FC SERIES PT TYPE DISTRIBUTOR (48mm width)
DATA SHEET
The FC series PT type distributor converts a current signal (4 to 20mA DC) from the transmitter into a voltage signal (1 to 5V DC ) then distributes the voltage signal to each receiver. In addition, the distributor is provided with built-in transmitter power supply. Its structure is plug-in style.
PTL
SPECIFICATIONS
INPUT SPECIFICATION
Input signal: 1 point
Input type Input signal Input resistance Current 4 to 20mA DC 250Ω
OUTPUT SPECIFICATION
Output signal: 2 points
Output type Output signal Voltage 1 to 5 V DC
Allowable load re- 500k Ω o r over (reception, non-insulation) 15kΩ or over sistance (with output buffer)
POWER SUPPLY
Power supply: 24V DC (20 to 30V DC) 24V AC, +13%, –10%,(47 to 63Hz) 100V AC (85 to 132V AC / 47 to 63Hz) 200V AC (187 to 264V AC / 47 to 63Hz) as specified. Power consumption: Approx. 2W (at DC power) Approx. 6VA (at AC power)
Reception only: Input/Output - Ground Non-insulation type: Input/Output•Power - Ground Non-insulation with buffer: Input/Output•Power - Ground Power insulation with buffer: Input/Output - Power - Ground Power I/O insulation with buffer: Input - Output - Power - Ground Ambient temperature effect: Less than ± 0.15% of full span/10°C Power regulation effect: Less than ± 0.1% of full span
CODE SYMBOLS
12345678
OPERATION CONDITION
Ambient temperature: 0 to 50°C Ambient humidity: Less than 90%RH (no condensation) Outline dimension (HxWxD): 96 x 52 x130mm Mass: Appox. 300g Housing: Plastic housing (color: black) Mounting method: Panel mounting or DIN rail mounting
PLT2V 2 V A0 B1 C1 D1 E1 D2 E2 D3 E3
1 Input signal 4 to 20mA DC Output signal 1 to 5V DC
Description
CHARACTERISTICS
Accuracy: Less than ± 0.1% of full span Response time: Less than 0.1 sec. (90% response) Dielectric strengh: 1500V AC, 1 min. (indicated below) Insolation resistance: 500V DC, 100MΩ or over (indicated below)
Output system Reception only Non-insulation type Non-insulation with buffer Power insulation with buffer Power I/O insulation with buffer Power insulation with buffer Power I/O insulation with buffer Power insulation with buffer Power I/O insulation with buffer
Power supply None 24V DC 24V DC 24V DC/ 24V AC (50/ 60Hz) 24V DC/24V AC (50/ 60Hz) 100V AC (50/60Hz) 100V AC (50/60Hz) 200V AC (50/60Hz) 200 V AC (50/60Hz)
EDS9-24a
Date Feb. 20, 1996
PTL
FUNCTIONAL DIAGRAM
1. Reception only type
11 12 250Ω
31 Output 1 32
Transmitter (4 to 20mA DC)
41 21 42 22 34 Output 2
2. Non-insulation type
11 12
Power restric circuit
31 Output 1 32 41
Transmitter (4 to 20mA DC)
21 42 22 250Ω 43
Output 2
Power 44 34
3. Power insulation with buffer
11 12
Power restric circuit
31 Output 1 32 41
Transmitter (4 to 20mA DC)
21 42 22 Power circuit 250Ω 34 43
Output 2
Power 44
4. Power input/output insulation with buffer
11 12
Current limiting circuit Signal insulation circuit
31 Output 1 32 41 Output 2 42
Transmitter (4 to 20mA DC)
21 22 Power circuit 250Ω 34 43
Power 44
OUTLINE DIAGRAM (Unit: mm)
Terminal screw M4 Main unit Terminal screw M2.5 (for transmission)
74
94
35
Terminal
48 52 100 130
2
Stopper
Panel mounting
DIN rail mounting
2-M4
DIN rail
40 52
Stopper
PTL
EXTERNAL CONNECTION DIAGRAM
General
(non-insulation type, power insulation type, power I/O insulation type)
Reception only type
+
-
+
-
11 12 + 21 22 5 6 31 32 + OUTPUT
13 14
11 12 + 21 22 5 6
13 14
23 24
23 24
33 34
31 32 + OUTPUT
33 34
41 42 + OUTPUT
43 44 + POWER
41 42 + OUTPUT
43 44
RANGE OF DELIVERY
Main unit and socket
Caution on Safety *Before using this product, be sure to read its instruction manual in advance.
Head Office
Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome, Shinagawa-ku, Tokyo 141-0032, Japan http://www.fesys.co.jp/eng
Instrumentation Div. International Sales Dept.
No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187 http://www.fic-net.jp/eng
Information in this catalog is subject to change without notice.
Printed in Japan