FFI SYSTEM
OPTICAL SIGNAL CONVERTER
DATA SHEET
The optical signal converter performs conversion between optical and electrical signals of FFI system specifications, and serves as an interface when connecting a detector or controlled element of an electronic instrumentation system to the FFI system. This is a high-precision intelligent instrument with a built-in microcomputer for digital processing of signals. Optical fiber is used in the signal transmission section which enables forming an optical fiber type field instrumentation system (FFI system) together with optical star coupler and master station.
FRK
FEATURES
1. Bidirectional transmission system Transmission of measured data and fault diagnosis data to the host computer and remote settings etc. from the host is done bidirectionally via a signal optical fiber cable. 2. Easy adjustment and setting operation Adjustment and settings can be made easily via remote operation from the host computer or by key switches on the indicating unit (option). 3. Self-diagnosis function A number of self-diagnoses are possible by the builtin microcomputer. 4. Digital display type field indicator available at option. 5. Flame-proof structure (d2G4) can be provided at option.
SPECIFICATIONS
Functional Specifications
Optical/electrical conversion output signal: 4 to 20mA DC (allowable load 600Ω) Electrical/optical conversion input signal: 1 to 5V DC (input resistance 1M Ω o r more) 4 to 20mA DC (input resistance 150 Ω or less) (None) 10 to 50mA DC (input resistance 80 Ω or less) Note) The power for a 2-wire type transmitter and converter for 4 to 20mA DC can also be supplied (supply voltage about 20V DC). Power supply: 24V DC (20 to 30V) or 24, 100, 115, 220V AC ( ± 10%), 50/60Hz
Power consumption: About 4W (DC power supply) or about 8VA (AC power supply) Setting: • Damping time constant up to 17 sec • Optical/electrical conversion output 0% and 100% calibration, readback 0% and 100% calibration • Electrical/optical conversion output 0% and 100% calibration Self-diagnosis: • Input overflow/underflow, microcomputer fault, battery down (for memory backup) • Optical/electrical D/A converter fault • External line disconnection fault Display (option): • Optical/electrical converter readback value (0 to 100%) • Electrical/optical conversion input value (0 to 100%) • Symbols and numerals for above setting items • Symbols for above diagnosis items … only at fault occurrence But microcomputer fault is not displayed since it is normalized through auto reset action. Ambient temperature: –20 to 60°C Ambient humidity: 95% R.H. or less Transmission: Half-duplex bidirectional transmission with one-fiber system Transmission distance; 1.2 km max.
EDS9-44e
Date Dec. 30, 1987
FRK
Other: Optical output alone can be provided by combining the electrical/optical converter with an optical receiving converter (type PRN). In this case the transmission distance is 4 km max.
Structure and Material
Finish: Epoxy/polyurethane double coating, silver (cover; blue) Enclosure: JIS C 0920 immersion-proof (equivalent to IEC IP65 or NEMA 4) Outer dimensions (H x W x D) and Mass (weight): 161 x 172 x 212 (240) mm, about 4.0 kg Parenthesized dimension is when display unit equipped. Mounting method: Mounted by U bolt on horizontal or vertical 50A (2B) pipe, or wall mounted Cable and connection method: JIS G1/2 internal thread (Terminals: M4 screw) Optical fiber cable is Fuji-specified one (prepare separately) Connection is made by optical connector.
Performance Specifications
Accuracy rating: ± 0.2% Repeatability: ± 0.1% Ripple content: 1% P–P (optical electrical converter output current) Insulation: (in arrester exclusion status) Between power supply and signals Insulation resistance; 500MΩ or more (with 500V DC megger) Withstand voltage; 1000V AC for 1 minute Between power supply and ground Insulation resistance; 500MΩ or more (with 500V DC megger) Withstand voltage; 1000V AC for 1 minute Between signals and ground Insulation resistance; 500MΩ or more (with 500V DC megger) Withstand voltage; 500V AC for 1 minute
Optical Specifications
Indication unit: 6-digit LCD unit with setting key (4 pushbutton switches) Acid and alkali-proof treatment: Mounting U bolt and nuts material: SUS304
CODE SYMBOLS
12345678 9 10 11
FRK 1 2 3
1-
Description
Kind Optical/electrical conversion Electrical/optical conversion Electrical/optical conversion transmitter power supply built in
Y A B C A B 1 2 3 4 5 0 2 1 3 4 Y B
Input/output signals FFI optical signal/4 to 20mA DC (unusable with 2, 3 in 4th digit) 1 to 5V DC/ FFI optical signal (unusable with 1, 3 in 4th digit) 4 to 20mA DC/ FFI optical signal (unusable with 1 in 4th digit) 10 to 50mA DC/ FFI optical signal (unusable with 1, 3 in 4th digit) Indicating unit None Equipped Power supply 24V DC 24V AC, 50/60Hz 100V AC, 50/60Hz 115V AC, 50/60Hz 220V AC, 50/60Hz Arrester None Equipped Enclosure Immersion-proof case, non-explosion-proof Flame-proof case (conduit flame-proof screw coupling type) Flame-proof case (flame-proof packing type) Treatment None Acid/alkali-proof processing
2
OUTLINE DIAGRAM (Unit : mm)
Indicating unit (optional specification) 172 119 53 Optical connection
ø105 60 108
(28)
212 109 Conduit cnnection (See "Details of A")
ø45 Indicating unit (optional specification)
Pipe mouting 73 129
Details of A ø15
161
152
173
G1/2 (JIS)
Mounting pipe JIS50A (2B)
M8 U bolt
Wall mouting
100 47
152
70
16
5
3
FRK
OPERATING PRINCIPLE DIAGRAM
Optical/electrical converter
Indicating unit (option)
Display Setting Optical connector
Optical unit µ-Com Output circuit Readback circuit DC 4 to 20mA
Electrical/optical converter
Display unit (option)
Display Setting Optical connector
Optical unit µ-Com
Input circuit
DC 1 to 5V 4 to 20mA 10 to 50mA
SYSTEM BLOCK DIAGRAM
Signal converter FRK Electrical signal Optical fiber, 8 lines max. Optical star coupler FXN Optical fiber, 4 lines max. Master station PMT,PMH Electrical signal
Power supply
Power supply
Signal converter(E/O) FRK 2 3 Electrical signal Optical fiber cable
Optical receiving converter PRN Output signal DC 1 to 5V or DC 4 to 20mA Power supply
Power supply
4
EXTERNAL CONNECTION DIAGRAM
Optical/electrical converter Electrical/optical converter
Power supply
Power supply
PC
PS
PC
PS
CK
O+
O-
CK
I-
I+
Current check terminal (Note 1) DC 4 to 20mA Current check terminal (Note 2) DC 1 to 5V DC 4 to 20mA DC 10 to 50mA
Note 1. O/E converter current can be checked at the CK (check) terminal and "0+" terminal Connect the "+" side of the check current ammeter (Internal resistance is less than 10Ω) to CK and the "–" side to "+0". 2. E/O converter current input can be checked at CK and I – terminals. Connect the "+" side of the check current ammeter to CK and the "–" side to I –. (Internal resistance of 4 to 20mA check current ammeter is less than 10Ω and that of 10 to 50mA check current ammeter is less than 4Ω).
SCOPE OF DELIVERY
Converter and mounting bracket
RELATED DEVICES
• • • • • •
Master station (Data sheet No. EDS11-86) Optical star coupler (Data sheet No. EDS8-43) Optical receiving converter (Data sheet No. EDS9-43) Optical connector Optical fiber cable Optical connector assembling tools
5
FRK
Caution on Safety *Before using this product, be sure to read its instruction manual in advance.
Head Office
6-17, Sanbancho, Chiyoda-ku, Tokyo 102-0075, Japan http://www.fesys.co.jp/eng
Sales Div. International Sales Dept.
No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187 http: //www.fic-net.jp/eng
Information in this catalog is subject to change without notice.
Printed in Japan
很抱歉,暂时无法提供与“EDS9-44E”相匹配的价格&库存,您可以联系我们找货
免费人工找货