeter. Note 1) D=diameter of measuring pipe. Note 2) Do not put any objects, which affect magnetic field, electromotive force and flow velocity profile, in the measuring pipe. Note 3) Use a straight pipe (2D to 3D) on the down-steam side, if the drift to the up-stream side is affected by installing valves, etc. 3 FMF1,2/FMH Mounting posture of electromagnetic flowmeter The flowmeter can be installed vertically, horizontally, or at other angle. When installing, be sure to observe the following points. q The measuring pipe should always fill with fluid which flows in the piping. Fluid may not fill up the pipe. Air are apt to from. Fluid may not fill up the pipe. Good Pump Good Example of mounting posture w The signal electrode should be at a level with the ground. And also signal electrode and ground electrode should always keep contact with fluid. If the signal electrode or the ground electrode is upper position against the fluid, correct measurements cannot be expected due to air bubbles on the fluid. Signal electrode Ground electrode Ground < Good > < Good > Ground electrode Signal electrode Ground electrode Signal electrode Ground Ground < No good > < No good > Ground Position of electrode How to connect the grounding cable contacting with measuring liquid. Since the electromagnetic flowmeter is provided with a grounding electrode, flow rate of liquid can be measured without an earth ring. However, if stray potential exists in a pipeline, the potential in the pipeline may fluctuate. In this case, the earth ring (option) of the same material as signal electrode and ground electrode should be mounted on the upstream and downstream sides of the flowmeter to connect to the grounding terminal. For liquid that contains attachments or deposits, take the liquid contacting ground from the optional earth rings and metallic pipe (without lining). Grounding connection In case of metallic pipe without linging Without earth ring With earth ring 4 CODE SYMBOLS Separate type electromagnetic flowmeter Detector (wafer type) 12345678 9 10 11 12 13 14 FMF 1 S A C D T E F G T P 0 H 1 -H0 A0 Meter size (5th code) 3A 6A 15A 25A 40A 50A 80A 100A Description Lining material (6th code) TFE (adhesive Tefron) : applied for meter size 15A to 100A PFA (mold Tefron) : applied for meter size 3A to 6A Earth ring material (7th code) None Hasteroy C H 0 1 7 A 0 Y A Electrode matertal (9th code) Hasteroy C Flange (10th code) None Guide ring (11th code) For JIS 10K For JIS 75M (Meter size 80A, 100A only) Wiring connection port size (12th code) G1/2(PF1/2) female screw with water-proof gland Application (13th code) Standard Optional specifications (14th code) None Stainless tag plate will be manufactured as order. Note 1) Items with the asterisk mark 5 FMF1,2/FMH Separate type electromagnetic flowmeter Detector (flange type) 12345678 9 10 11 12 13 14 FMF 2 C D T E F G H J K L T 1 - H 10A0 Meter size (5th code) 15A 25A 40A 50A 80A 100A 150A 200A 250A 300A Description T 0 H H 1 0 A 0 Y A Lining material (6th code) TFE (adhesive Tefron) Earth ring material (7th code) None Hasteroy C Electrode matertal (9th code) Hasteroy C Flange (10th code) For JIS 10K Guide ring (11th code) None Wiring connection port size (12th code) G1/2(PF1/2) female screw with water-proof gland Application (13th code) Standard Optional specifications (14th code) None Stainless tag plate will be manufactured as order. Note 1) Items with the asterisk mark Separate type electromagnetic flowmeter Converter 12345678 9 10 11 12 13 F MH 1 N 1 N A B A1 - Y Description Application (4th digit) Standard Power supply (5th digit) AC100 230V Mounting method (6th digit) Pipe mount Wall mount A Y A Y 0 0 0 0 0 0 0 1 2 3 4 5 0 0 0 0 0 0 Wiring lead-in port (7th digit) G1/2(PF1/2) female, with water-proof gland Optional specification (9th digit) None With parameter setting function Cable termination (10th digit) None Cable length (11 to 13th digit) Nothing 10m 20m 30m 40m 50m 6 OUTLINE DIAGRAM (Unit: mm) (Wafer type detector) < Stainless tag > Option Wiring lead-in port G 1/ 2 88 35 67.5 20 67 Water-proof gland H Meter size 3A,6A W1 B F H Mass ( Kg ) 69 75 62 191 2 15A 69 75 62 191 2 25A 91 95 73 213 3.5 75 40A 104 112 82 231 5 50A 119 130 90 247 5.5 80A 103 163 110 287 8 100A 133 190 130 327 9 F B W1 (Flange type detector) < Stainless tag > Option Wiring lead-in port 88 35 Water-proof gland 67.5 20 N-øB øC H Meter size W1 W2 øD øC N-øB JIS 10K T flange øG H F Mass ( Kg ) 15A 25A 40A 50A 80A 100A 66.5 87 100 116 100 130 200 200 200 200 200 250 95 125 140 155 185 210 70 90 105 120 150 175 4-12 4-15 4-15 4-19 8-19 8-19 14 20 20 22 18 20 52 70 85 100 130 155 191 62 3 213 231 73 82 4 6 247 90 8 287 327 110 130 16 17 F W1 -3 W2 (Note) 0 T øG øD (Note) W2 are dimensions after positioning to piping. The lining flare sections are not glued before positioning to piping (There are about 30mm protruding of each side.) 75 7 FMF1,2/FMH OUTLINE DIAGRAM (Unit: mm) Wiring lead-in port G1/2 ø80 67 35 øC Water-proof gland H øG N-øB W1 W2 (Note) T F Meter size W1 W2 øD øC N-øB T øG H F Mass (kg) 150A 170 0 300 -3 280 200A 195 0 350 -3 330 290 12-23 28 268 430 179 53 250A 250 0 450 -5 400 355 12-25 30 320 486 207 79 300A 250 0 500 -5 445 400 16-25 31 370 572 250 81 < Stainless tag > Option 240 8-23 25 212 368 148 29 JIS 10K flange 20 (Note) W2 are dimensions after positioning to piping. The lining flare sections are not glued before positioning to piping (There are about 30mm protruding of each side.) 8 75 øD OUTLINE DIAGRAM (Unit: mm) (Pipe mount type converter) U-bolt M8 49 Mounting pipe JIS 2B 229 199 Water-proof gland 78 108 70 ø120 329 310 288 (Wall mount type converter) 80 60 229 199 Wiring lead-in port G1/2 Water-proof gland 35 26 78 34 ø7 35 220 288 Wiring lead-in port G1/2 ø7 9 FMF1,2/FMH EXTERNAL CONNECTION DIAGRAM Flow rate signal Converter Excitation Shield of flow rate signal cable Inner shield Outer shield Detecter V9 V8 P7 G2 X2 + – N L M2 M1 2S 2 1 1S 3 M2 M1 2 1 3 SE Total pulse output Power supply Special signal cable Current output Status output Status input FLOW RATE – FLOW VELOCITY CONVERSION DIAGRAM m/s 3 4 5 6 810-2 10 8 6 5 4 3 2 2 3 4 5 6 810-1 2 3 4 56 8 1 2 3 4 5 6 8 10 2 3 4 5 6 8 102 2 3 4 56 8 L/s Flow velocity [m/s] 3A 1 0.8 0.7 0.5 6A A 15 A 25 A A 40 50 AA 80 100 0A 00A 50A 00A 15 2 23 3 10-2 2 2 3 4 5 6 810-1 2 2 3 456 8 1 2 2 3 4 5 6 8 10 2 2 3 4 5 6 8102 2 2 3 4 5 6 8103 2 2 3 m/h L/min 3 4 56 8 1 3 4 5 6 8 10 3 4 5 6 8102 Flow rate 3 4 5 6 8103 3 4 5 6 8104 3 45 SCOPE OF DELIVERY Detecter (mounting bolt and packing should be prepared separately). Converter ×1 (with metal fixtures for pipe-mount or wallmount) Special signal cable ×1 (length; by specifing) Magnetic stick HOW TO CONNECT CABLE 1. Press the terminal spring by inserting a minus driver (small) through the opening at top. 2. Insert terminated cable into the cable lead-in port as shown below. 3. When the driver is removed, the cable is fixed (connected) by the spring force in the terminal. SPARE PARTS Guide rings (note) / for wafer type. Note) Not supplied for 80A and 100A JIS 10K. Minus driver (small) 10 15mm Cable ITEMS SPECIFIED AT ORDERING 1. Type, specification code. 2. Flow measurement range and mesurement fluid. 3. When ordering “with stainless tag plate,” specify Tag No. (up to 16 alphanumeric characters) as needed. 4. When ordering “with parameter setting,” complete and send the attached parameter designation table. Note) Cable should be securely fixed with the supplied water-proof gland. 10 If you want the instrument with certain parameters factory set as you desire, specify them in the following parameter designation tables 1 and 2. Company : Name : Measured fluid : Standard set value Setting item Range (Note 1) Damping 5.0s 1.0 to 99.0s LCD Real scale 1st line indication q Real scale indication indication Volume unit: mL, L, m3 Unit: m3/h Mass unit: g, kg Time unit: /s, /min, /h w Arbitrary real scale unit • Unit factor: 0.00001 to 9999999 • Unit name: Arbitrary value of 4 characters e Percent indication (%) r Total real scale indication Volume unit: mL, L, m3 Mass unit: g, kg t Arbitrary total real scale unit • Unit factor: 0.00001 to 9999999 • Unit name: Arbitrary value of 4 charactes y TAG No. indication LCD 2nd line indication Total real scale indication Unit: m3 u Bar graph indication (Percent indication can also be indicated simultaneously in 1% step) i Non-display Sector : Telephone No. : Put check marks into which precede items to modify for. Item selection or Example value designation . [s] 020.0s According to selection of left item, Select an item from the following. designate necessary item and value. Real scale indication Volume unit: mL, L, m3 Mass unit: g, kg Time unit: /s, /min, /h Arbitrary real scale indication Unit factor: 0.00001 to 9999999 1000000 *Value converted the units into L Item to select Unit name: Percent indication None. Total real scale indication Volume unit: mL, L, m3 Mass unit: g, kg Arbitrary total real scale Unit factor: 0.00001 to indication 9999999 *Value converted the units into L Unit name: TAG No. indication Bar graph indication Non-display Select an item from the following. Real scale indication t None None None According to selection of left item, designate necessary item and value. Volume unit: mL, L, m3 Mass unit: g, kg Time unit: /s, /min, /h Arbitrary real scale indication Unit factor: 0.00001 to 9999999 1000000 *Value converted the units into L Unit name: t/h Percent indication None. Total real scale indication Volume unit: mL, L, m3 Mass unit: g, kg Arbitrary total real scale Unit factor: 0.00001 to indication 9999999 *Value converted the units into L Unit name: t TAG No. indication Bar graph indication Non-display Volume unit: mL, L, m3 Time unit: /s, /min, /h, /d None. None None None Must be designated in 4 significant digits. 100.0 Value: t/h 1000000 1000000 Range By table-1 (Note 5) 0.5 to 10 m/s converted to flow velocity. Instantaneous output low-cut point Total direction Total constant (Note 2) (Total value per pulse) Total pulse width (Note 3) Filter 0.0% 0.0% to 10.0% FORWARD FORWARD/REVERSE Volume unit: mL, L, m3 . None. Value: % 3.5% FORWARD FORWARD /REVERSE (Note4) FORWARD/REVERSE Value: 0.001 to 1000 1m3 Unit : mL, L, m3 30ms 0.1 to 2000ms None. . [ms] 50.0[ms] off on off on off None. 11 FMF1,2/FMH Standard set value Setting item (Note 1) Empty detection off on function off Range on off Item to select Item selection or value designation Alarm output value 3.6mA 4mA 24.8mA Example Upper/Lower Upper limit value limit alarm : 130% Lower limit value : 0% Upper limit value: 0 to 130% Lower limit value: 0 to 130% Specific gravity 1.000g/cm3 TAG-NO Blank unless designated Flow STANDARD direction 0.01 5g/cm3 Up to 16 alphanumerics STANDARD OPPOSITE Alarm output value 3.6mA 4mA Lower limit alarm 24.8mA Upper limit value: Upper/Lower limit alarm     .   % Lower limit value:     .   % None g/cm3 None STANDARD OPPOSITE None Upper limit alarm Upper limit value: 120.0% Lower limit value: 0.0% 0.95g/cm3 F-100 (Note 1) Standard set value refers to parameter set value as factory set in case parameter setting is not designated. (Note 2) Designate so that the number of total pulse outputs will be below 5kHz at the maximum flow rate (to meet the following equation). Range [m3/h] / (total constant [m3] × 3600) 5000 (Note 3) Designate the total pulse width so as to hold: (Total constant [m3]) × 3600/range [m3/h] total pulse width [ms]/500 (Note 4) When selecting FORWARD/REVERSE from the total direction, total pulse is only outputted in the FORWARD direction. (Note 5) Factory-set range before shipment (unless specified). Table-1 Meter size 3A 6A 15A 25A Range [m3/h] 0.05 0.2 1.2 3.5 Meter size 40A 50A 80A 100A Range [m3/h] 14.0 14.0 35.0 55.0 Meter size 150A 200A 250A 300A Range [m3/h] 120.0 220.0 350.0 350.0 (Material selection table of electrode/earth ring) Material of electrode/earth ring SUS316 Measurable liquid Water and waste water, weak acid, weak alkali Example: 25% acetic acid or less, hydroiodic acid, butyric acid, aqueous ammonia or alike Unmeasurable liquid Inorganic acid, organic acid, chloride or alike Hastelloy C-4 or equivalent Suitable for intermediate oxidation and reduction Chloride, high-temperature strong acids (nitric acid, hydrochloric acid, sulfuric acid), and can be used for various fields. Example: Sea water, formic acid, acetic acid, aqueous ferric chloride or alike ammonia, normal-temperature nitric acid and sulfuric acid or alike Resistant to sea water, most oxidative acids, chloride, sulfide and alkali. Example: Sea water, saline water, aqueous ammonia, chlorine water, polyelectrolyte, acetic acid, ferric chloride or alike Resistant to most chemicals. (particularly, strong acids) Example: Hydrochloric acid, sulfuric acid, nitric acid, aqua regia, ferric chloride, hypochlorous acid, sodium hypochlorite, PAC (Polyaluminum chloride) or alike Resistant to almost chemicals. Reductive acids such as hydrochloric acid, sulfuric acid, phosphoric acid, oxalic acid Titanium Tantalum Sodium hydroxide, potassium hydroxide, hydroflouric acid, fuming sulfuric acid or alike Platinum-iridium (Pt-Ir) Aqua regia (Note): The electrode/earth ring for E-series electromagnetic flowmeter use Hastelloy C-4 or equivalent. If other material except Hastelloy C-4 is required, select a model that uses other material from the separate type electromagnetic flowmeter (FMB/C series) of Fuji Electric. Caution on Safety *Before using this product, be sure to read its instruction manual in advance. Head Office 6-17, Sanbancho, Chiyoda-ku, Tokyo 102-0075, Japan http://www.fesys.co.jp/eng Sales Div. International Sales Dept. No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187 http: //www.fic-net.jp/eng Information in this catalog is subject to change without notice. Printed in Japan
EDS6-120 价格&库存

很抱歉,暂时无法提供与“EDS6-120”相匹配的价格&库存,您可以联系我们找货

免费人工找货